Plan Review Details - Permit 17120885
Plan Review Stops For Permit 17120885
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-02-28 Cont ID  
Sent By thunt Date 2018-02-28 Time 16:29 Rev Time 0.00
Received By thunt Date 2018-02-23 Time 09:58 Sent To I
Notes
2018-02-26 09:59:16RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-01 Cont ID  
Sent By tklarge Date 2018-02-01 Time 06:34 Rev Time 0.00
Received By tklarge Date 2018-01-30 Time 10:27 Sent To  
Notes
2018-01-31 10:27:32RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-11 Cont ID  
Sent By thunt Date 2018-01-11 Time 06:16 Rev Time 0.00
Received By thunt Date 2018-01-09 Time 12:52 Sent To  
Notes
2018-01-10 12:53:05RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-28 Cont ID  
Sent By thunt Date 2017-12-28 Time 15:58 Rev Time 0.00
Received By thunt Date 2017-12-22 Time 10:56 Sent To  
Notes
2017-12-27 10:56:54PLUMB -$5000

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-02-28 Cont ID  
Sent By thunt Date 2018-02-28 Time 16:29 Rev Time 0.00
Received By thunt Date 2018-02-28 Time 16:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-02-01 Cont ID  
Sent By tklarge Date 2018-02-01 Time 06:34 Rev Time 0.00
Received By tklarge Date 2018-02-01 Time 05:18 Sent To I
Notes
2018-02-01 06:28:20AT THIS POINT, I HAVE NO IDEA WHAT THIS APPLICATION IS
 FOR.
 1) THE PERMIT APPLICATION STATES THE DESCRIPTION OF
 WORK IS FOR A GREASE TRAP BUT ONE SET OF PLANS SHOWS AN
 OIL/GREASE INTERCEPTOR AND ANOTHER SET OF PLANS SHOWS
 AN OIL SEPARATOR. WHICH IS IT? CHANGE THE DESCRIPTION
 OF WORK ON THE PERMIT APPLICATION.
 2) REMOVE ALL OLD PLANS AND SPECIFICATIONS FFROM THE
 PERMIT PACKAGE AND SUBMIT TWO COMPLETE SETS OF PLANS
 THAT CLEARLY REFLECT THE SCOPE OF WORK TO BE DDONE. WPB
 AMEND. TO FBC SEC. 107.2.1.2014 .
 3) YOU HAVE SUBMITTED COPIES OF DETAILS OF A TANK FROM
 FLORIDA SEPTIC INC. THE DETAILS STATE THAT THE TANK
 COMPLIES WITH SEC. 1003.5.1 OF THE 2014 FLORIDA
 PLUMBING CODE. THERE IS NO SUCH CODE SECTION IN THE
 PLUMBING CODE AND SEC. 1003.5 IS FOR GREASE
 INTERCEPTORS. CLARIFY.
 4) OIL SEPARATOR DESIGN SHALL COMPLY WITH 2014
 FBC-PLUMBING SEC.1003.4.2, 1003.4.2.1. THERE IS A NOTE
 ON THE SPECIFICATIONS FROM FLORIDA SEPTIC THAT THE
 TREATMENT RECEPTACLE HAS BEEN DESIGNED, CONSTRUCTED AND
 STRUCTURUALLY TESTED IN ACCORDANCE WITH CHAPTER
 64E-6.013, FL. ADMIN. CODE. THE F.A.C. DOES NOT APPLY
 TO OIL SEPARATORS. CLARIFY.
 5) THE PLAN SHEET C.1 SHALL BEAR THE SEAL AND WET
 SIGNATURE OF THE ARCHITECT OF RECCORD IN ACCORDANCE
 WITH FL. ADMIN. CODE RULE 61G1-16.003.
  
 NOTE: THE NEXT PLAN REVIEW SUBMITTAL SHALL BE SUBJECT
 TO A RESUBMITTAL FEE OF 4 TIME THE AMOUNT APPLIED TO
 THE PLAN REVIEW FEE PER FL. STATUTE 553.80 (2) (B).
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-01-11 Cont ID  
Sent By thunt Date 2018-01-11 Time 06:11 Rev Time 0.00
Received By thunt Date 2018-01-11 Time 06:11 Sent To  
Notes
2018-01-11 06:16:2701/10/2018 2ND PLUMBING REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 FL STATE STAUTE 553.8.0 2(B): WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1) YOUR MASTER # 15020937 DOES NOT SHOW A KITCHEN OR
 GREASE INTERCEPTOR. PROVIDE KITCHEN FLOOR PLAN WITH
 ISOMETRIC DRAWING AND KITCHEN SPECIFICATION COMPLYING
 WITH SECTION 1003 FPC.
  
 2) THE CODE IN AFFECT FOR YOUR SUBMITTAL IS THE 5TH ED
 OF THE FLORIDA BUILDING CODE ( PLUMBING) , NOT THE 2001
 AS ON INTERCEPTOR DRAWING PROVIDED. FBC107.2.1
  
 3) GREASE INTERCEPTOR MUST ALSO COMPLY WITH GS-7 OR
 GS-7 DRAWING CITY OF WEST PALM BEACH PUBLIC WORKS
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805 -6695
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-12-28 Cont ID  
Sent By thunt Date 2017-12-28 Time 15:52 Rev Time 0.00
Received By thunt Date 2017-12-28 Time 15:52 Sent To  
Notes
2017-12-28 15:58:2912/28/2017 PLUMBING 1ST REVIEW**DENIED**
  
 PERMIT# 15020937 DOES NOT HAVE AN APPROVED GREASE
 INTERCEPTOR. THERE IS ALSO NO GREASE LINE SHOWING ON
 THE APPROVE PLUMBING ISOMETRIC DRAWING
  
 PROVIDE SIZING SPEC AND DETAILS ALONG WITH COMPLING IN
 FULL WITH ALL OF SECTION 1003
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  