Plan Review Details - Permit 18010296
Plan Review Stops For Permit 18010296
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-02 Cont ID  
Sent By thunt Date 2018-03-02 Time 14:08 Rev Time 0.00
Received By thunt Date 2018-02-28 Time 13:21 Sent To I
Notes
2018-03-01 13:21:10RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-17 Cont ID  
Sent By thunt Date 2018-01-17 Time 06:54 Rev Time 0.00
Received By thunt Date 2018-01-10 Time 13:51 Sent To I
Notes
2018-01-11 13:51:43PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-02 Cont ID  
Sent By thunt Date 2018-03-02 Time 14:08 Rev Time 0.00
Received By thunt Date 2018-03-02 Time 14:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-17 Cont ID  
Sent By thunt Date 2018-01-17 Time 06:52 Rev Time 0.00
Received By thunt Date 2018-01-17 Time 06:52 Sent To I
Notes
2018-01-17 06:54:5101/17/2018 PLUMBING 1ST REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) PLUMBING SANITARY AND WATER ISOMETRIC DRAWING
 REQUIRED FBC 107.3.5
  
 2) SHOW CLEAR FLOOR SPACES FOR FIXTURES AS REQUIRED.
 FBC-A 604.3
  
 3) SHOW TUNING SPACE TO COMPLY WITH FBC-A 304
  
 4) YOUR MIRROR MOUNTED @ 40? PER NOTE (B) WOULD NOT
 COMPLY AS IT HAS A STEEL FRAME. PER 603.3 THE MIRROR
 SHALL BE MOUNTED A MAX 40? ABOVE A LAVATORY TO THE
 REFLECTIVE SURFACE.
  
 5) YOUR SHOWING KNEE CLEARANCE OF 21? PER NOTE ( C ).
 FBC-A 306.3 REQUIRES A MIN 27?
  
 6)TEMPERED WATER SHALL BE PROVIDE PER FBC-P 607.1.2
  
  
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  