Plan Review Details - Permit 17120958
Plan Review Stops For Permit 17120958
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-25 Cont ID  
Sent By jgomez Date 2018-01-25 Time 15:37 Rev Time 0.00
Received By jgomez Date 2018-01-24 Time 16:10 Sent To  
Notes
2018-01-24 16:59:13RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
 NOTE: THIS MAY BE DONE LATER AT TIME OF PERMIT PRINTING
 WHEN PLANS ARE APPROVED AND STAMPED.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ALL NEW WINDOW TYPES AS SPECIFIED ON PLANS.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY
 SPECIFY WINDOW MULLION SIZES TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES.
  
 C) ALL NEW EXTERIOR DOORS AS SPECIFIED ON PLANS.
  
 D) HURRICANE SHUTTERS IF WINDOWS AND DOORS WITH GLAZING
 DON'T HAVE IMPACT GLASS. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 E) ROOF TILE AS SPECIFIED ON PLANS.
  
 F) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 G) FLAT ROOF ASSEMBLY. AND CLEARLY IDENTIFY SPECIFIC
 APPROVED INSULATED ASSEMBLY AND NON-INSULATED ASSEMBLY
 AS SPECIFIED ON ROOF LEGEND ON SHEET A-1.30. NOTE: IF
 SELECTED ASSEMBLIES DON'T MEET THE DESIGN PRESSURES OF
 ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED.
  
 H) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 I) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 LIST THE CURRENT FLORIDA PRODUCT APPROVAL NUMBER NEXT
 TO EACH SPECIFIED CONNECTOR.
 NOTE: FLORIDA PRODUCT APPROVALS LISTED ON THE TRUSS TIE
 DOWN SCHEDULE ON SHEET S-2 NEED TO BE UPDATED TO THE
 CURRENT 2014 CODE.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY NUMBER OF SCREWS AND
 SIZE. IF SPECIFYING ADHESIVE, THEN PRODUCT APPROVAL IS
 REQUIRED.
  
 5- SHEET S-2:
 A) ROOF WIND LOADS SHOWN ON THE COMPONENT & CLADDING
 WIND DESIGN PRESSURES TABLE FOR ROOF ZONE #3 DON'T
 CORRESPOND TO ROOF ZONE #3. REVISE AS REQUIRED. TABLE
 R301.2(2) FBC-RESIDENTIAL, 5TH EDITION (2017).
 NOTE: SEE PLANS FOR TYPE OF ROOF AND REVISE DESIGN
 PRESSURES AS REQUIRED.
  
 B) WALL WIND LOADS SHOWN ON THE COMPONENT & CLADDING
 WIND DESIGN PRESSURES TABLE ARE TOO LOW FOR A BUILDING
 IN EXPOSURE "C". REVISE AS REQUIRED OR PROVIDE COMPLETE
 CALCULATIONS. TABLE R301.2(2) FBC-RESIDENTIAL.
  
 C) REVISE CORNER DISTANCE "A". ACCORDING TO NOTE "A" OF
 FIGURE R301.2(7) FBC-RESIDENTIAL THE MINIMUM DIMENSION
 FOR "A" IS 4'-0".
  
 6- STOOP DETAIL #2 ON SHEET A-1.00: SPECIFY THE
 DIMENSION OF THE TREAD AND LANDING. SEC. R311.7.5.2 AND
 R311.3 FBC-RESIDENTIAL.
  
 7- ROOF PLAN ON SHEET A-1.30: SPECIFY THE OVERFLOW
 DRAINS AND SCUPPERS FOR BOTH NEW ROOF SECTIONS AS
 REQUIRED BY SEC. R903.4.1 FBC-RESIDENTIAL.
  
 8- WINDOW SCHEDULE ON SHEET A-5.00: CLEARLY SPECIFY
 TYPE OF WINDOWS (SINGLE HUNG, FIXED, ETC). WINDOW
 SCHEDULE DOESN'T SPECIFY TYPE OF WINDOWS. SEC. 107.2.1
 CITY AMENDMENTS.
  
 9- CARBON MONOXIDE ALARM SHOWN ON SHEET E1.1 DOESN'T
 COMPLY WITH SEC. R315.1 FBC-RESIDENTIAL. CARBON
 MONOXIDE ALARM NEED TO BE WITHIN 10'-0" OF EACH
 BEDROOM. BEDROOM #1 DOESN'T COMPLY. REVISE AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-18 Cont ID  
Sent By jpearson Date 2018-01-18 Time 14:21 Rev Time 0.00
Received By jpearson Date 2018-01-18 Time 14:21 Sent To  
Notes
2018-01-18 14:21:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM STATES TO CONNECT TO SPARE METER.
 THERE SHOULD NOT BE ANY SPARE METERS, ONLY ONE SERVICE
 PER RESIDENTIAL ADDRESS IS PERMITTED. PROVIDE
 CORRECTION AND/OR CLARIFICATION. FBC 107.2.1; NEC
 230.2; FBC RE E3601.2
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 3. SERVICE GROUNDING ELECTRODE TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.56; FBC RE E3608.4
 4. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 5. DINING ROOM LIGHT IS SHOWN ON THE SAME CIRCUIT AS
 THE DINING ROOM RECEPTACLE OUTLETS, WHICH IS A CODE
 VIOLATION. PROVIDE CORRECTION. NEC 210.52(B)(2); FBC RE
 E3703.2
 6. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION FOR MASTER ALL BATHROOMS, INCLUDING CIRCUITS
 A-15, A-17, AND A-23. NEC 210.11(C)(3) , FBC RE E3703.4
 7. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2018-01-22 Cont ID  
Sent By gjohnson Date 2018-01-22 Time 15:35 Rev Time 0.00
Received By gjohnson Date 2018-01-22 Time 15:35 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-01-10 Cont ID  
Sent By fmittner Date 2018-01-10 Time 08:26 Rev Time 0.00
Received By fmittner Date 2018-01-09 Time 11:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-25 Cont ID  
Sent By jgomez Date 2018-01-25 Time 18:52 Rev Time 0.00
Received By jgomez Date 2017-12-27 Time 09:33 Sent To I
Notes
2017-12-28 09:34:06R04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-01-25 Cont ID  
Sent By jgomez Date 2018-01-25 Time 15:41 Rev Time 0.00
Received By jgomez Date 2018-01-25 Time 15:41 Sent To  
Notes
2018-01-25 15:41:411- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
 NOTE: THIS MAY BE DONE LATER AT TIME OF PERMIT PRINTING
 WHEN PLANS ARE APPROVED AND STAMPED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-25 Cont ID  
Sent By jgomez Date 2018-01-25 Time 17:46 Rev Time 0.00
Received By jgomez Date 2018-01-25 Time 17:46 Sent To  
Notes
2018-01-25 17:59:42RESIDENTIAL (R3) ADDITION/ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- ENGINEER OF RECORD TO PROVIDE COMPLETE EQUIPMENT
 SIZING CALCULATIONS (2 COPIES) SIGNED AND SEALED AS
 REQUIRED BY FS CHAPTER 471. SEC. M1401.3
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 2- SHEET M0.1:
 A) SCOPE OF WORK IS INCORRECT. THIS IS A SINGLE FAMILY
 RESIDENCE NOT MEDICAL OFFICE. REVISE AS REQUIRED TO
 MATCH ARCHITECTURAL PLANS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) REVISE THE ROOF INSULATION SHOWN ON THE DESIGN
 CRITERIA TO MATCH ARCHITECTURAL PLANS. SEE ROOF LEGEND
 ON SHEET A-1.30 AND REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 3- SHEET M0.2: INFORMATION ON THE EXHAUST FAN SCHEDULE
 DOESN'T MATCH NUMBER OF BATHROOMS SHOWN ON PLANS.
 MISSING THE POWDER ROOM AND THE DUCT SIZE DOESN'T
 MATCH. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-01-22 Cont ID  
Sent By gjohnson Date 2018-01-22 Time 15:20 Rev Time 0.00
Received By gjohnson Date 2018-01-22 Time 14:05 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-01-25 Cont ID  
Sent By jgomez Date 2018-01-25 Time 17:43 Rev Time 0.00
Received By jgomez Date 2018-01-25 Time 17:43 Sent To  
Notes
2018-01-25 17:45:111- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF TILE AS SPECIFIED ON PLANS.
  
 B) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 C) FLAT ROOF ASSEMBLY. AND CLEARLY IDENTIFY SPECIFIC
 APPROVED INSULATED ASSEMBLY AS SPECIFIED ON PLANS.
 NOTE: IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES OF ALL ROOF ZONES, THEN SIGNED AND SEALED RAS
 117 CALCULATIONS WILL BE REQUIRED.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.

Review Stop Z ZONING
Rev No 1 Status F Date 2018-01-10 Cont ID  
Sent By fmittner Date 2018-01-10 Time 08:26 Rev Time 0.00
Received By fmittner Date 2018-01-10 Time 08:26 Sent To  
Notes
2018-01-10 08:29:27VALUE OF WORK EXCEEDS 50% OF VALUE OF IMPROVEMENTS ON
 SITE. REQUIRES SUBMITTAL OF SEPERATE LANDSCAPE PERMIT.
  
 QUESTIONS, CONTACT: RAY CARANCI, LANDSCAPE PLANNER AT
 822-1462


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved