Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-30 Cont ID  
Sent By tklarge Date 2018-05-30 Time 13:32 Rev Time 0.00
Received By tklarge Date 2018-05-30 Time 13:32 Sent To  
Notes
2018-05-30 13:32:25THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A
 COMPRREHENSIVE REVIEW CANNOT BE DONE. COMPLY WITH THE
 FOLLOWING COMMENTS.
  
 1)T THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE
 SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE.
 SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES USED
 TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3. THE SUBMITTED
 SIZING TABLE DOES NOTE SHOW THAT IT IS FROM THE 2014
 FBC-FUEL GAS.
  
 2) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYTEM BUT
 YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR LESS
 THAN A 2 PSI SYSTEM. CLARIFY.
  
 4) CLEARLY IDENTIFY THE REGULATORS ON THE GAS DRAWING.
 WPB AMEND. TO FBC SEC. 107.2.1.
  
 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES 402.4
 FOR THE PROPER PIPE SIZE AND BTU LOAD.
  
 6) SHOW THE TYPE OF UNDERGROUND PIPING AND THE PIPE
 SIZE FOR THE GENERATOR. NOTE: GALVANIZED PIPE IS NOT
 PERMITTED TO BE INSTALLED UNDERGROUND.
  
 7) SHOW THE TYPE OF PIPE AND THE PIPE SIZE AT THE
 OUTLET OF THE GAS METER.
  
 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR
 SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR 2017 FBC-RES. SEC. G2422.1 (8).
  
 9) SHOW THE DISTANCE FROM THE GAS METER TO EACH
 PRESSURE REGULATOR
  
 10) SUBMIT 2 COPIES OF THE MANUFACTURER'S INSTALLATION
 MANUAL. WPB AMEND. TO FBC SEC. 107.2.1.
  
 11) SHOW THE DISTANCE OF THE GENERATOR FROM THE
 EXTERIOR WALL OF THE STRUCTURE ON THE SURVEY. THE
 GENERATOR SHALL BE LOCATED A MINIMUM OF 5 FEET FROM THE
 EXTERIOR WALL OF THE STRUCTURE UNLESS THE WALL IS ONE
 HOUR FIRE RATED PER NFPA 37 SEC. 4.1.4.
  
 12) DELETE THE OLD GAS DRAWINGS FROM THE PERMIT PACKAGE
 AND SUBMIT TWO COMPLETE SETS OF PLANS FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-26 Cont ID  
Sent By tklarge Date 2019-02-26 Time 09:25 Rev Time 0.00
Received By tklarge Date 2019-02-26 Time 09:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-30 Cont ID  
Sent By tklarge Date 2018-05-30 Time 13:32 Rev Time 0.00
Received By tklarge Date 2018-05-30 Time 13:32 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved