Plan Review Details - Permit 17120956
Plan Review Stops For Permit 17120956
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-12 Cont ID  
Sent By aclange Date 2018-03-12 Time 15:16 Rev Time 0.00
Received By aclange Date 2018-03-12 Time 14:51 Sent To  
Notes
2018-03-12 15:05:20PROVISIO
  
 DEFERRED SUBMITTALS:
  
 1. FLOOR SOUND PROOFING
  
 2. PRODUCT APPROVAL FOR EXTERIOR DOORS
  
 FBC107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-29 Cont ID  
Sent By aclange Date 2017-12-29 Time 13:51 Rev Time 0.00
Received By aclange Date 2017-12-29 Time 09:11 Sent To  
Notes
2017-12-29 13:53:17****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. ON PAGES A0.03 AND A0.18 PLEASE SELECT THE SOUND
 PROOFING USED UNDER THE FLOOR SYSTEMS SELECTED. PROVIDE
 A MANUFACTURERS TEST REPORT SHOWING COMPLIANCE WITH FBC
 603.1 FLAME SPREAD ? ASTM E-84-09.
  
 2. PROVIDE PRODUCT APPROVALS FOR TWO NEW DOORS USED ON
 OPENINGS 004 AND 006.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 3. PLEASE CLARIFY ON PAGE A0.03 SYSTEMS NUMBER WL 1001
 AND WL 2003 SHOW THE OPTION OF WOOD FRAMING.
  
 FBC 603.1 ALLOWABLE MATERIALS IN TYPE I CONSTRUCTION.
  
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
  
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
 1.2. NONBEARING EXTERIOR WALLS WHERE FIRE-RESISTANCE
 RATED CONSTRUCTION IS NOT REQUIRED.
 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-12 Cont ID  
Sent By jpearson Date 2018-03-12 Time 17:23 Rev Time 0.00
Received By jpearson Date 2018-03-12 Time 16:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-31 Cont ID  
Sent By jpearson Date 2018-01-31 Time 10:15 Rev Time 0.00
Received By jpearson Date 2018-01-31 Time 06:59 Sent To  
Notes
2018-01-31 10:15:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM. NEC 215.5
 2. PANEL C IS SHOWN BEING FED FROM PANEL B ON A 20 AMP
 BREAKER. THE LOAD SHOWN FOR THIS PANEL EXCEEDS 20 AMPS.
 PROVIDE CORRECTION. NEC 215.2
 3. ALL RECEPTACLES INSTALLED WITHIN 6 FEET OF A SINK
 REQUIRE GFCI PROTECTION. PROVIDE CORRECTION FOR LOUNGE,
 ROOM 417. NEC 210.8(B)(5)
 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-02-26 Cont ID  
Sent By pleduc Date 2018-02-26 Time   Rev Time 0.00
Received By pleduc Date 2018-02-26 Time 12:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-01-03 Cont ID  
Sent By pleduc Date 2018-01-03 Time   Rev Time 0.00
Received By pleduc Date 2017-12-29 Time 15:02 Sent To  
Notes
2017-12-29 16:15:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PROPOSED PROJECT CHANGES A BUSINESS OCCUPANCY TO
 AN ASSEMBY OCCUPANCY.
  
 SHEET A0.14 INDICATES EXIT DOORS 001, 002, 010 & 011.
 SHEET AO.13 INDICATES A DOOR SCHEDULE WHICH SHOWS
 VARIOUS HARDWARE SETS FOR THOSE DOORS. NO PANIC
 HARDWARE IS INDICATED
  
 PER NFPA 101, CHAPTER 12, NEW ASSEMBLY OCCUPNACIES:
  
 12.2.2.2 DOORS.
 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK
 ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR FIRE
 EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS OTHERWISE
 PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS AS PERMITTED IN
 12.2.2.2.6.
  
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED TO BE USED ON A SINGLE DOOR OR A
 SINGLE PAIR OF DOORS IF BOTH OF THE FOLLOWING
 CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY OCCUPANCY HAS AN OCCUPANT LOAD NOT
 GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR
 MORE ARE RELEASED BY PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC FIRE
 CODE REFERENCES.
  
  
  
  
 2) SHEET A1.11- PATIO DOORS ARE INDICATED AROUND THE
 EXTERIOR OF THE PROJECT. THOUGH THESE DOORS ARE
 EXISTING THE HARDWARE SHALL BE INDICATED OF THE THE
 DOOR SCHEDULE.
  
 PLEASE INCLUDE ALL DOOR HARDWARE OF ALL PATIO DOORS ON
 THE DOOR SCHEDULE.
  
  
  
  
 3) SHEET AO.13 - THE DOOR SCHEDULE INDICATES HARDWARE
 ON SOME OF THE PATIO DOORS. HOWEVER, THEY APPEAR TO
 INDICATE EXITING OUT ONTO THE PATIO. WHAT TYPE OF
 HARDWARE IS ON THESE DOORS THAT ALLOWS THEM BACK IN?
 WHAT IS THE OCCUPANCY SPACE OF THE PATIO? WILL PEOPLE
 BE ALLOWED TO GATHER ON THE PATIO? IF THE OCCUPANCY
 TOTAL IS OVER 50 THE EXIT DOORS FROM THE PATION ARE
 REQUIRED TO SWING IN THE DIRECTION OF TRAVEL.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS:
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE OF THE SIDE-HINGED OR PIVOTED-SWINGING
 TYPE SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL
 UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR MORE, EXCEPT UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO SWING IN THE DIRECTION OF EGRESS TRAVEL
 WHERE PERMITTED BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS THE DOOR OPENING SERVES AN INDIVIDUAL
 LIVING UNIT THAT OPENS DIRECTLY INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
 IF THE PATIO DOORS ARE EXIT DOORS, THE EXIT PATH IS NOT
 INDICATED ON THE LIFE SAFETY PLAN. IF THESE DOORS DO
 NOT LEAD TO A DEFINED EXIT, THEY ARE NO EXIT DOORS. SEE
 # 6 BELOW.
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC FIRE
 CODE REFERENCES.
  
  
  
  
 4) SHEETS A 1.13 - NOTE # 7 INDICATES SOUND PANELS ON
 THE CEILING. THERE ARE NO INDICATIONS OF HOW THESE WILL
 BE FASTENED? THERE ARE NO MANUFACTURES SPECIFICATION
 SHEETS TO VERIFY INTERIOR FINISH CODE COMPLIANCE.
  
 PER NFPA 101, CHAPTER 12
  
 12.3.3 INTERIOR FINISH.
 12.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH SECTION 10.2.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 5) SHEET A1.11 - NOTE # 8 INDICATES FLOORING PER
 MANUFACTURESE SPECIFICATIONS. THE IS NO FLOORING
 DOCUMENT OR INDICATIONS THAT CAN BE EASYILY OR
 DIFNITIVELY IDENTIFIED.
  
 PER NFPA 101, CHAPTER 12
  
 12.3.3.5 INTERIOR FLOOR FINISH
 12.3.3.5.1 INTERIOR FLOOR FINSIH SHALL COMPLY WITH
 SECTION10.2.
 12.3.3.5.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND
 EXIT ACCESS CORRIDORS AND IN SPACES NOT SEPARATED FROM
 THEM BY WALLS COMPLYING WITH 12.3.6 SHALL BE NOT LESS
 THAN CLASS II.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 6) SHEET E 2.1 - THERE ARE EXIT SIGNS OVER THE PATIO
 DOORS LEADING OUT ONTO THE PATIO AREA. THERE IS NO
 DEFINED EXIT INDICATED FROM THIS PATION SPACE. THE LIFE
 SAFETY PLAN DOES NOT INDICATE A DEFINED EXIT FROM THE
 PATIO SPACE.
  
 IF THE PATIO AREA DOES NOT HAVE A DEFINED EXIT, THE THE
 EXIT SIGNS ABOVE THESE DOORS IN NOT APPLICABLE FROM THE
 INTERIOR. ON THE CONTRARY, THESE DOORS MAY NEED TO HAVE
 EXIT SIGN INDICATORS ON THE EXTERIOR LEADING IN.
  
 EITHER WAY IT IS NOT CLEAR IF A PERSON CAN EXIT THE
 PATIO AREA WITH THIS PLAN SUBMITTAL.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY WITH DETAILS.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-03-13 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-22 Time 11:35 Sent To  
Notes
2018-02-23 11:35:43C25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-12 Cont ID  
Sent By lmarchan Date 2018-02-12 Time 10:59 Rev Time 0.00
Received By lmarchan Date 2017-12-27 Time 08:44 Sent To  
Notes
2017-12-28 08:44:50C06

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-03-13 Cont ID  
Sent By ccole Date 2018-03-13 Time 09:22 Rev Time 0.00
Received By ccole Date 2018-03-13 Time 08:50 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-24 Cont ID  
Sent By ccole Date 2018-01-24 Time 17:09 Rev Time 0.00
Received By ccole Date 2018-01-24 Time 16:38 Sent To  
Notes
2018-01-24 17:54:181ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17120956
 1/24/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 2) SUBMIT ENERGY CALCULATIONS FOR THE CHANGE OF
 OCCUPANCY IN ACCORDANCE WITH SECTIONS C101.4.4 AND
 C101.5.1.
  
 3) M6.1: THE O/A CALCULATION SCHEDULE IS INACCURATE.
 THE SCHEDULE INDICATES 9800 SF. FOR AHU-1 WHICH APPEARS
 TO BE THE ENTIRE SPACE, HOWEVER THERE IS AN EXISTING
 AHU SERVING THE LARGER PERCENTAGE OF THE SPACE. PLEASE
 CORRECT AND REVISE THE SCHEDULE TO INCLUDE BREAKDOWN
 CALCULATIONS FOR ALL OF THE VARIOUS ROOMS AND SPACES-
 OPEN GYM, LIFTING ROOM, CARDIO, LOUNGE, WAITING,
 STORAGE, LOBBY, CORRIDOR ETC. THESE ARE ALL CALCULATED
 AT DIFFERENT RATES PER TABLE 403.3
  
 4) M6.1: THE EXHAUST AIR CALCULATION SCHEDULE IS
 INDICATING EF-1 HOWEVER THERE IS NO EF-1 SHOWN ON THE
 PLAN, AND THE 500 CFMS OF EXHAUST AIR SHOWN DOES NOT
 MATCH THE 800 CFMS OF EXHAUST AIR SHOWN IN THE AIR
 BALANCE TABLE. IT APPEARS THAT EXHAUST AIR FROM THE
 JANITOR ROOM AND OTHER ROOMS AND SPACES ARE MISSING.
 PLEASE CORRECT THESE CALCULATIONS.
  
 5) M2.1: VERIFY THAT THERE ARE EXISTING SMOKE DETECTORS
 IN THE RETURN AIR PLENUM OF THE EXISTING AHU- SEE
 SECTIONS 606.2.1 AND 606.2.2.
  
 6) M2.1: VERIFY THERE IS A MINIMUM 3' CLEARANCE FROM
 THE ERV EXHAUST OUTLET TO THE DOORWAY OPENING- SECTION
 501.3.1(3)
  
 7) M2.1: PROVIDE CONDENSATE DISPOSAL PLANS FOR THE
 AHU'S. SHOW THE PIPING RUNS AND DISCHARGE LOCATIONS.
  
 8) M6.1: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE ROOF TOP CONDENSER AND STAND-
 SECTION 301.15.
  
 9) SUBMIT THE NOA'S FOR THE AC STAND AND THE O/A
 LOUVERS WITHY NSHOP DRAWING APPROVAL STAMPS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-01-19 Cont ID  
Sent By gjohnson Date 2018-01-19 Time 12:32 Rev Time 0.00
Received By gjohnson Date 2018-01-18 Time 17:22 Sent To  
Notes
2018-01-19 13:03:471ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO
 THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS
 PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER
 CLOSETS AND URINALS PROVIDED FOR MEN. PER FBC PL
 403.1.3
  
 2. SHT. P5.1 THE WATER CLOSETS ARE NOT VENTED PROPERLY
 IF A DRY VENT IS INSTALLED BETWEEN THE TWO MOST UP
 STREAM WATER CLOSETS THE SYSTEM WOULD COMPLY AS A
 CIRCUIT VENT. PER FBC PL 914.1
  
 3. THE FIXTURE BRANCH FOR THE SHOWERS IS NOT VENTED A
 DRY VENT BETWEEN THE TWO MOST UPSTREAM SHOWERS WILL
 COMPLY AS A CIRCUIT VENT. PER FBC PL 914.1
  
 4. SHOW TRAP PRIMERS ON THE FLOOR DRAINS ON THE THE
 ISOMETRIC DRAWING. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2018-02-08 Cont ID  
Sent By AA Date 2018-02-08 Time 11:18 Rev Time 0.00
Received By aaponte Date 2018-02-08 Time 11:18 Sent To  
Notes
2018-02-08 11:18:44INTERIOR TENANT IMPROVEMENT ONLY.