2018-01-17 07:43:21 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) PROVIDE A SITE DRAINAGE PLAN THAT SHOWS COMPLIANCE |
| WITH FBC-R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE |
| DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED |
| POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS |
| SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM). |
| EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| PERCENT AWAY FROM THE BUILDING. |
| |
| 2) THE DESIGN WIND PRESSURES FOR THE ROOF AREAS ON |
| SHEET A-1 ARE NOT CORRECT. BASED ON THE PLANS AND WIND |
| DESIGN DATA THAT WAS PROVIDED, THE UPLIFT PRESSURES FOR |
| THE FLAT ROOF ARE -37.9 PSF (ZONE1), -63.6 PSF (ZONE 2) |
| AND -95.7 PSF (ZONE 3). FBC-R301.2.1 |
| |
| 3) THE DISTANCE TO THE PROPERTY LINE AT THE REAR IS |
| LESS THAN 3 FEET. PER FBC-R TABLE R302.1(1), NO |
| OPENINGS ARE ALLOWED IN WALLS LESS THAN 3 FEET FROM |
| PROPERTY LINE. EXTERIOR WALLS AND THE UNDERSIDE OF |
| PROJECTIONS THAT ARE LESS THAN 5 FEET ARE REQUIRED TO |
| HAVE A ONE HOUR FIRE RATING. THESE ITEMS WILL NEED TO |
| BE ADDRESSED WITHOUT THE UNITY OF TITLE. |
| |
| 4) SHOW COMPLIANCE WITH FBC-R314.3.1 ALTERATIONS, |
| REPAIRS AND ADDITIONS. WHEN ALTERATIONS, REPAIRS OR |
| ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE |
| SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING |
| DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE |
| EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW |
| DWELLINGS. |
| |
| 5) ALL DOORS AND WINDOWS THAT OPEN FROM THE NEW |
| ADDITION TO THE POOL SHALL BE EQUIPPED WITH AN APPROVED |
| EXIT ALARM OR OTHER MEANS OF A POOL BARRIER COMPLYING |
| WITH FBC-R4501.17.1.9. |
| |
| 6) ALL METAL WINDOW AND DOOR FRAMES WITHIN 5 FEET OF |
| THE INSIDE WALL OF THE POOL ARE REQUIRED TO BE BONDED. |
| FBCR-E 4204.2(7) |
| |
| 7) THE POOL DECK IS REQUIRED TO SLOPE AWAY FROM THE |
| POOL AND FBC-R401.3 REQUIRES IMPERVIOUS SURFACES TO BE |
| SLOPED A MINIMUM OF 2 PERCENT AWAY FROM THE BUILDING. |
| PROVISIONS SHALL BE MADE TO DRAIN THE WATER AWAY FROM |
| THE POOL AS WELL AS THE STRUCTURE SIDEWALLS AND PREVENT |
| IT FROM PONDING ON THE POOL DECK. A DECO DRAIN FOR THE |
| POOL MAY BE USED. SHOW HOW THIS WILL BE ACCOMPLISHED ON |
| THE PLANS. FBC 107.2.1 |
| |
| 8) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| AND MAXIMUM DESIGN PRESSURES FOR THE LARGE MISSILE |
| RATED EXTERIOR FRENCH DOORS. |
| |
| 9) SUBMIT TWO COPIES OF SIGNED AND SEALED RAS 117 |
| ENHANCED FASTENING CALCULATIONS AS REQUIRED BY |
| LIMITATION NUMBER 7 ON PAGE 34 OF THE PRODUCT APPROVAL |
| FOR THE POLYGLASS SELF-ADHERED ROOF SYSTEM NOA NO. |
| 17-1004.09. FBC 107.2.1.3 |
| |
| 10) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |