2018-05-30 13:32:25 | THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A |
| COMPRREHENSIVE REVIEW CANNOT BE DONE. COMPLY WITH THE |
| FOLLOWING COMMENTS. |
| |
| 1)T THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE |
| SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE. |
| SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES USED |
| TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL |
| GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 |
| (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4, |
| G2412.8, G2413.1, G2413.2, & G2413.3. THE SUBMITTED |
| SIZING TABLE DOES NOTE SHOW THAT IT IS FROM THE 2014 |
| FBC-FUEL GAS. |
| |
| 2) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYTEM BUT |
| YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR LESS |
| THAN A 2 PSI SYSTEM. CLARIFY. |
| |
| 4) CLEARLY IDENTIFY THE REGULATORS ON THE GAS DRAWING. |
| WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES 402.4 |
| FOR THE PROPER PIPE SIZE AND BTU LOAD. |
| |
| 6) SHOW THE TYPE OF UNDERGROUND PIPING AND THE PIPE |
| SIZE FOR THE GENERATOR. NOTE: GALVANIZED PIPE IS NOT |
| PERMITTED TO BE INSTALLED UNDERGROUND. |
| |
| 7) SHOW THE TYPE OF PIPE AND THE PIPE SIZE AT THE |
| OUTLET OF THE GAS METER. |
| |
| 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE |
| FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR |
| SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE |
| GENERATOR 2017 FBC-RES. SEC. G2422.1 (8). |
| |
| 9) SHOW THE DISTANCE FROM THE GAS METER TO EACH |
| PRESSURE REGULATOR |
| |
| 10) SUBMIT 2 COPIES OF THE MANUFACTURER'S INSTALLATION |
| MANUAL. WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| 11) SHOW THE DISTANCE OF THE GENERATOR FROM THE |
| EXTERIOR WALL OF THE STRUCTURE ON THE SURVEY. THE |
| GENERATOR SHALL BE LOCATED A MINIMUM OF 5 FEET FROM THE |
| EXTERIOR WALL OF THE STRUCTURE UNLESS THE WALL IS ONE |
| HOUR FIRE RATED PER NFPA 37 SEC. 4.1.4. |
| |
| 12) DELETE THE OLD GAS DRAWINGS FROM THE PERMIT PACKAGE |
| AND SUBMIT TWO COMPLETE SETS OF PLANS FOR REVIEW. WPB |
| AMEND. TO FBC SEC. 107.1. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |