Plan Review Details - Permit 18010391
Plan Review Stops For Permit 18010391
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-26 Cont ID  
Sent By rmcdouga Date 2018-03-26 Time 17:31 Rev Time 0.00
Received By rmcdouga Date 2018-03-26 Time 16:30 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-02 Cont ID  
Sent By rmcdouga Date 2018-02-02 Time 18:16 Rev Time 0.00
Received By rmcdouga Date 2018-02-02 Time 08:25 Sent To I
Notes
2018-02-02 18:15:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE FBC FIFTH
 EDITION (2014). THE FBC SIXTH EDITION (2017) WENT INTO
 EFFECT ON JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR
 ON OR AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC SIXTH EDITION (2017).
  
 2) CORRECT NOTE #1 IN THE DETAIL LEGEND ON SHEET 3.0.
 THE WORD HEATHER SHOULD BE CHANGED TO HEADER TO AVOID
 ANY CONFUSION. FBC 107.2.1
  
 3) THE PLANS ARE SIGNED AND SEALED BY AN ENGINEER,
 THEREFORE, ONLY THE ENGINEER CAN MAKE CHANGES TO THE
 DRAWINGS. ADD THE LAUNDRY ROOM DOOR AND WINDOW
 REPLACEMENT TO THE DRAWINGS. SPECIFY THE DOOR AND
 WINDOW SIZES ON THE PLANS. FS 471
  
 4) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 EXTERIOR LAUNDRY ROOM DOOR DO NOT HAVE THE FLORIDA FL
 NUMBER ON THEM. SUBMIT TWO SETS OF THE COVER SHEET FOR
 THE DOOR WITH THE FL#. FAC 61G20-3.001
  
 5) THE PRODUCT APPROVAL FOR THE EXTERIOR DOOR IS
 REQUIRED TO BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD FOR THE PROJECT. FBC 107.3.4.1

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-12 Cont ID  
Sent By jpearson Date 2018-03-12 Time 16:08 Rev Time 0.00
Received By jpearson Date 2018-03-12 Time 16:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-30 Cont ID  
Sent By jpearson Date 2018-01-30 Time 13:48 Rev Time 0.00
Received By jpearson Date 2018-01-30 Time 09:11 Sent To  
Notes
2018-01-30 13:48:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODE ABOVE)
 2. BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 3. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 4. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 .
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-27 Cont ID  
Sent By hmoser Date 2018-03-27 Time 11:01 Rev Time 0.00
Received By hmoser Date 2018-03-08 Time 13:19 Sent To I
Notes
2018-03-09 13:20:07R25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-02 Cont ID  
Sent By rmcdouga Date 2018-02-02 Time 18:16 Rev Time 0.00
Received By rmcdouga Date 2018-01-11 Time 14:43 Sent To  
Notes
2018-01-16 14:43:11R18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-03-27 Cont ID  
Sent By hmoser Date 2018-03-27 Time 11:01 Rev Time 0.00
Received By hmoser Date 2018-03-27 Time 10:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-31 Cont ID  
Sent By hmoser Date 2018-01-31 Time 11:38 Rev Time 0.00
Received By hmoser Date 2018-01-31 Time 11:06 Sent To  
Notes
2018-01-31 11:38:13PLAN DENIED
 1) PROVIDE AHRI SHEET FOR MISMATCHED
 AIR CONDITIONING EQUIPMENT. PER SECTION
 107 FBC 2017
 2) PROVIDE LOCATION AND SIZE OF MAIN
 RETURN AIR. SECTION 107 FBC 2017
 3) REFER TO SECTION M1602.3
 BALANCED RETURN AIR 2017
 RESIDENTIAL CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-16 Cont ID  
Sent By lcrespo Date 2018-03-16 Time 18:19 Rev Time 0.00
Received By lcrespo Date 2018-03-16 Time 18:19 Sent To  
Notes
2018-03-16 18:20:3103/16/18 APPROVED BY PLUMBING AND PUT BACK IN R25, LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-29 Cont ID  
Sent By gjohnson Date 2018-01-29 Time 14:07 Rev Time 0.00
Received By gjohnson Date 2018-01-29 Time 09:58 Sent To  
Notes
2018-01-29 14:13:491ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. LAVATORY SHOWN WITHOUT VENT SHOW VENT O LAVATORY NOT
 THE TOILET. PER FBC PL 901.2.1
  
 2. THE SHOWER VALVE SHALL COMPLY WITH FBC PL 424.3
 PLACE NOT ON PLAN.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  