Plan Review Details - Permit 17121009
Plan Review Stops For Permit 17121009
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-02 Cont ID  
Sent By cthroop Date 2018-03-02 Time 08:26 Rev Time 0.00
Received By cthroop Date 2018-03-02 Time 08:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-06 Cont ID  
Sent By cthroop Date 2018-01-06 Time 11:12 Rev Time 0.00
Received By cthroop Date 2018-01-06 Time 11:09 Sent To E
Notes
2018-01-06 11:14:30BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ATTACHMENT DETAIL WITH FASTENER SCHEDULE.
 2. PROVIDE DESIGN WIND LOADS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-01 Cont ID  
Sent By jleahy Date 2018-03-01 Time 15:01 Rev Time 0.00
Received By jleahy Date 2018-03-01 Time 15:00 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-08 Cont ID  
Sent By jleahy Date 2018-01-08 Time 10:59 Rev Time 0.00
Received By jleahy Date 2018-01-08 Time 10:59 Sent To  
Notes
2018-01-08 12:21:32FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
  
 C405.2.5 EXTERIOR LIGHTING CONTROLS.
  
 LIGHTING FOR EXTERIOR APPLICATIONS OTHER THAN EMERGENCY
 LIGHTING THAT IS INTENDED TO BE AUTOMATICALLY OFF
 DURING BUILDING OPERATION, LIGHTING SPECIFICALLY
 REQUIRED TO MEET HEALTH AND LIFE SAFETY REQUIREMENTS OR
 DECORATIVE GAS LIGHTING SYSTEMS SHALL:
  
 1.BE PROVIDED WITH A CONTROL THAT AUTOMATICALLY TURNS
 OFF THE LIGHTING AS A FUNCTION OF AVAILABLE DAYLIGHT.
  
 2.WHERE LIGHTING THE BUILDING FA?ADE OR LANDSCAPE, THE
 LIGHTING SHALL HAVE CONTROLS THAT AUTOMATICALLY SHUT
 OFF THE LIGHTING AS A FUNCTION OF DAWN/DUSK AND A SET
 OPENING AND CLOSING TIME.
  
 3.WHERE NOT COVERED IN ITEM 2, THE LIGHTING SHALL HAVE
 CONTROLS CONFIGURED TO AUTOMATICALLY REDUCE THE
 CONNECTED LIGHTING POWER BY NOT LESS THAN 30 PERCENT
 FROM NOT LATER THAN MIDNIGHT TO 6 A.M., FROM ONE HOUR
 AFTER BUSINESS CLOSING TO ONE HOUR BEFORE BUSINESS
 OPENING OR DURING ANY PERIOD WHEN ACTIVITY HAS NOT BEEN
 DETECTED FOR A TIME OF LONGER THAN 15 MINUTES.
  
 ALL TIME SWITCHES SHALL BE ABLE TO RETAIN PROGRAMMING
 AND THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD
 OF AT LEAST 10 HOURS.
  
 EXCEPTION: LIGHTING FOR COVERED VEHICLE ENTRANCES OR
 EXITS FROM BUILDINGS OR PARKING STRUCTURES WHERE
 REQUIRED FOR SAFETY, SECURITY OR EYE ADAPTATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-02 Cont ID  
Sent By cthroop Date 2018-03-02 Time 08:26 Rev Time 0.00
Received By cthroop Date 2018-02-08 Time 13:45 Sent To I
Notes
2018-02-09 13:46:04RESUB ROUTED TO AAPONTE VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-08 Cont ID  
Sent By jleahy Date 2018-01-08 Time 12:22 Rev Time 0.00
Received By jleahy Date 2017-12-28 Time 17:01 Sent To Z
Notes
2018-01-04 11:16:33MISC 2 BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-03-01 Cont ID  
Sent By AA Date 2018-03-01 Time 11:49 Rev Time 0.00
Received By aaponte Date 2018-02-13 Time 12:02 Sent To E
Notes
2018-03-01 11:55:01PROVISO: ONLY ALLOWED FOR INSTALLATION INSIDE WINDOW.

Review Stop Z ZONING
Rev No 1 Status F Date 2018-01-04 Cont ID  
Sent By jleahy Date 2018-01-08 Time 12:22 Rev Time 0.00
Received By aaponte Date 2018-01-03 Time 14:10 Sent To  
Notes
2018-01-04 11:16:19PROPOSED SIGN WILL BE CONSIDERED THE INDENTITY SIGN FOR
 THE BUILDING, THEREFORE AN APPROVAL FROM THE BUILDING
 ASSOCIATION AUTHORIZING THE SIGN IS REQUIRED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-8221439.