Plan Review Details - Permit 17120974
Plan Review Stops For Permit 17120974
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-21 Cont ID  
Sent By dbattles Date 2018-08-21 Time 11:03 Rev Time 0.00
Received By dbattles Date 2018-08-20 Time 11:15 Sent To  
Notes
2018-08-21 11:08:14****CORRECTIONS****
 W.P.B. PERMIT: 17120974 (MAIN HOUSE) 18020157 (CABANA)
 REVIEWED: AUGUST 20, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 1ST REVIEW
 RESULTS: DENIED
 2ND REVIEW
 RESULTS: DENIED
  
 1. NEW LOT NEEDS TO BE CREATED.
 PROVIDE UNITY OF TITLE TO SHOW BOTH LOTS TOGETHER.
  
 2. NEW ADDRESS NEEDS TO BE CREATED.
 THE PERMIT CANNOT BE ISSUED UNTIL AND ADDRESS HAS BEEN
 ASSIGNED TO THE PROPERTY. PLEASE CALL MICHAEL ORIO BY
 PHONE AT 561-494-1080, OR BY E-MAIL [email protected]
  
 3. WILL EXISTING STRUCTURES BE DEMOLISHED?
 SEPARATE PERMIT WILL BE REQUIRED, PROVIDE SURVEY
 SHOWING EXISTING, DEMO PLAN AND ELECTRICAL SUB-PERMIT.
  
 4. OK.
  
 5. OK
  
 6. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 [FBC AMENDED 109] PLANS REQUIRE REVIEW BY THE PBC
 IMPACT FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL,
 YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE
 FOR REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF
 THE RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  
 7. PROPOSED STRUCTURES ARE IN A FLOOD ZONE. PROVIDE
 ELEVATION CERTIFICATE PRIOR TO THE ISSUANCE OF PERMIT,
 PROVIDE FORM BOARD SURVEY WITH ELEVATION OF FINISHED
 FLOOR AT FOUNDATION INSPECTION AND PROVIDE ELEVATION
 CERTIFICATE WITH PICS PRIOR TO FINAL INSPECTION.
 **CERTIFICATE NOT PROVIDED.
  
 8. ROOFING PERMIT REQUIRED.
 **PROVIDE TYPE OF ATTACHMENT FOR THE ROOF. PROVIDE NOA
 FOR ADHESIVE.
  
 9. ENERGY SUBMITTAL TO BE SIGNED BY OWNER/AGENT.
 **I HAVE ONE COPY FOR HOUSE AND 1 COPY FOR CABANA ONLY.
 PLEASE ADD VENTING TYPE AND CEILING INSULATION TYPE TO
 CABABNA ENERGY CALCULATIONS AND PROVIDE 2 COPIES.
  
 10. OK.
  
 11. OK.
  
 12. OK.
  
 13. OK (SEE PROVISO)
  
 14. OK.
  
 15. OK.
  
 16. PROVIDE DRAINAGE PLAN.
  NOT PROVIDED
  
 17. PLANS SPECIFY WOOD GARAGE DOORS. NOA 14-0825.06 IS
 FOR A STEEL GARAGE DOOR. PLEASE CLARIFY.
 **A NEW NOA 17-0731.01 WAS SUBMITTED. VERIFY IT MEETS
 DESIGN PRESSURES ON PLANS AND UPDATE IF NEEDED. THE
 PLANS STILLL CALL FOR WOOD GARAGE DOORS.
  
 18. ONLY ONE SET OF PRODUCT APPROVALS WAS SUBMITTED.
 ALL SUBMITTAL DOCUMENTS SHALL BE IN DUPLICATE.
 **THE RESPONSE SHEET SAYS 2 WERE PROVIDED, BUT THE SET
 IS MISSING THE DRAWING PORTION (11" X 17") OF FOLLOWING
 PRODUCT APPROVALS:
 FL 17783-R1, FL 17908-R1, FL 18596-R2 AND FL 17878-R1
 PLEASE PROVIDE 1 COPY OF EACH.
  
 PROVISO:
 PROVIDE SHOP DRAWINGS FOR ROOFTOP DECORATIVE METAL
 STRUCTURE.
 PROVIDE TRUSS ENGINEERING.
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-06 Cont ID  
Sent By cthroop Date 2018-02-06 Time 08:48 Rev Time 0.00
Received By cthroop Date 2018-02-05 Time 07:08 Sent To  
Notes
2018-02-06 10:09:12 
 BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NEW STRUCTURES SHALL COMPLY WITH BUILDING SETBACK
 REQUIREMENTS PER FBC 107.2.5 AND FBC RESIDENTIAL
 CHAPTER 3.
  
 1. NEW LOT NEEDS TO BE CREATED.
 2. NEW ADDRESS NEEDS TO BE CREATED.
 3. WILL EXISTING STRUCTURES BE DEMOLISHED?
 4. SEPARATE PERMIT HAS BEEN CREATED FOR CABANA,
 18020157. PRIMARY PERMIT 17120974 VALUE HAS BEEN
 REDUCED BY 120,204.00. NEW VALUE IS 1,879,796.00.
 5. SEPARATE PLANS ARE NOT REQUIRED FOR CABANA.
 6. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 7. PROPOSED STRUCTURES ARE IN A FLOOD ZONE. PROVIDE
 ELEVATION CERTIFICATE PRIOR TO THE ISSUANCE OF PERMIT,
 PROVIDE FORM BOARD SURVEY WITH ELEVATIOIN OF FINISHED
 FLOOR AT FOUNDATION INSPECTION AND PROVIDE ELEVATION
 CERTIFICATE WITH PICS PRIOR TO FINAL INSPECTION.
 8. ROOFING PERMIT REQUIRED.
 9. ENERGY SUBMITTAL TO BE SIGNED BY OWNER/AGENT.
 10. PROVIDE SHOP DRAWINGS FOR ROOFTOP DECORATIVE METAL
 STRUCTURE.
 11. NOA 13-1113.07 FOR ALHAMBRA ROOF TILE DOES NOT
 MATCH ROOFING NOTE, PLAN PAGE A-105.0.
 12. UNVENTED ROOF - PROVIDE ICC EVALUATION REPORT FOR
 ICYNENE INSULATION.
 13. PROVIDE PRODUCT APPROVALS FOR DECORATIVE METAL CAP
 OR PROVIDE ENGINEERING DESIGN FOR WIND LOADS AND
 STRUCTURAL ATTACHMENT.
 14. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 BBQ GRILL.
 15. PROVIDE DETAIL FOR FLOOD VENTS IN ATTACHED GARAGE.
 16. PROVIDE DRAINAGE PLAN.
 17. PLANS SPECIFY WOOD GARAGE DOORS. NOA 14-0825.06 IS
 FOR A STEEL GARAGE DOOR. PLEASE CLARIFY.
 18. ONLY ONE SET OF PRODUCT APPROVALS WAS SUBMITTED.
 ALL SUBMITTAL DOCUMENTS SHALL BE IN DUPLICATE.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING AND DOOR SUBMITTALS.
  
 PROVISO
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 NFIP
 THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS
 A5 WITH A BASE FLOOD ELEVATION (BFE) OF 7FT. THE CITY
 OF WEST PALM BEACH (THROUGH ORDINANCE) REQUIRES AN
 ADDITIONAL 24 INCHES OF FREEBOARD REQUIRING THE DESIGN
 FLOOD ELEVATION (DFE) TO BE 9. 0 FEET NAVD 88. PLEASE
 NOTE THIS INFORMATION ON YOUR PLANS.
  
 1. BASED ON THE SUBMITTED PLANS, THE FINISHED FLOOR
 ELEVATION IS ESTABLISHED AT 9.25 FEET NAVD 88.
 2. AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY
 MANAGEMENT AGENCY (FEMA) ESTABLISHED A NEW FLOOD
 INSURANCE RATE MAP (FIRM) UTILIZING THE RECENTLY
 COMPLETED FLOOD HAZARD DETERMINATION (FHD) FOR THE CITY
 OF WEST PALM BEACH, FL.
 3. ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED
 ON NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST
 PALM BEACH, BY ORDINANCE, ESTABLISHED A TWO FOOT
 FREEBOARD ABOVE THE (BFE).
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
 NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS
 SITE ARE REQUIRED TO BE AT OR ABOVE 9.0 FEET NAVD 88.
  
 AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED
 FLOOR ELEVATION IS REQUIRED.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
 G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION.
 FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION
 SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO
 THE FOLLOWING:
  
 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY
 WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS
 TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF
 FLOODWATERS.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-06 Cont ID  
Sent By jpearson Date 2018-08-06 Time 10:05 Rev Time 0.00
Received By jpearson Date 2018-08-06 Time 08:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-19 Cont ID  
Sent By jpearson Date 2018-01-19 Time 08:35 Rev Time 0.00
Received By jpearson Date 2018-01-18 Time 15:24 Sent To  
Notes
2018-01-19 08:35:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THERE IS A DISCREPANCY WITH THE FIRE ALARM RISER AND
 WHAT IS SHOWN ON PLANS FOR SMOKE/CO ALARMS. THE RISER
 DIAGRAM ON SHEET E-202 STATES THIS INSTALLATION WILL
 COMPLY WITH NEC 760, BUT ALSO SHOWS STANDARD 120 VOLT
 SMOKE AND CO ALARMS, WHICH ARE NOT COVERED BY NEC 760.
 TYPICAL SMOKE AND CO ALARMS ARE WIRED FROM A 120 VOLT
 BRANCH CIRCUIT CONTROLLED WITH AN AFCI BREAKER. PROVIDE
 CLARIFICATION AND/OR CORRECTION. FBC 107.2.1; FBC RE
 R314.3, R315.1
 2. SHEET E-202, LEGEND GENERAL NOTES, STATES THAT CODE
 IS BASED ON NEC 2008, WHICH IS NOT THE CODE FOR THIS
 PROJECT. ALSO, NOTE 2 SITES NEC 406.11 FOR TAMPER
 RESISTANT RECEPTACLES, WHICH IS NOT THE CURRENT CODE
 SECTION FOR THIS REQUIREMENT. PROVIDE CORRECTIONS. FBC
 PREFACE, NEC 2011, SECTION 406.12
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 4. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING ADDED TO WHAT IS
 SHOWN. NEC 250.32; FBC RE3607.3
 5. BBQ TERRACE SHOWS RECEPTACLE OUTLETS THAT ARE NOT
 GFCI PROTECTED. ALL RECEPTACLES OUTSIDE REQUIRE GFCI
 PROTECTION. NEC 210.8(A)
 6. CIRCUIT A-29 IS SHOWN AS THE WASHING MACHINE AND AS
 GFCI RECEPTACLES IN BATHROOMS. A MINIMUM OF ONE 20
 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE
 NO OTHER OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3)
 7. UPPER LAUNDRY ROOM (ROOM 211) SHOWS WHAT APPEARS TO
 BE COUNTER SPACE IN FRONT OF THE ELECTRICAL PANELS.
 PANELS ARE REQUIRED TO HAVE CLEARANCE PER NEC 110.26.
 PROVIDE CLARIFICATION AND/OR CORRECTION. NEC 110.26
 8. MORNING BAR (ROOM 222) SHOWS A RECEPTACLE ON CIRCUIT
 2E-4 WITHIN 6 FEET OF A SINK THAT IS NOT GFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.8(A)
 9. GUEST BATH (ROOM 241) SHOWS A RECEPTACLE THAT IS NOT
 GFCI PROTECTED. PROVIDE CORRECTION. NEC 210.8(A)
 10. THERE IS A SMALL SQUARE SYMBOL USED FOR LIGHT
 FIXTURE THAT IS NOT EXPLAINED IN THE LEGEND THIS
 FIXTURE IS SHOWN IN MANY CLOSET LOCATIONS. PER CODE:
 "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS". PROVIDE CLARIFICATION
 AND/OR CORRECTION. NEC 410.16
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-08-28 Cont ID  
Sent By shill Date 2018-08-28 Time 15:38 Rev Time 0.00
Received By jesmith Date 2018-08-28 Time 15:38 Sent To  
Notes
2018-08-28 15:40:15PERMIT 17 120974
 GAS REVIEW SEQUENCE 2
  
 COMMENTS FROM SEQUENCE 1
  
 1. SIZE THE BRANCH TO GENERATOR. PER WPB AMEND TO FBC
 107.2.1
 RESPONSE: REFER TO REVISED GAS PIPING ISOMETRIC ON
 SHEET P201
 SEQUENCE 2 COMMENT(S): APPROVED
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR INDOOR
 APPLIANCES PER THE FBC-2014 FUEL GAS CODE SEC. 304.
 RESPONSE: ALL APPLIANCES ARE OUTDOORS EXCEPT KITCHEN
 RANGE
 SEQUENCE 2 COMMENT(S): SUBMIT CALCULATIONS FOR
 COMBUSTION AIR FOR KITCHEN RANGE (SEE FBC RES G2407)
 CONFIRM MECHANICAL IS USING THOSE CALCULATION WHEN
 PROVIDING OUTSIDE AIR.
  
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND
 INSTALLATION GUIDES FOR ALL GAS EQUIPMENT AND
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
 RESPONSE: REFER TO ATTACHED SPECIFICATION SHEETS
 SEQUENCE 2 COMMENT(S): ONLY RECEIVED SPECIFICATION
 SHEETS FOR OUTSIDE GRILL. SUBMIT SPECIFICATION SHEETS
 FOR GAS GENERATOR, KITCHEN GAS RANGE, FIREPLACES (SEE
 NOTES ON A406.1 AND A406.2), GWH 1 AND GWH 2,
  
 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
 RESPONSE: REFER TO REVISED SHEETS P201 AND P101 FOR U/G
 PIPE GAS VENT
 SEQUENCE 2 COMMENT(S): APPROVED
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-02-02 Cont ID  
Sent By gjohnson Date 2018-02-02 Time 18:04 Rev Time 0.00
Received By gjohnson Date 2018-02-02 Time 18:04 Sent To  
Notes
2018-02-02 18:10:081ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SIZE THE BRANCH TO GENERATOR. PER WPB AMEND TO FBC
 107.2.1
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR INDOOR
 APPLIANCES PER THE FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND
 INSTALLATION GUIDES FOR ALL GAS EQUIPMENT AND
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-28 Cont ID  
Sent By shill Date 2018-08-28 Time 15:41 Rev Time 0.00
Received By jesmith Date 2018-07-11 Time 16:49 Sent To  
Notes
2018-07-12 16:49:27R40
 **TRAVELLING TOGETHER - 17120974 & 18020157**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-14 Cont ID  
Sent By hmoser Date 2018-02-14 Time 11:33 Rev Time 0.00
Received By hmoser Date 2017-12-28 Time 12:16 Sent To  
Notes
2017-12-28 12:16:36R40

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-02-06 Cont ID  
Sent By cthroop Date 2018-02-06 Time 10:15 Rev Time 0.00
Received By cthroop Date 2018-02-05 Time 07:08 Sent To  
Notes
2018-02-06 10:16:18BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-10 Cont ID  
Sent By hmoser Date 2018-08-10 Time 11:15 Rev Time 0.00
Received By hmoser Date 2018-08-06 Time 12:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-14 Cont ID  
Sent By hmoser Date 2018-02-14 Time 11:33 Rev Time 0.00
Received By hmoser Date 2018-02-13 Time 14:08 Sent To I
Notes
2018-02-14 11:33:19PLAN DENIED
 1) PAGE 101 PROVIDE RETURN AIR SIZE AND DUCT SIZE ROOM
 105
 2) ENERGY CALCULATIONS AND PLAN DO NOT MATCH
 ENERGY CALCULATIONS DON'T SHOW ALL THE AIR CONDITIONING
 UNITS ON THE BULBING INPUT SUMMARY REPORT.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2018-08-21 Cont ID  
Sent By dbattles Date 2018-08-21 Time 11:10 Rev Time 0.00
Received By dbattles Date 2018-08-21 Time 11:10 Sent To  
Notes
2018-08-21 11:11:20****CORRECTIONS****
 W.P.B. PERMIT: 17120974 (MAIN HOUSE)
 18020157 (CABANA)
 REVIEWED: AUGUST 20, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
 PROPOSED STRUCTURES ARE IN A FLOOD ZONE. PROVIDE
 ELEVATION CERTIFICATE PRIOR TO THE ISSUANCE OF PERMIT,
 PROVIDE FORM BOARD SURVEY WITH ELEVATION OF FINISHED
 FLOOR AT FOUNDATION INSPECTION AND PROVIDE ELEVATION
 CERTIFICATE WITH PICS PRIOR TO FINAL INSPECTION.
  
  
 **CERTIFICATE NOT PROVIDED.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2018-02-06 Cont ID  
Sent By cthroop Date 2018-02-06 Time 10:09 Rev Time 0.00
Received By cthroop Date 2018-02-05 Time 08:24 Sent To  
Notes
2018-02-06 10:13:52BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NFIP
 THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS
 A5 WITH A BASE FLOOD ELEVATION (BFE) OF 7FT. THE CITY
 OF WEST PALM BEACH (THROUGH ORDINANCE) REQUIRES AN
 ADDITIONAL 24 INCHES OF FREEBOARD REQUIRING THE DESIGN
 FLOOD ELEVATION (DFE) TO BE 9. 0 FEET NAVD 88. PLEASE
 NOTE THIS INFORMATION ON YOUR PLANS.
  
 1. BASED ON THE SUBMITTED PLANS, THE FINISHED FLOOR
 ELEVATION IS ESTABLISHED AT 9.25 FEET NAVD 88.
 2. AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY
 MANAGEMENT AGENCY (FEMA) ESTABLISHED A NEW FLOOD
 INSURANCE RATE MAP (FIRM) UTILIZING THE RECENTLY
 COMPLETED FLOOD HAZARD DETERMINATION (FHD) FOR THE CITY
 OF WEST PALM BEACH, FL.
 3. ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED
 ON NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST
 PALM BEACH, BY ORDINANCE, ESTABLISHED A TWO FOOT
 FREEBOARD ABOVE THE (BFE).
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
 NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS
 SITE ARE REQUIRED TO BE AT OR ABOVE 9.0 FEET NAVD 88.
  
 AN UNDER CONSTRUCTION (FORM BOARD) SURVEY WITH FINISHED
 FLOOR ELEVATION IS REQUIRED.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
 G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION.
 FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION
 SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO
 THE FOLLOWING:
  
 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY
 WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS
 TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF
 FLOODWATERS.
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-08-28 Cont ID  
Sent By shill Date 2018-08-28 Time 15:22 Rev Time 0.00
Received By jesmith Date 2018-08-28 Time 15:21 Sent To  
Notes
2018-08-28 15:37:54PERMIT 17 120974
 PLUMBING REVIEW SEQUENCE 2
  
 COMMENTS FROM SEQUENCE 1
  
 1-SHEET P100 NOTE READS "GAS OUTER"
 RESPONSE: REFER TO SHEET P100 FOR SPELLING REVISION
 SEQUENCE 2 COMMENT(S): APPROVED
  
 2-SHEET P100 SHOWS WATER SERVICE RUNNING TO BACK OF
 PROPERTY WHERE THERE IS AN EXISTING HOME NOW; WILL THIS
 BE DEMOLISHED? PLEASE CLARIFY PER WPB AMEND TO FBC
 107.2.1
 RESPONSE: EXISTING HOME
 SEQUENCE 2 COMMENT(S): DENIED. PLEASE SEE REVIEW STOP
 B-BUILDING, 2ND REVIEW,NOTE 3. RESPONSE BY RPJ TO
 PLUMBING REVIEW FOR REVIEW 3 NOT REQUIRED
  
 3-SHEET P102 IS MISSING FROM FROM PLAN SET.PLEASE
 PROVIDE TWO FULL SETS OF PLANS PER WPB AMEND TO FBC
 107.2.1
 RESPONSE: REFER TO ATTACHED SHEET P102 (FURNISHED REV 1
 DATED 6-19-18)
 SEQUENCE 2 COMMENT(S): STORM PIPING FOR COURTYARD IS
 NOT SIZED AND SQUARE FOOTAGE IS NOT INDICATED; CORRECT
 AND RESUBMIT
  
 4-PLEASE LABEL THE BATHROOMS ON THE ISOMETRIC DRAWING
 PER WPB AMEND TO FBC 107.2.1
 RESPONSE: PLEASE REFER TO SHEET P201
 SEQUENCE 2 COMMENT(S): SANITARY ISOMETRIC IS LABELED,
 HOWEVER "POWDER" FOR THE POWDER ROOM IS MISPELLED
 "POWER"; CORRECT AND RESUBMIT
  
 5-PROVIDE STORM WATER ISOMETRIC PER WPB AMEND TO FBC
 107.3.5.3(11)
 RESPONSE: WPB AMENDMENT ONLY APPLIES TO FBC 2010, NOT
 2014. PERMIT DRAWINGS INCLUDE SANITARY, WATER AND GAS
 PIPING RISERS. STORM DRAINAGE SYSTEM INDICATED IN FLOOR
 PLANS IS PROPERLY SIZED WITH RESPECTIVE FLOOR AREAS
 INDICATED. FBC RESIDENTIAL DOES NOT REQUIRE PIPING
 RISERS.
 SEQUENCE 2 COMMENT(S): WPB DID NOT ADOPT 2014 BUT
 ADOPTED 2017 WHEN IT BECAME AVAILABLE, THEREFORE THE
 2010 APPLIES TO THE 2014 FBC; CORRECT AND RESUBMIT.
  
 6-SHEET P201; THE TOILET FOR BATHROOM #2 SHALL CONNECT
 TO THE BATHROOM GROUP WITH THE SHOWER AND LAVATORY PER
 FBC RES P3108.1
 RESPONCE: NOT NOTED ON RPJ LETTER, BUT SHEET P201 HAS
 BEEN CORRECTLY MODIFIED TO MEET THIS REQUIREMENT
 SEQUENCE 2 COMMENT(S): SHEET P201 MODIFICATION
 APPROVED. PLEASE REVISE PLAN VIEW ON SHEET P104 TO
 REFLECT THE CHANGE.
  
 7-THE VALVES FOR THE STACKABLE WASHING MACHINES SHALL
 BE ACCESSIBLE PER FBC RES P2803.9.3
 RESPONCE: NOT NOTED ON RPJ LETTER, BUT SHEET P201 HAS
 BEEN CORRECTLY MODIFIED TO MEET THIS REQUIREMENT
 SEQUENCE 2 COMMENT(S): SHEET P201 MODIFICATION
 APPROVED. PLEASE ADVISE IF THE APPURTENANCES SHOWN ON
 THE WATER SUPPLY OUTLETS ON THE WATER RISER DIAGRAM FOR
 THE WASHING MACHINES, ICE LINES AND DISH WASHERS ARE
 WATER HAMMER ARRESTORS AS REQUIRED BY RES FBC 2903.5.
 PLEASE ID THEM ON THE WATER RISER DIAGRAM.
  
 SEQUENCE 2 COMMENT(S): NEW ITEM
 1-RE: SHEET P103; GAZEBO STORM WATER PING FOR TRENCH
 DRAIN IS NOT SHOWN. FURNISH PIPING AND SIZING AND
 RESUBMIT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561-805-6711

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-02 Cont ID  
Sent By gjohnson Date 2018-02-02 Time 17:15 Rev Time 0.00
Received By gjohnson Date 2018-02-02 Time 17:15 Sent To  
Notes
2018-02-02 17:26:491ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P100 NOTE ON GAS READS GAS OUTER PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT. P100 SHOWS THE NEW WATER SERVICE RUNNING TO THE
 BACK OF THE PROPERTY WERE THERE IS AN EXISTING HOME NOW
 WILL THIS HOME BE DEMOLISHED . PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 3. SHT. P102 IS MISSING FROM PLAN SET. PLEASE PROVIDE
 TWO FULL SETS OF PLANS. PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE LABEL THE BATHROOMS ON THE ISOMETRIC DRAWING.
 PER WPB AMEND TO FBC 107.2.1
  
 5. PROVIDE STORM WATER ISOMETRIC. PER WPB AMEND TO FBC
 107.3.5.3(11)
  
 6. SHTP201 THE TOILET FOR BATHROOM #2 SHALL CONNECT TO
 BATHROOM GROUP #2 WITH THE SHOWER AND LAVATORY. PER FBC
 RES P3108.1
  
 7. THE VALVES FOR THE STACKABLE WASHING MACHINES SHALL
 BE ACCESSIBLE. PER FBC RES P2903.9.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2018-08-21 Cont ID  
Sent By dbattles Date 2018-08-21 Time 11:08 Rev Time 0.00
Received By dbattles Date 2018-08-21 Time 11:08 Sent To  
Notes
2018-08-21 11:09:48****CORRECTIONS****
 W.P.B. PERMIT: 17120974 (MAIN HOUSE)
 18020157 (CABANA)
 REVIEWED: AUGUST 20, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
 1. PROVIDE TYPE OF ATTACHMENT FOR THE ROOF. PROVIDE NOA
 FOR ADHESIVE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-02-06 Cont ID  
Sent By cthroop Date 2018-02-06 Time 10:16 Rev Time 0.00
Received By cthroop Date 2018-02-05 Time 07:08 Sent To  
Notes
2018-02-06 10:21:38BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE SHOP DRAWINGS FOR ROOF TOP DECORATIVE METAL
 STRUCTURE.
 3. NOA 13-1113.07 FOR ALHAMBRA ROOF TILE DOES NOT MATCH
 ROOFING NOTE PLAN PAGE A-105.0 PLEASE CLARIFY.
 4. PROVIDE PRODUCT APPROVAL OR ENGINEERED DESIGN FOR
 DECORATIVE METAL CAPS. INCLUDE WIND LOADS AND
 STRUCTURAL ATTACHMENT MDETAIL.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-08-01 Cont ID  
Sent By ajones Date 2018-08-01 Time 15:21 Rev Time 0.00
Received By ajones Date 2018-07-31 Time 17:03 Sent To  
Notes
2018-08-01 15:21:108-1-18 FAILED REPEAT COMMENTS
  
 1. A MINOR SUBDIVISION NEEDS TO BE APPROVED TO CREAST
 THE NEW LOT FOR THE HOME TO BE CONSTRUCTED ON.
 2. WILL THE 2 EXISTING HOMES ON 5200 AND 5300 ESSEX
 COURT STAYING?
 3. A NEW ADDRESS NEEDS TO BE ASSISGNED AS PART OF THE
 MINOR SUBDIVISION PROCESS.
  
  
 ANGELLA VANN
 [email protected]
 561-822-1441

Review Stop Z ZONING
Rev No 1 Status F Date 2018-02-01 Cont ID  
Sent By AV Date 2018-02-01 Time 15:26 Rev Time 0.00
Received By ajones Date 2018-01-22 Time 15:53 Sent To  
Notes
2018-02-01 15:34:152/1/18- FAILED.
  
 1. A MINOR SUBDIVISION NEEDS TO BE APPROVED TO CREAST
 THE NEW LOT FOR THE HOME TO BE CONSTRUCTED ON.
 2. WILL THE 2 EXISTING HOMES ON 5200 AND 5300 ESSEX
 COURT STAYING?
 3. A NEW ADDRESS NEEDS TO BE ASSISGNED AS PART OF THE
 MINOR SUBDIVISION PROCESS.
  
  
 ANGELLA VANN
 [email protected]
 561-822-1441