Plan Review Details - Permit 18010368
Plan Review Stops For Permit 18010368
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-11 Cont ID  
Sent By dharvey Date 2018-06-11 Time 12:20 Rev Time 0.00
Received By dharvey Date 2018-06-11 Time 12:20 Sent To  
Notes
2018-06-11 12:20:37RESIDENT INSPECTOR AGREEMENT REMOVED. PROVISOS AND
 DEFERRED SUBMITTALS NOTED ON PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-28 Cont ID  
Sent By jwitmer Date 2018-03-28 Time 08:54 Rev Time 0.00
Received By jwitmer Date 2018-03-28 Time 07:24 Sent To  
Notes
2018-03-28 08:02:482017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010368
 ADD: 2481 OKEECHOBEE BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-822-7650
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MARCH 28, 2018
 ACTION: DENIED.
  
 1)PROVISO: DEFERRED SUBMITTAL / 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, INTAKE AND EXHAUST
 FANS & ROOF TOP VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 2) PROVISO: PLEASE IDENTIFY ON THE PRODUCT APPROVAL
 BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS
 WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH &
 HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH IF
 UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 3)PROVISO: ROOFING: FOR ALL ROOFING PRODUCTS PLEASE
 IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED
 PRESSURES FOR ROOF ZONE # 1. REVIEW THE PRODUCT
 APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED
 FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL BE
 INCREASED FOR BOTH INSULATION & THE BASE SHEET AS
 CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 4)PROVISO: SHEET S-403 DETAIL # 1 SHOW A NEW MECHANICAL
 STAND WITH A VERTICAL DISTANCE MEASURED 48 INCHES FROM
 THE TOP OF THE BAR JOIST TO THE BOTTOM OF THE
 CONDENSING UNIT. THE 2017 FBC-B TABLE 1510.10 STATES
 CLEARANCE BELOW RAISED ROOF MOUNTED MECHANICAL UNITS.
 FOR A UNIT 60 INCHES IN WIDTH OR WIDER THERE IS TO BE
 48 INCHES OF CLEARANCE. THE WAY THE DISTANCE IS
 MEASURED YOU DO NOT HAVE 48 INCHES CLEARANCE.
 DEFINITION: THE DISTANCE BY WHICH ONE OBJECT CLEARS
 ANOTHER OR THE CLEAR SPACE BETWEEN THEM.
  
 5) PROVISO: THE S-403 DETAIL 1 NOR THE H DRAWINGS SHOW
 HOW THE ROOF TOP CONDENSERS ARE GOING TO BE ANCHORED TO
 RESIST SLIDING OR THE MOMENT OF OVERTURNING. 2017 FBC-B
 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND
 THEIR CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY
 STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING
 EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND LOADS.
  
 6-8) COMPLIED.
  
 9) THE RESPONSE INDICATED THE TENANT WOULD LIKE A
 RESIDENT INSPECTOR ON SITE FOR THE STEEL AND CONCRETE
 WORK. FORMS WERE E-MAILED TO:
 [email protected] CAME BACK UNDELIVERABLE
 [email protected] 3/27/2018 04:46 PM
  
 FORMS NEED TO BE SIGNED AND RETURNED BEFORE PERMIT
 ISSUANCE.
  
 ONLY (2) SETS OF PLANS WERE SUBMITTED, (3) SETS
 REQUIRED FOR RESIDENT INSPECTOR!!!!!!!
  
 10) COMPLIED.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-01 Cont ID  
Sent By jwitmer Date 2018-02-01 Time 16:19 Rev Time 0.00
Received By jwitmer Date 2018-02-01 Time 07:01 Sent To  
Notes
2018-02-01 16:19:182017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010368
 ADD: 2481 OKEECHOBEE BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-822-7650
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. FEB. 01/ 2018
 ACTION: DENIED
  
 1) SHEET A-101: AT DOOR 102B THERE IS A SECTION THROUGH
 THE DOOR NO NOMENCLATURE, NOT COMPLETE XX/XXX.
 ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.3. UNKNOWN
 IF THE EXISTING DOOR IS A 3 FOOT DOOR THAT IS BEING
 INCREASED TO A 4 FOOT WIDE DOOR THE STRUCTURAL PLAN
 S-102 IS ALSO SILENT ON THIS DOOR OPENING?
  
 2) SHEET A-601:
 2A) PLEASE REVIEW THE DOOR SCHEDULE 101A IS LABELED 7
 FT. 6 IN. LISTED AS ELEVATION DD BUT THE DETAIL
 INDICATES THE DOOR TO BE 8 FT. THEN VERIFY. DISCREPANCY
 IN HEIGHT. THE STRUCTURAL SHEET S-201 SOUTH ELEVATION
 FRAMING SHOWS A HORIZONTAL 6X6 HSS STEEL BEAM BUT NO
 ELEVATION IS GIVEN, SHEET S-401
 DETAIL # 4 SHOWS THE SAME 6X6 HSS STEEL BEAM AND NO
 ELEVATION IS PROVIDED. AGAIN NO ELEVATION HAS BEEN
 PROVIDED FOR THIS BEAM.
  
 2B) SHEET A-101 SHOWS DOORS 101B & 101C BOTH AS A
 SINGLE SWING DOOR, SHEET A-601 DEPICTS THESE DOORS AS
 TYPE EE. SHEET A-602 INDICATES BOTH SETS OF DOORS ARE
 AUTO SLIDING DOORS. PLEASE NOTE AS DEPICTED THERE IS NO
 HORIZONTAL MULLION BETWEEN THE UPPER TRANSOM AND AUTO
 DOOR MECHANISM HOUSING.
 NOTE ALSO INDICATES THAT THE AUTOMATIC DOORS ARE
 PROVIDED BY A ALDI VENDOR. ARE THE DOORS NEW DOORS, OR
 RE-USED DOORS? IS THE VENDOR TO BE COVERED UNDER THIS
 PERMIT? DOES THE ALDI VENDOR HAVE FLORIDA CONTRACTING
 LICENSURE TO DO THIS TYPE OF INSTALLATION?
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3) SHEET G-002 LIST 9 PRODUCT APPROVALS, THESE PRODUCT
 APPROVALS WERE NOT SUBMITTED THIS REVIEW CYCLE. THE
 DESIGNER OF RECORD CAN DEFER THE SUBMISSION OF THESE
 APPROVALS UNTIL AFTER PERMIT ISSUANCE. PLEASE NOTE IN
 THE NARRATIVE RESPONSE IF THE PRODUCT APPROVALS ARE TO
 BE CONSIDERED A DEFERRED SUBMITTAL.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 4) REQUIRED PRODUCT APPROVALS. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, INTAKE AND EXHAUST
 FANS & ROOF TOP VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 5) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 7A) SHEET S-403 DETAIL # 1 SHOW A NEW MECHANICAL STAND
 WITH A VERTICAL DISTANCE MEASURED 48 INCHES FROM THE
 TOP OF THE BAR JOIST TO THE BOTTOM OF THE CONDENSING
 UNIT. THE 2017 FBC-B TABLE 1510.10 STATES CLEARANCE
 BELOW RAISED ROOF MOUNTED MECHANICAL UNITS. FOR A UNIT
 60 INCHES IN WIDTH OR WIDER THERE IS TO BE 48 INCHES OF
 CLEARANCE. THE WAY THE DISTANCE IS MEASURED YOU DO NOT
 HAVE 48 INCHES CLEARANCE.
 DEFINITION: THE DISTANCE BY WHICH ONE OBJECT CLEARS
 ANOTHER OR THE CLEAR SPACE BETWEEN THEM.
  
 7B) THE S-403 DETAIL 1 NOR THE H DRAWINGS SHOW HOW THE
 ROOF TOP CONDENSERS ARE GOING TO BE ANCHORED TO RESIST
 SLIDING OR THE MOMENT OF OVERTURNING. 2017 FBC-B 1604.4
 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR
 CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY
 STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING
 EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND LOADS.
  
 8) SHEET S-002. PRESSURES FOR ROOF ZONES ARE GOOD, THE
 PRESSURES FOR WALL ZONES 4 & 5 APPEAR LOW. 2017 FBC-B
 1603.1.4 WIND DESIGN DATA. ASSUMED MEAN ROOF HEIGHT OF
 25 FEET.
 WALL ZONE 4 AT 10 SQ FT. 3.6 PSF LOW
 20 SQ . FT.3.2 PSF LOW
 50 SQ. FT. 2.8 PSF LOW
 100 SQ. FT. 1.2 PSF LOW
  
 WALL ZONE 5 AT 10 SQ. FT. 3.4 PSF LOW
 20 SQ. FT. 3.2 PSF LOW.
 50 SQ. FT. 3.0 PSF LOW.
 100 SQ. FT. 1.1 PSF LOW.
  
 9) PLEASE NOTE THIS PROJECT MAY BE CONSIDERED FOR A
 RESIDENT INSPECTOR PROGRAM BECAUSE OF THE STEEL OR THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 10) THE SHEET A-131 SHOWS 6 CHECKOUT LANES BUT THERE
 ARE NO DETAILS PROVIDING COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE SECTION 904.3 CHECK-OUT AISLES.
 904.3.2 COUNTER. THE COUNTER SURFACE HEIGHT SHALL BE 38
 INCHES (965 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. THE TOP OF THE COUNTER EDGE PROTECTION SHALL BE
 2 INCHES (51 MM) MAXIMUM ABOVE THE TOP OF THE COUNTER
 SURFACE ON THE AISLE SIDE OF THE CHECK-OUT COUNTER.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-06-11 Cont ID  
Sent By dharvey Date 2018-06-11 Time 12:20 Rev Time 0.00
Received By dharvey Date 2018-06-11 Time 12:20 Sent To  
Notes
2018-06-11 12:21:14PREVIOUSLY APPROVED. NO CHANGES NOTED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-03 Cont ID  
Sent By jpearson Date 2018-05-03 Time 08:00 Rev Time 0.00
Received By jpearson Date 2018-05-03 Time 07:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-14 Cont ID  
Sent By jpearson Date 2018-02-14 Time 13:44 Rev Time 0.00
Received By jpearson Date 2018-02-14 Time 07:15 Sent To  
Notes
2018-02-14 13:44:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. FBC 105.1, 107.2.1
 3. ELECTRICAL LOAD SUMMARY STATES THAT NEC 220.87 IS
 USED TO DETERMINE EXISTING LOAD. PROVIDE THE 12 MONTH
 HISTORY TO CONFIRM STATED DEMAND LOAD ON PLAN. FBC
 107.2.1, NEC 220.87
 4. ELECTRICAL LOAD SUMMARY SHOWS THAT A TOTAL OF 65.2
 KVA IS BEING ADDED TO PANEL DP1. THE PANEL SCHEDULE
 SHOWS A LOAD OF 101.52 KVA FOR CDRU AND 47.1 KVA FOR
 REMOTE DEFROST PANEL, WHICH WOULD BE A TOTAL OF 148.62
 KVA, PLUS OTHER ADDITIONAL LOADS FROM THE SUMMARY
 TOTALING 12.3 KVA, FOR A GRAND TOTAL OF 160.92 KVA.
 THIS WOULD OVERLOAD THE EXISTING PANEL AND TRANSFORMER
 FEEDING PANEL DP1. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 215.2, 220, 408.30: FBC 107.2.1
 5. PROVIDE LOAD CALCULATION FOR 400 AMP, 3 PHASE,
 277/480 VOLT SYSTEM. ARE THERE ANY LOADS BEING FED FROM
 THIS AHEAD OF THE TRANSFORMER FOR PANEL DP1? IF NOT,
 DISREGARD THIS REQUEST. NEC 215.2, 220, 408.30: FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-26 Cont ID  
Sent By scaldero Date 2018-03-26 Time 10:57 Rev Time 0.00
Received By scaldero Date 2018-03-26 Time 10:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-01-25 Cont ID  
Sent By scaldero Date 2018-01-25 Time 11:58 Rev Time 0.00
Received By scaldero Date 2018-01-25 Time 11:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-11 Cont ID  
Sent By dharvey Date 2018-06-11 Time 12:21 Rev Time 0.00
Received By dharvey Date 2018-06-04 Time 14:27 Sent To  
Notes
2018-06-05 14:27:49C28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-03 Cont ID  
Sent By shill Date 2018-05-03 Time 09:02 Rev Time 0.00
Received By shill Date 2018-03-22 Time 14:52 Sent To  
Notes
2018-03-23 14:52:50C21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-22 Cont ID  
Sent By gjohnson Date 2018-02-22 Time 11:42 Rev Time 0.00
Received By gjohnson Date 2018-01-11 Time 14:29 Sent To  
Notes
2018-01-16 14:29:41C21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2018-06-11 Cont ID  
Sent By dharvey Date 2018-06-11 Time 13:27 Rev Time 0.00
Received By dharvey Date 2018-06-11 Time 13:27 Sent To  
Notes
2018-06-11 13:27:30NO NEW SQUARE FOOTAGE. INTERIOR WORK AND FACADE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-03-28 Cont ID  
Sent By jwitmer Date 2018-03-28 Time 08:01 Rev Time 0.00
Received By jwitmer Date 2018-03-28 Time 08:01 Sent To  
Notes
2018-03-28 08:01:57BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-02-01 Cont ID  
Sent By jwitmer Date 2018-02-01 Time 16:19 Rev Time 0.00
Received By jwitmer Date 2018-01-31 Time 16:11 Sent To  
Notes
2018-02-01 16:19:57BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-05-02 Cont ID  
Sent By ccole Date 2018-05-02 Time 16:40 Rev Time 0.00
Received By ccole Date 2018-05-02 Time 16:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-12 Cont ID  
Sent By ccole Date 2018-02-12 Time 10:15 Rev Time 0.00
Received By ccole Date 2018-02-12 Time 07:26 Sent To  
Notes
2018-02-12 10:45:521ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18010368
 2/12/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET H-101: PROVIDE THE TYPE AND SIZE OF THE NEW
 DUCTWORK- NOTE H2.
  
 2) H-101: PROVIDE AND AIR DEVICE SCHEDULE.
  
 3) H-101: NOTES H1 AND H5 ARE IN CONFLICT. NOTE H1
 SPECIFIES PAINTED DUCTWORK HOWEVER NOTE H5 INDICATES
 THE DUCTS TO BE INSULATED. PLEASE NOTE FIBERGLASS
 INSULATION AND/OR FIREGLASS DUCTWORK SHALL NOT BE
 PAINTED PER THE UL LISTINGS AND FLAMESPEAD
 SMOKE-DEVELOPED INDEX OF THE MATERAL.
  
 4) PROVIDE SUPPORT AND HANGING DETAILS FOR THE NEW
 DUCTWORK PER SMACNA HVAC DUCT CONSTRUCTION STANDARDS-
 2005.
  
 5) COMCHECK REPORT: PROVIDE COMPLIANCE DATA FOR THE
 HVAC ALTERATIONS.
  
 6) ADVISORY: THE ARCHITECTURAL AND ELECTRICAL PLANS ARE
 SHOWING ALERATIONS TO THE REFRIGERATIONS SYTEMS. PLEASE
 NOTE THAT THE CITY OF WEST PALM BEACH REQUIRES A
 SEPARATE PERMIT FOR REFRIGERATION SYSTEMS FOR FOOD
 CASES, WALK-IN BOXES ETC. COMPLETE PLANS AND
 SPECIFICATIONS MUST BE SUBMITTED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-05-02 Cont ID  
Sent By gjohnson Date 2018-05-02 Time 15:44 Rev Time 0.00
Received By gjohnson Date 2018-05-02 Time 15:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-22 Cont ID  
Sent By gjohnson Date 2018-02-22 Time 11:16 Rev Time 0.00
Received By gjohnson Date 2018-02-21 Time 07:14 Sent To  
Notes
2018-02-22 11:42:161ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. D-101 IF NO WORK IS BEING DONE IN BATHROOMS
 PLEASE SHOW LOCATION OF FIXTURE AND NOTE ON THE PLAN
 EXISTING TO REMAIN. PER WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE RPZ
 BACKFLOW TO VERIFY THAT IT MEETS THE LEAD FREE
 REQUIREMENTS. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. A-513 DETAIL D3 HAS NOTE REF EVAC SYSTEM SEE
 REFRIGERATION DRAWING NON ARE PROVIDED IN PLAN SET, A
 VACUUM SYSTEM PIPING DIAGRAM WILL BE REQUIRED IN THE
 PLAN SET FOR REVIEW. PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR THE
 EVAC SYSTEM. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status N Date 2018-06-11 Cont ID  
Sent By dharvey Date 2018-06-11 Time 12:21 Rev Time 0.00
Received By dharvey Date 2018-06-11 Time 12:21 Sent To  
Notes
2018-06-11 12:22:42THRESHOLD AGREEMENT TO BE FILED IF REQUIRED PRIOR TO
 STRUCTURAL WORK BEING PERFORMED.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-03-28 Cont ID  
Sent By jwitmer Date 2018-03-28 Time 07:55 Rev Time 0.00
Received By jwitmer Date 2018-03-28 Time 07:55 Sent To  
Notes
2018-03-28 07:58:35RESIDENT INSPECTOR REQUESTED BY TENANT/ ALDI
 THE RESPONSE INDICATED THE TENANT WOULD LIKE A RESIDENT
 INSPECTOR ON SITE FOR THE STEEL AND CONCRETE WORK.
 FORMS WERE E-MAILED TO:
  
 [email protected] CAME BACK UNDELIVERABLE
  
 [email protected] 3/27/2018 04:46 PM
  
 FORMS NEED TO BE SIGNED BY ALL REQUIRED PARTIES AND
 RETURNED BEFORE PERMIT ISSUANCE.
  
 FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME'
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT: KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected]
  
 NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED.
 FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE PERMIT
 LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND BATCH
 STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF
 PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE
 RESIDENT INSPECTOR, THE OTHER FOR THE MEP INSPECTORS.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 AND GUIDELINES
 AND POLICIES FOR PROJECTS CONCERNING RESIDENT
 INSPECTORS. COMMENT # 14. 3 COPIES OF ALL SHOP DRAWINGS
 (HANDRAILS, PRECAST JOINT AND SLABS, PRODUCT APPROVALS,
 TRUSSES, BAR JOIST, ETC.) MUST BE SUBMITTED TO THE
 BUILDING DEPARTMENT. TWO REVIEWED SETS OF DOCUMENTS
 WILL BE RETURNED TO THE JOB SITE BEFORE ANY OF THE
 ABOVE ARE INSTALLED ON THE JOB.
  
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-06-08 Cont ID  
Sent By llouie Date 2018-06-08 Time   Rev Time 0.00
Received By llouie Date 2018-06-08 Time   Sent To  
Notes
2018-06-08 15:25:31ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) SEPARATE PERMIT FOR BICYCLE RACK SHALL BE ISSUED
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 (C.O.).
  
 REFERENCE: PB 1520L
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-05-03 Cont ID  
Sent By llouie Date 2018-05-03 Time   Rev Time 0.00
Received By llouie Date 2018-05-03 Time   Sent To  
Notes
2018-05-03 08:51:06** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) MODIFICATIONS INCLUDE EXTERIOR CHANGES TO THE SITE.
 AN APPLICATION FOR A MINOR DSI AMENDMENT TO THE
 APPROVED SITE PLAN IS REQUIRED WITH THE PLANNING
 DIVISION PRIOR TO BUILDING PERMIT. NOTE: THE MINOR DSI
 APPLICATION HAS BEEN SUBMITTED AND IS PENDING WITH THE
 PLANNING DIVISION FOR APPROVAL (REFERENCE: PB 1520L)
  
 NOTES:
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * SPOKE TO THE ARCHITECT (MVERRASTRO) ON 1/30/18 AND
 THE CONTRACTOR (SBROIT) ON 1/31/18 TO DISCUSS PROCESS
 FOR THE MINOR DSI AMENDMENT.
  
 * ZONE: GC (WESTWARD PLAZA DSI)
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-01-31 Cont ID  
Sent By LL Date 2018-01-31 Time   Rev Time  
Received By llouie Date 2018-01-29 Time   Sent To  
Notes
2018-01-31 09:07:57** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) MODIFICATIONS INCLUDE EXTERIOR CHANGES TO THE SITE.
 AN APPLICATION FOR A MINOR DSI AMENDMENT TO THE
 APPROVED SITE PLAN IS REQUIRED WITH THE PLANNING
 DIVISION PRIOR TO BUILDING PERMIT.
  
 NOTES:
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * SPOKE TO THE ARCHITECT (MVERRASTRO) ON 1/30/18 AND
 THE CONTRACTOR (SBROIT) ON 1/31/18 TO DISCUSS PROCESS
 FOR THE MINOR DSI AMENDMENT.
  
 * ZONE: GC (WESTWARD PLAZA DSI)
  
  
  