2018-02-08 11:50:15 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE PLANS HAVE SEVERAL REFERENCES TO THE FBC FIFTH |
| EDITION (2014). THE FBC SIXTH EDITION (2017) WENT INTO |
| EFFECT ON JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR |
| ON OR AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND |
| REFERENCE THE FBC SIXTH EDITION (2017). CHECK SHEETS: |
| T-1, A-007, A-008, S-0, S-4 AND S-6 |
| |
| 2) ON SHEET T-1 THE ALLOWABLE STRESS DESIGN (V BASIC) |
| WIND SPEED IS MISTAKENLY SPECIFIED AS 32 MPH AND IT |
| SHOULD BE 132 MPH. FBC-R301.2.1 |
| |
| 3) SUBMIT TWO SETS OF A SURVEY OF THE PROPERTY. FBC |
| 107.2.1 |
| |
| 4) SUBMIT TWO SETS OF A SITE DRAINAGE PLAN WITH THE |
| ELEVATIONS USING NAVD 88, WHICH IS THE VERTICAL DATUM |
| USED ON THE CURRENT FLOOD MAPS. FBC 107.2.5 AND |
| FBC-R401.3 |
| |
| 5) SEPARATE PERMIT APPLICATIONS ARE REQUIRED FOR THE |
| DRIVEWAY, WALKS AND POOL. |
| |
| 6) UPDATE THE EDITIONS OF THE STANDARDS THAT ARE LISTED |
| ON SHEET S-4 TO THE ONES REFERENCED IN THE 2017 FBC-R. |
| ACI 318-14, 332-14, 530-13, 530.1-13, TMS 402-16, |
| 403-2013, 602-2016 AND ASCE 5-13, 6-13. |
| |
| 7) THIS PROJECT HAS A ROOF SLOPE OF 3:12. WALL SECTION |
| 2 ON SHEET A-008 HAS A NOTE FOR FOR 30 YEAR ASPHALT |
| SHINGLES ON 30# FELT. FBC-R 905.2.2 REQUIRES TWO LAYERS |
| OF UNDERLAYMENT ON ROOF SLOPES LESS THAN 4:12. REVISE |
| NOTE. |
| |
| 8) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE |
| ENERGY FORM R405-2017. FBC ENERGY CONSERVATION |
| R103.1.1.2 |
| |
| 9) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE |
| AH-160 ROOF TILE ADHESIVE (NOA NO. 14-0805.01) EXPIRED |
| ON 5/10/2017. SUBMIT A CURRENT PRODUCT APPROVAL. FBC |
| 107.3.4 PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER |
| FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE |
| TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS |
| INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN |
| PRESSURES FOR EACH OF THE DIFFERENT ROOFING MATERIALS, |
| WINDOW/GLASS TYPES, STRUCTURAL MULLIONS AND EXTERIOR |
| DOOR TYPES. |
| |
| 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED DO NOT |
| REFERENCE THE CURRENT 2017 FLORIDA BUILDING CODE. |
| SUBMIT NEW PRODUCT APPROVALS THAT HAVE BEEN UPDATED TO |
| THE 2017 FBC. |
| |
| 11) THE NOA NO. ON THE PRODUCT APPROVAL LETTER FROM THE |
| DESIGNER OF RECORD HAS THE WRONG NOA NO. FOR THE FRENCH |
| DOORS. IT SHOULD BE NOA NO. 14-0908.07 NOT NOA NO. |
| 14-0809.07. |
| |
| 12) A PRODUCT APPROVAL WAS SUBMITTED FOR SLIDING GLASS |
| DOORS, HOWEVER, THERE ARE NOT ANY SLIDING GLASS DOORS |
| SHOWN ON THE PLANS OR LISTED IN THE DOOR SCHEDULE. |
| PLEASE CLARIFY. IF THERE ARE NO SLIDING GLASS DOORS, |
| THEN REMOVE THE PRODUCT APPROVALS FROM THE PERMIT |
| DOCUMENTS. |
| |
| 13) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR STRUCTURAL |
| MULLIONS. FBC 107.3.4 |
| |
| 14) THE WINDOW SCHEDULE SPECIFIES DOUBLE HUNG WINDOWS |
| AND THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR |
| SINGLE HUNG WINDOWS. PLEASE COORDINATE THE PRODUCT |
| APPROVALS WITH THE PLANS. FBC 107.2.1 |
| |
| 15) THE PLANS REQUIRE DESIGN PRESSURES OF +47.8 AND |
| -59.31 FOR THE SECTIONAL GARAGE DOORS. THE MAXIMUM |
| DESIGN LOADS LISTED IN PRODUCT APPROVALS FOR THE |
| SECTIONAL GARAGE DOORS IS +46 AND -52 PSF WHICH DO NOT |
| MEET THE REQUIRED DESIGN PRESSURES. FBC-R301.2.1.1 |
| NOTE: TABLE R301.2(4) IN THE FBC RESIDENTIAL HAS LOWER |
| DESIGN PRESSURE FOR GARAGE DOORS. |
| |
| 16) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |