Plan Review Details - Permit 18010302
Plan Review Stops For Permit 18010302
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-02-02 Cont ID  
Sent By jgomez Date 2018-02-02 Time 14:58 Rev Time 0.00
Received By jgomez Date 2018-02-02 Time 14:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-01-18 Cont ID  
Sent By jgomez Date 2018-01-18 Time 19:01 Rev Time 0.00
Received By jgomez Date 2018-01-18 Time 16:32 Sent To  
Notes
2018-01-18 16:36:40RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017)
  
 ORIGINAL COMMENT:
 1- PROVIDE PRODUCT APPROVAL THAT MEETS THE DESIGN
 PRESSURES FOR EXPOSURE "C". DRAWINGS SUBMITTED WITH
 FLORIDA PRODUCT APPROVAL FL17347-R2 DON'T MEET THOSE
 DESIGN PRESSURES.
 FAC 61G20-3.001
  
 RESPONSE:
 SAME DRAWING FL17347.15 WAS RE-SUBMITTED. IT DOESN'T
 MEET THE DESIGN PRESSURES SHOWN ON WIND-LOADS
 SUBMITTED. THE REPLACEMENT DOOR IS A SINGLE DOOR WITH
 SIDELITE ASSEMBLY. THEREFORE, THE DESIGN PRESSURES FOR
 A SINGLE DOOR WITH SIDELITE ASSEMBLY (OX/XO) SHOWN ON
 PRODUCT APPROVAL SUBMITTED DON'T MEET THE DESIGN
 PRESSURES. CONTRACTOR MARKED THE SINGLE DOOR ONLY. THIS
 IS INCORRECT. PROVIDE PRODUCT APPROVAL THAT MEETS THE
 DESIGN PRESSURES SHOWN ON THE WIND LOAD TABLE SUBMITTED
 FOR THE DOOR WITH SIDELITE ASSEMBLY.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-11 Cont ID  
Sent By jgomez Date 2018-01-11 Time 17:57 Rev Time 0.00
Received By jgomez Date 2018-01-11 Time 17:48 Sent To  
Notes
2018-01-11 18:14:57RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017)
  
 1- WIND LOAD CALCULATIONS SUBMITTED ARE MARKED WITH THE
 DESIGN PRESSURES FOR AN INTERIOR ZONE IN EXPOSURE "B".
 ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL, THIS
 BUILDING IS LOCATED IN EXPOSURE "C" NOT EXPOSURE.
 REVISE AS REQUIRED. OR PROVIDE COMPLETE ENGINEERING
 ANALYSIS WITH CALCULATIONS FOR ALL WIND DIRECTIONS.
  
 2- PROVIDE PRODUCT APPROVAL THAT MEETS THE DESIGN
 PRESSURES FOR EXPOSURE "C". DRAWINGS SUBMITTED WITH
 FLORIDA PRODUCT APPROVAL FL17347-R2 DON'T MEET THOSE
 DESIGN PRESSURES.
 FAC 61G20-3.001
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-02 Cont ID  
Sent By jgomez Date 2018-02-02 Time 14:59 Rev Time 0.00
Received By jgomez Date 2018-01-29 Time 14:34 Sent To I
Notes
2018-01-30 14:35:05RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-18 Cont ID  
Sent By jgomez Date 2018-01-18 Time 19:01 Rev Time 0.00
Received By jgomez Date 2018-01-12 Time 11:13 Sent To I
Notes
2018-01-16 11:13:58RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-11 Cont ID  
Sent By jgomez Date 2018-01-11 Time 18:15 Rev Time 0.00
Received By jgomez Date 2018-01-10 Time 10:44 Sent To I
Notes
2018-01-11 10:44:23BLDG <5K