Plan Review Details - Permit 18010478
Plan Review Stops For Permit 18010478
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-05-11 Cont ID  
Sent By skennedy Date 2018-05-11 Time 09:19 Rev Time 0.00
Received By skennedy Date 2018-05-11 Time 09:19 Sent To  
Notes
2018-05-21 14:51:52PENDING UPDATE OF LICENSE & INSURANCE AS APPLICABLE FOR
 GC & TWO OF THE SUBS, INFORMED ALFONSO..

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-05 Cont ID  
Sent By rmcdouga Date 2018-04-05 Time 17:32 Rev Time 0.00
Received By rmcdouga Date 2018-04-05 Time 07:36 Sent To  
Notes
2018-04-05 15:52:08PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEW COMMENT: A SURVEY WAS SUBMITTED, HOWEVER, THE
 PLANS INDICATE THAT THE EXISTING STORAGE STRUCTURE IS
 16' X 26' AND THE MIDDLE BUILDING ON THE SURVEY IS
 16.2' X 32'. PLEASE PROVIDE CLARIFICATION.
  
 2) (PREVIOUS COMMENT.) PROVIDE THE WINDSPEED DATA AND
 EXPOSURE CATEGORY ON THE PLANS. SPECIFY THE REQUIRED
 COMPONENT AND CLADDING DESIGN PRESSURES ON THE PLANS.
 FBC-R301.2.1
  
 3) (PREVIOUS COMMENT.) IN ORDER TO CLARIFY THE WORK
 THAT WILL BE DONE, PROVIDE AN EXISTING FLOOR PLAN AND A
 PROPOSED FLOOR PLAN. FBC 107.2.1
  
 4) (PREVIOUS COMMENT.) SPECIFY THE LEVEL OF ALTERATION
 ON THE PLANS. FBC EXISTING BUILDING CHAPTER 5. THIS
 APPEARS TO BE A LEVEL 3 ALTERATION. NEW COMMENTS: THIS
 PROJECT IS A CHANGE OF USE THAT DOES NOT INVOLVE A
 CHANGE IN OCCUPANCY CLASSIFICATION PER FBC EXISTING
 BUILDING 1001.2.1.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED. THE ALTERATION WILL NOT CREATE ANY
 ADDITIONAL LOADS TO THE EXISTING STRUCTURE. EVALUATION
 REPORT NOT REQUIRED.
  
 9) COMPLIED. THE EXISTING WINDOWS AND DOORS WERE
 INSTALLED UNDER SEPARATE PERMIT # 91BA03568 AND
 #94008097.
  
 10) (PREVIOUS COMMENT.) FBC - R 301.2.1.2 SUBMIT TWO
 COPIES OF AN INSTALLATION SCHEDULE AND KEY PLAN FOR THE
 STORM PANELS. SPECIFY THE OPENING SIZE, THE WIND
 PRESSURES, TYPE OF ANCHOR, ANCHOR SPACING, EDGE
 DISTANCE, PANEL LENGTH, PANEL SPAN, SEPARATION DISTANCE
 FROM PANEL TO GLASS AND THE APPLICABLE SECTION NUMBER
 FROM THE INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK
 TO THE CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS
 MANY OF THE RELATED FORMS INCLUDING THE SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-16 Cont ID  
Sent By rmcdouga Date 2018-02-16 Time 18:17 Rev Time 0.00
Received By rmcdouga Date 2018-02-16 Time 08:27 Sent To I
Notes
2018-02-16 08:32:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) BASED ON AERIAL PHOTOS, THERE APPEARS TO BE THREE
 BUILDINGS ON THIS LOT. SUBMIT TWO COPIES OF A RECENT
 SURVEY AND SITE PLAN THAT SHOWS ALL OF THE STRUCTURES
 THAT ARE LOCATED ON THE PROPERTY. IDENTIFY THE EXISTING
 UTILITY SHED THAT WILL BE CONVERTED TO HABITABLE SPACE
 AND THE DISTANCES FROM THE SHED TO PROPERTY LINES AND
 OTHER STRUCTURES ON THE PROPERTY. FBC-R302.1
  
 2) PROVIDE THE WINDSPEED DATA AND EXPOSURE CATEGORY ON
 THE PLANS. SPECIFY THE REQUIRED COMPONENT AND CLADDING
 DESIGN PRESSURES ON THE PLANS. FBC-R301.2.1
  
 3) IN ORDER TO CLARIFY THE WORK THAT WILL BE DONE,
 PROVIDE AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR
 PLAN. FBC 107.2.1
  
 4) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS. FBC
 EXISTING BUILDING CHAPTER 5. THIS APPEARS TO BE A LEVEL
 3 ALTERATION.
  
 5) THE ENERGY CALCULATIONS ARE ON AN OUTDATED 2014
 FORM. THE FBC SIXTH EDITION (2017) WENT INTO EFFECT ON
 JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR ON OR
 AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC SIXTH EDITION (2017).
  
 6) THE ENERGY CALCULATIONS SPECIFY A BEDROOM. THE CARD
 ROOM ON THE PLANS HAS A CLOSET AND APPEARS TO BE A
 BEDROOM. BEDROOMS/SLEEPING ROOMS ARE REQUIRED TO HAVE
 AN EMERGENCY ESCAPE AND RESCUE OPENING (FBC-R310) AND
 SMOKE ALARMS (FBC-R314). IF THIS ROOM WILL NOT BE USED
 AS A BEDROOM, THEN PRINT "THIS ROOM IS NOT TO BE USED
 FOR FOR SLEEPING PURPOSES" ON THE PLANS.
  
 7) THE ENERGY CALCULATIONS SPECIFY A KITCHEN. THE
 ZONING CODE DOES NOT ALLOW A KITCHEN IN THIS ACCESSORY
 STRUCTURE. CORRECT THE ENERGY CALCULATIONS AND PRINT ON
 THE PLANS THAT A KITCHEN IS NOT ALLOWED. FBC 107.2.1
  
 8) FBC EXISTING BUILDING 907.4.1 SUBMIT TWO COPIES OF
 AN ENGINEERING EVALUATION AND ANALYSIS THAT ESTABLISHES
 THE STRUCTURAL ADEQUACY OF THE ALTERED STRUCTURE SHALL
 BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE CODE OFFICIAL.
  
 9) UNDER PREVIOUS PERMIT
  
 10) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN
 INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES,
 TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL
 LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO
 GLASS AND THE APPLICABLE SECTION NUMBER FROM THE
 INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE
 CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF
 THE RELATED FORMS INCLUDING THE SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-05-11 Cont ID  
Sent By skennedy Date 2018-05-11 Time 09:20 Rev Time 0.00
Received By skennedy Date 2018-05-11 Time 09:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-12 Cont ID  
Sent By ppetty Date 2018-04-12 Time 13:09 Rev Time 0.00
Received By ppetty Date 2018-04-12 Time 13:09 Sent To  
Notes
2018-04-12 13:09:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION FOR MAIN SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 2. PANEL B, PROVIDE GROUNDING ELECTRODE SYSTEM AS
 REQUIRED FOR A BUILDING OR STRUCTURE SUPPLIED BY A
 FEEDER OR BRANCH CIRCUIT. NEC 250.32; FBC RE3607.3
 3. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL B. NEC 225.31,
 225.32
 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 5. SMOKE ALARM MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR. PROVIDE CORRECTION. FBC RE R314.3(4)
 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER, CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-09 Cont ID  
Sent By jpearson Date 2018-02-09 Time 10:31 Rev Time 0.00
Received By jpearson Date 2018-02-09 Time 10:31 Sent To  
Notes
2018-02-09 10:31:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION FOR MAIN SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 2. PANEL B, PROVIDE GROUNDING ELECTRODE SYSTEM AS
 REQUIRED FOR A BUILDING OR STRUCTURE SUPPLIED BY A
 FEEDER OR BRANCH CIRCUIT. NEC 250.32; FBC RE3607.3
 3. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL B. NEC 225.31,
 225.32
 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 5. SMOKE ALARM MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR. PROVIDE CORRECTION. FBC RE R314.3(4)
 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-05-21 Cont ID  
Sent By skennedy Date 2018-05-21 Time 14:45 Rev Time 0.00
Received By skennedy Date 2018-05-18 Time 13:10 Sent To  
Notes
2018-05-21 13:10:25RESUB ROUTED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-11 Cont ID  
Sent By skennedy Date 2018-05-11 Time 11:28 Rev Time 0.00
Received By skennedy Date 2018-05-11 Time 09:18 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-18 Cont ID  
Sent By shill Date 2018-04-18 Time 08:49 Rev Time 0.00
Received By shill Date 2018-03-28 Time 10:31 Sent To  
Notes
2018-03-29 10:31:53R04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-16 Cont ID  
Sent By rmcdouga Date 2018-02-16 Time 18:18 Rev Time 0.00
Received By rmcdouga Date 2018-01-16 Time 11:20 Sent To  
Notes
2018-01-17 11:20:59R05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-05-21 Cont ID  
Sent By skennedy Date 2018-05-21 Time 14:44 Rev Time 0.00
Received By skennedy Date 2018-05-11 Time 09:18 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-02-16 Cont ID  
Sent By rmcdouga Date 2018-02-16 Time 08:32 Rev Time 0.00
Received By rmcdouga Date 2018-02-16 Time 08:32 Sent To  
Notes
2018-02-16 08:33:41BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-05-11 Cont ID  
Sent By skennedy Date 2018-05-11 Time 09:20 Rev Time 0.00
Received By skennedy Date 2018-05-11 Time 09:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-05-11 Cont ID  
Sent By skennedy Date 2018-05-11 Time 09:19 Rev Time 0.00
Received By skennedy Date 2018-05-11 Time 09:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-17 Cont ID  
Sent By cmontell Date 2018-04-17 Time 13:55 Rev Time 0.00
Received By cmontell Date 2018-04-17 Time 13:55 Sent To  
Notes
2018-04-17 13:55:511 - PER FBC. SEC 107 MANUAL J AND PLANS NEED TO MATCH

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-07 Cont ID  
Sent By cmontell Date 2018-02-07 Time 15:25 Rev Time 0.00
Received By cmontell Date 2018-02-07 Time 15:24 Sent To  
Notes
2018-02-07 15:27:141 - PER FBC. SEC 107 MANUAL J AND PLANS NEED TO MATCH

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-05-11 Cont ID  
Sent By skennedy Date 2018-05-11 Time 09:19 Rev Time 0.00
Received By skennedy Date 2018-05-11 Time 09:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-30 Cont ID  
Sent By lcrespo Date 2018-03-30 Time 15:18 Rev Time 0.00
Received By lcrespo Date 2018-03-30 Time 15:18 Sent To  
Notes
2018-03-30 15:38:4503/30/18 APPROVED BY PLUMBING AND PUT BACK IN R04, LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-09 Cont ID  
Sent By thunt Date 2018-02-09 Time 06:43 Rev Time 0.00
Received By thunt Date 2018-02-09 Time 06:43 Sent To  
Notes
2018-02-09 06:46:4102/09/2018 PLUMBING 1ST REVIEW**DEINED**
  
 1) YOU DO NOT SHOW THE REQUIRED VENT TO THE OUTDOORS ON
 THE ISOMETRIC SYSTEM AS REQUIRED PER FBC-P 904.1
  
 2) PIPE FITTINGS SHALL BE INSTALLED TO GUIDE SEWAGE AND
 WASTE IN THE DIRECTION OF FLOW. FBC-P 706.3
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-04-09 Cont ID  
Sent By skennedy Date 2018-05-11 Time 11:28 Rev Time 0.00
Received By awooten Date 2018-04-09 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-01-18 Cont ID  
Sent By AW Date 2018-01-18 Time 15:29 Rev Time  
Received By awooten Date 2018-01-18 Time   Sent To  
Notes
2018-01-18 15:28:58***************************************ZONING REVIEW
 FAILED****************************************
  
 PROVIDE A COPY OF THE SURVEY SHOWING ALL EXISTING
 SETBACKS. FURTHER COMMENTS MAY FOLLOW.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]