Plan Review Details - Permit 17120802
Plan Review Stops For Permit 17120802
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 14:26 Rev Time 0.00
Received By shill Date 2018-06-16 Time 14:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-04-24 Cont ID  
Sent By jgomez Date 2018-04-24 Time 11:14 Rev Time 0.00
Received By jgomez Date 2018-04-24 Time 09:27 Sent To  
Notes
2018-04-24 09:33:37NEW SINGLE FAMILY RESIDENCE (R3), SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 2- COMPLIED.
  
 3- SHEET A-1. REVISE THE EGRESS WINDOWS NOTE THAT IS
 LOCATED BELOW THE WINDOW SCHEDULE:
 A) COMPLIED.
 B) COMPLIED.
 C) COMPLIED.
  
 4- COMPLIED.
  
 5- RESPONSE: NOT ADDRESSED. NOTE: NEED DRAINAGE PLAN.
 SEE CITY AMENDMENTS SEC. 107.2.5 BELOW.
  
 ORIGINAL COMMENT:
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL.
 R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 CITY AMENDMENTS SEC. 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE
 AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY. IN THE CASE OF DEMOLITION, THE SITE PLAN
 SHALL SHOW CONSTRUCTION TO BE DEMOLISHED AND THE
 LOCATION AND SIZE OF EXISTING STRUCTURES AND
 CONSTRUCTION THAT ARE TO REMAIN ON THE SITE OR PLOT.
 THE BUILDING OFFICIAL IS AUTHORIZED TO WAIVE OR MODIFY
 THE REQUIREMENT FOR A SITE PLAN WHEN THE APPLICATION
 FOR PERMIT IS FOR ALTERATION OR REPAIR OR WHEN
 OTHERWISE WARRANTED.
  
  
 6- ROOF PLAN ON SHEET S-1:
 A) RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 SPECIFY THE CONNECTORS AT ALL ENDS OF ALL THE FRAMING
 MEMBERS SPECIFIED ON THE FRONT PORCH AREA. COORDINATE
 WITH DETAIL 1 ON SHEET A-3. SEC. R301.1
 FBC-RESIDENTIAL.
  
 B) RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FRAMING OF THE OUT-LOOKERS AT THE FRONT GABLE AREA.
 COORDINATE WITH DETAIL 1 ON SHEET A-3. SEC. R301.1
 FBC-RESIDENTIAL.
  
 C) RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 BEAMS AT THE REAR PORCH. THERE IS NOT PRECAST LINTEL
 SCHEDULE. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- COMPLIED.
  
 8- COMPLIED.
  
 9- SHEET A-2:
 A) COMPLIED?.
  
 B) COMPLIED.
  
 C) SEMI-COMPLIED. NOTE: IF THERE IS ANY DISCREPANCY
 BETWEEN THE REFERENCED MANUAL AND FBC AND PRODUCT
 APPROVAL SUBMITTED, THEN FBC AND PRODUCT APPROVAL
 PREVAILS.
  
 ORIGINAL COMMENT:
 CLARIFY WHY REFERENCING "THE ARMA RESIDENTIAL ROOFING
 MANUAL 2006". THIS STANDARD IS NOT REFERENCED IN THE
 FLORIDA BUILDING CODE. SEE SEC. R905.2 FBC-RESIDENTIAL
 AND REVISE AS REQUIRED. REVISE AS REQUIRED ON WALL
 SECTIONS #5 AND #6. NOTE: REVISE DETAIL #2 ON SHEET A-3
 AND DETAIL #1 ON SHEET A-4 AS WELL.
  
 D) COMPLIED.
  
 10- SECTION 5 ON SHEET S-3:
 A) RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE SPECIFICATIONS FOR THE BASE PLATE
 FASTENERS. SPECIFY HOW MUCH EMBEDMENT IS REQUIRED. WHAT
 DOES H.S STANDS FOR?. THERE IS NOT ABBREVIATION LEGEND.
 NOTE: COORDINATE INFORMATION WITH STEEL COLUMN SCHEDULE
 ON SHEET S-1, INCLUDING SIZE OF PLATE. REVISE AS
 REQUIRED TO MATCH. SEC. R301.1 FBC-RESIDENTIAL.
  
  
 B) RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 WELDING INFORMATION FOR THE STEEL COLUMN AT TOP AND
 BOTTOM PLATES IS INCOMPLETE. ONLY THE WELDING SYMBOL IS
 PROVIDED. PROVIDE COMPLETE SPECIFICATIONS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 11- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) COMPLIED.
  
 B) COMPLIED.
  
 C) COMPLIED.
  
 D) COMPLIED.
  
 E) COMPLIED.
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: (NOTE: ALL
 PRODUCT APPROVALS WILL BE SUBMITTED LATER AS DEFERRED
 SUBMITTAL)
 A) ENTRY DOOR WITH SIDELITES AND TRANSOM AS SHOWN ON
 PLANS.
 B) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS.
 C) HORIZONTAL ROLLER WINDOWS AS SPECIFIED ON PLANS.
 D) SLIDING GLASS DOORS AS SHOWN ON PLANS.
 E) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 HURRICANE IMPACT GLAZING. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE CITY SAMPLE.
 F) ROOF SHINGLES.
 G) ROOF SHINGLES UNDERLAYMENT AS SPECIFIED ON PLANS.
 H) RIDGE VENTS AS SPECIFIED ON PLANS. SEE SHEET A-1.
 I) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS (NOT SIGNING AND SEALING).
  
 14- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUE TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $192,608. THE
 PERMIT FEE BALANCE IS $3,674.29.
 NOTE: PROVIDE COPY OF THE CONSTRUCTION CONTRACT/COST
 BREAKDOWN AS REQUESTED BY ROBERT BROWN (BUILDING
 OFFICIAL). COORDINATE WITH ARMANDO FANA. DIRECTOR,
 HOUSING AND COMMUNITY DEVELOPMENT.
  
  
 *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE AND HELP EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date 2018-04-20 Cont ID  
Sent By jgomez Date 2018-04-20 Time 17:59 Rev Time 0.00
Received By jgomez Date 2018-04-20 Time 15:23 Sent To  
Notes
2018-04-20 15:24:52 
  
 *****REVIEW IN PROGRESS...... NOT FINAL YET
  
  
 NEW SINGLE FAMILY RESIDENCE (R3), SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
 NOTE: THIS MAY BE DONE LATER WHEN THE PLANS ARE
 APPROVED AND STAMPED BY THE CITY.
  
 2- COMPLIED.
  
 3- SHEET A-1. REVISE THE EGRESS WINDOWS NOTE THAT IS
 LOCATED BELOW THE WINDOW SCHEDULE:
 A) COMPLIED.
 B) COMPLIED.
 C) COMPLIED.
  
 4- COMPLIED.
  
 5- RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL.
 R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 6- ROOF PLAN ON SHEET S-1:
 A) RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 SPECIFY THE CONNECTORS AT ALL ENDS OF ALL THE FRAMING
 MEMBERS SPECIFIED ON THE FRONT PORCH AREA. COORDINATE
 WITH DETAIL 1 ON SHEET A-3. SEC. R301.1
 FBC-RESIDENTIAL.
  
 B) RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FRAMING OF THE OUT-LOOKERS AT THE FRONT GABLE AREA.
 COORDINATE WITH DETAIL 1 ON SHEET A-3. SEC. R301.1
 FBC-RESIDENTIAL.
  
 C) RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 BEAMS AT THE REAR PORCH. THERE IS NOT PRECAST LINTEL
 SCHEDULE. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- COMPLIED.
  
 8- COMPLIED.
  
 9- SHEET A-2:
 A) COMPLIED?.
  
 B) COMPLIED.
  
 C) SEMI-COMPLIED. NOTE: IF THERE IS ANY DISCREPANCY
 BETWEEN THE REFERENCED MANUAL AND FBC AND PRODUCT
 APPROVAL SUBMITTED, THEN FBC AND PRODUCT APPROVAL
 PREVAILS.
  
 ORIGINAL COMMENT:
 CLARIFY WHY REFERENCING "THE ARMA RESIDENTIAL ROOFING
 MANUAL 2006". THIS STANDARD IS NOT REFERENCED IN THE
 FLORIDA BUILDING CODE. SEE SEC. R905.2 FBC-RESIDENTIAL
 AND REVISE AS REQUIRED. REVISE AS REQUIRED ON WALL
 SECTIONS #5 AND #6. NOTE: REVISE DETAIL #2 ON SHEET A-3
 AND DETAIL #1 ON SHEET A-4 AS WELL.
  
 D) COMPLIED.
  
 10- SECTION 5 ON SHEET S-3:
 A) RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE SPECIFICATIONS FOR THE BASE PLATE
 FASTENERS. SPECIFY HOW MUCH EMBEDMENT IS REQUIRED. WHAT
 DOES H.S STANDS FOR?. THERE IS NOT ABBREVIATION LEGEND.
 NOTE: COORDINATE INFORMATION WITH STEEL COLUMN SCHEDULE
 ON SHEET S-1, INCLUDING SIZE OF PLATE. REVISE AS
 REQUIRED TO MATCH. SEC. R301.1 FBC-RESIDENTIAL.
  
  
 B) RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 WELDING INFORMATION FOR THE STEEL COLUMN AT TOP AND
 BOTTOM PLATES IS INCOMPLETE. ONLY THE WELDING SYMBOL IS
 PROVIDED. PROVIDE COMPLETE SPECIFICATIONS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 11- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) COMPLIED.
  
 B) COMPLIED.
  
 C) COMPLIED.
  
 D) COMPLIED.
  
 E) COMPLIED.
  
  
  
  
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOOR WITH SIDELITES AND TRANSOM AS SHOWN ON
 PLANS.
  
 B) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS.
  
 C) HORIZONTAL ROLLER WINDOWS AS SPECIFIED ON PLANS.
  
 D) SLIDING GLASS DOORS AS SHOWN ON PLANS.
  
 E) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 HURRICANE IMPACT GLAZING. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 F) ROOF SHINGLES.
  
 G) ROOF SHINGLES UNDERLAYMENT AS SPECIFIED ON PLANS.
 (COORDINATE WITH ITEM #9(B) ABOVE.
  
 H) RIDGE VENTS AS SPECIFIED ON PLANS. SEE SHEET A-1.
  
 I) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS (NOT SIGNING AND SEALING) AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 14- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUE TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $192,608. THE
 PERMIT FEE BALANCE IS $3,674.29.
  
 *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE AND HELP EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-17 Cont ID  
Sent By jgomez Date 2018-01-16 Time 16:37 Rev Time 0.00
Received By jgomez Date 2018-01-11 Time 12:48 Sent To  
Notes
2018-01-11 13:23:32NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
 NOTE: THIS MAY BE DONE LATER WHEN THE PLANS ARE
 APPROVED AND STAMPED BY THE CITY.
  
 2- HORIZONTAL ROLLER EGRESS WINDOW #4 MAY NOT COMPLY
 WITH THE MINIMUM CLEAR WIDTH OPENING REQUIRED BY SEC.
 R310.1.3 FBC-RESIDENTIAL, 5TH EDITION (2014). PROVIDE
 MANUFACTURER'S SPECIFICATIONS SHOWING THAT THE
 SPECIFIED SIZE COMPLIES WITH ALL THE EGRESS
 REQUIREMENTS.
  
 3- SHEET A-1. REVISE THE EGRESS WINDOWS NOTE THAT IS
 LOCATED BELOW THE WINDOW SCHEDULE:
 A) WINDOWS NEED TO HAVE A MINIMUM TOTAL CLEAR OPENING
 AREA NOT MINIMUM TOTAL GLASS AREA. SEE SEC. R310.1.1
 FBC-RESIDENTIAL AND REVISE WORDING AS REQUIRED.
  
 B) THE MINIMUM CLEAR HEIGHT IS 24" NOT 22". SEE SEC.
 R310.1.2 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 C) THE NET CLEAR OPENING SHALL BE MINIMUM 5.7 SQUARE
 FEET. THE ONLY EXCEPTION IS 5.0 SQUARE FEET FOR
 OPENINGS IN GRADE FLOOR. (NOT 4 SQUARE FEET). SEE SEC.
 R310.1.1 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 4- PROVIDE FIRE RESISTANCE SPECIFICATIONS FOR THE
 INTERIOR GARAGE DOOR LEADING FROM THE GARAGE TO THE
 MAIN HOUSE (INCLUDING THE SELF CLOSING DEVICE) AS
 REQUIRED BY SEC. R302.5.1 FBC-RESIDENTIAL.
  
 5- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL.
  
 6- ROOF PLAN ON SHEET S-1:
 A) SPECIFY THE CONNECTORS AT ALL ENDS OF ALL THE
 FRAMING MEMBERS SPECIFIED ON THE FRONT PORCH AREA.
 COORDINATE WITH DETAIL 1 ON SHEET A-3. SEC. R301.1
 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FRAMING OF THE OUT-LOOKERS AT THE FRONT GABLE AREA.
 COORDINATE WITH DETAIL 1 ON SHEET A-3. SEC. R301.1
 FBC-RESIDENTIAL.
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 BEAMS AT THE REAR PORCH. THERE IS NOT PRECAST LINTEL
 SCHEDULE. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- SPECIFY ATTIC ACCESS LOCATION AND SIZE SHOWING
 COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 8- SHEET A-0.1: PROVIDE SITE PLAN SHOWING THE
 DIMENSIONS OF THE LOT. THERE ARE NO DIMENSIONS GIVEN.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 9- SHEET A-2:
 A) WINDOW #4 SHOWN ON THE EXTERIOR ELEVATIONS DOESN'T
 MATCH TYPE OF WINDOW SPECIFIED ON THE WINDOW SCHEDULE.
 ELEVATIONS SHOW SINGLE HUNG WINDOWS. WINDOW #4 IS
 HORIZONTAL ROLLER. REVISE AS REQUIRED TO MATCH TO AVOID
 CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) CLARIFY WHICH SHINGLES UNDERLAYMENT IS GOING TO BE
 INSTALLED. " DECK ARMOR" OR 30# UNDERLAYMENT. BOTH
 SPECIFICATIONS ARE ON TYPICAL WALL SECTIONS #5 AND #6.
 REVISE AS REQUIRED ON BOTH WALL SECTIONS. NOTE: REVISE
 DETAIL #2 ON SHEET A-3 AND DETAIL #1 ON SHEET A-4 AS
 WELL. SEC. 107.2.1 CITY AMENDMENTS.
  
 C) CLARIFY WHY REFERENCING "THE ARMA RESIDENTIAL
 ROOFING MANUAL 2006". THIS STANDARD IS NOT REFERENCED
 IN THE FLORIDA BUILDING CODE. SEE SEC. R905.2
 FBC-RESIDENTIAL AND REVISE AS REQUIRED. REVISE AS
 REQUIRED ON WALL SECTIONS #5 AND #6. NOTE: REVISE
 DETAIL #2 ON SHEET A-3 AND DETAIL #1 ON SHEET A-4 AS
 WELL.
  
 D) COORDINATE ROOFING PRODUCT APPROVALS LISTED ON
 TYPICAL WALL SECTIONS #5 AND #6 WITH THOSE PRODUCT
 APPROVALS SUBMITTED TO AVOID CONFLICTS/DELAYS. SEC.
 107.2.1 CITY AMENDMENTS. NOTE: REVISE DETAIL #2 ON
 SHEET A-3 AND DETAIL #1 ON SHEET A-4 AS WELL.
  
 10- SECTION 5 ON SHEET S-3:
 A) PROVIDE COMPLETE SPECIFICATIONS FOR THE BASE PLATE
 FASTENERS. SPECIFY HOW MUCH EMBEDMENT IS REQUIRED. WHAT
 DOES H.S STANDS FOR?. THERE IS NOT ABBREVIATION LEGEND.
 NOTE: COORDINATE INFORMATION WITH STEEL COLUMN SCHEDULE
 ON SHEET S-1, INCLUDING SIZE OF PLATE. REVISE AS
 REQUIRED TO MATCH. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) WELDING INFORMATION FOR THE STEEL COLUMN AT TOP AND
 BOTTOM PLATES IS INCOMPLETE. ONLY THE WELDING SYMBOL IS
 PROVIDED. PROVIDE COMPLETE SPECIFICATIONS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 11- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) CONDITIONED FLOOR AREA SHOWN ON ITEM #6 DOESN'T
 MATCH CONDITIONED AREA SHOWN ON PLANS. REVISE AS
 REQUIRED TO MATCH. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) THE NAME OF THE BUILDER IS INCORRECT. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) PROVIDE THE NAME OF THE PERSON PREPARING THE ENERGY
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2 FBC-ENERGY
 CONSERVATION.
  
 D) ARCHITECT OF RECORD IS DESIGNING A HOUSE WITH AN
 ATTIC VENTILATION RATIO OF 1/300. SEE SHEET A-1 AND
 REVISE ATTIC VENT RATIO ON PAGE 2 OF 5 AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) PROVIDE THE INSPECTION CHECKLIST AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION.
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOOR WITH SIDELITES AND TRANSOM AS SHOWN ON
 PLANS.
  
 B) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS.
  
 C) HORIZONTAL ROLLER WINDOWS AS SPECIFIED ON PLANS.
  
 D) SLIDING GLASS DOORS AS SHOWN ON PLANS.
  
 E) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 HURRICANE IMPACT GLAZING. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 F) ROOF SHINGLES.
  
 G) ROOF SHINGLES UNDERLAYMENT AS SPECIFIED ON PLANS.
 (COORDINATE WITH ITEM #9(B) ABOVE.
  
 H) RIDGE VENTS AS SPECIFIED ON PLANS. SEE SHEET A-1.
  
 I) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS (NOT SIGNING AND SEALING) AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 14- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUE TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $192,608. THE
 PERMIT FEE BALANCE IS $3,674.29.
  
 *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE AND HELP EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-06-04 Cont ID  
Sent By ppetty Date 2018-06-04 Time 13:47 Rev Time 0.00
Received By ppetty Date 2018-06-04 Time 13:47 Sent To  
Notes
2018-06-04 13:47:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW.
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10.OK
 11. OK
 12. OK
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER, CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-17 Cont ID  
Sent By ppetty Date 2018-04-17 Time 13:09 Rev Time 0.00
Received By ppetty Date 2018-04-17 Time 13:03 Sent To  
Notes
2018-04-17 13:09:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10.
 11. FEED TO INTERIOR PANEL FROM DISCONNECT IS REQUIRED
 TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR, SIZED PER
 CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE E3704.6,
 3607.3.1
 12. PROVIDE LOCATION OF DISCONNECT ON PLAN. FBC 107.2.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER, CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-19 Cont ID  
Sent By jpearson Date 2018-01-19 Time 10:28 Rev Time 0.00
Received By jpearson Date 2018-01-19 Time 08:43 Sent To I
Notes
2018-01-19 10:28:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH
 IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT
 125% OF THE LOAD, WHICH IS A 25 AMP. PROVIDE
 CORRECTION. NEC 422.13; FBC RE3702.10
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE3609.3
 3. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE,
 INCLUDING THE GARAGE DOOR OPENER. NEC 210.8; FBC
 RE3902.2
 4. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING. BACK
 OF HOUSE RECEPTACLE IS MISSING, FRONT OF HOUSE IS NOT
 SHOWN AS GFCI PROTECTED. PROVIDE CORRECTION. NEC 210.8,
 210.52(E)(1) FBC RE E3901.7, E3902.3
 5. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION. NEC 210.11(C)(3) , FBC RE3703.4
 6. ALL RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION.
 ALSO, THE WALL SPACING OF OUTLETS IS NOT PER CODE.
 PROVIDE CORRECTIONS. NEC 210.8, 210.52(C)(1); FBC
 RE3901.4, E3902.6
 7. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE
 CORRECTION FOR MASTER BATH. NEC 210.11(C)(3),
 210.52(D); FBC RE 3703.4, 3901.6
 8. PLAN STATES THIS IS A LEVEL 2 ALTERATION, BUT
 APPLICATION STATES THIS IS A NEW HOUSE. PROVIDE
 CORRECTION. FBC 107.2.1
 9. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 11. FEED TO INTERIOR PANEL FROM DISCONNECT IS REQUIRED
 TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR, SIZED PER
 CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE E3704.6,
 3607.3.1
 12. PROVIDE LOCATION OF METER AND DISCONNECT ON PLAN.
 FBC 107.2.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-06-29 Cont ID  
Sent By jgomez Date 2018-06-29 Time 17:22 Rev Time 0.00
Received By jgomez Date 2018-06-26 Time 15:13 Sent To I
Notes
2018-06-27 15:13:21IMPACT FEES ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 14:26 Rev Time 0.00
Received By shill Date 2018-05-24 Time 13:56 Sent To  
Notes
2018-05-25 13:56:49R32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-24 Cont ID  
Sent By jgomez Date 2018-04-24 Time 11:49 Rev Time 0.00
Received By jgomez Date 2018-04-02 Time 13:48 Sent To I
Notes
2018-04-03 13:48:47R13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-01-19 Time   Rev Time 0.00
Received By cpuell Date 2017-12-28 Time 11:52 Sent To  
Notes
2017-12-29 11:52:24R13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-06-29 Cont ID  
Sent By jgomez Date 2018-06-29 Time 17:22 Rev Time 0.00
Received By jgomez Date 2018-06-29 Time 17:19 Sent To  
Notes
2018-06-29 17:24:35NO FEES. MU-2018-022359.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-04-24 Cont ID  
Sent By jgomez Date 2018-04-24 Time 11:47 Rev Time 0.00
Received By jgomez Date 2018-04-24 Time 11:47 Sent To  
Notes
2018-04-24 11:47:53BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-01-16 Cont ID  
Sent By jgomez Date 2018-01-16 Time 18:25 Rev Time 0.00
Received By jgomez Date 2018-01-16 Time 18:25 Sent To  
Notes
2018-01-16 18:25:351- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-24 Cont ID  
Sent By jgomez Date 2018-04-24 Time 11:55 Rev Time 0.00
Received By jgomez Date 2018-04-24 Time 11:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-01-18 Cont ID  
Sent By jgomez Date 2018-01-18 Time 09:41 Rev Time 0.00
Received By jgomez Date 2018-01-18 Time 09:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-06-13 Cont ID  
Sent By gjohnson Date 2018-06-13 Time 14:32 Rev Time 0.00
Received By gjohnson Date 2018-06-13 Time 14:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-04-17 Cont ID  
Sent By thunt Date 2018-04-17 Time 19:11 Rev Time 0.00
Received By thunt Date 2018-04-17 Time 19:09 Sent To  
Notes
2018-04-17 19:10:1404/17/2018 2ND PLUMBING REVIEW**DENIED**
  
 1) BATH #1 ISOMETRIC IS STILL SHOWING 2 WET VENTED
 FIXTURES ABOVE THE UPSTREAM DRY-VENT. FBC-R P 3108.2.1
  
 2) MASTER BATHROOM TOILET IS BEING WET VENTED FROM THE
 LAUNDRY. FBC-R P3108.1 WET VENT OF BATHROOM FIXTURES
 ARE ONLY PERMITTED WITH THE BATHROOM GROUP
  
 3) ADDRESS IS REQUIRED ON THE PLAN. FBC 107.2.1
  
 4) THE FLORIDA ENERGY EFFICIENCY FORM R405-2014 IS
 CALLING OUT A 40 GALLON WATER HEATER WITH A E.F OF .92.
 AS OF APRIL 16, 2015 ALL RESDENTIAL WATER HEATER'S ARE
 REQUIRED TO BE .95 E.F UP TO 55 GALLONS. FBC- ENERGY
 CONSERVATION R 405-2017 AS DEFINED IN THE CODE OF
 FEDERAL REGULATION (CFR) 75 FR 2012.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-18 Cont ID  
Sent By jgomez Date 2018-01-18 Time 10:53 Rev Time 0.00
Received By jgomez Date 2018-01-18 Time 09:42 Sent To  
Notes
2018-01-18 11:17:21NEW SINGLE FAMILY RESIDENCE (R3), PLUMBING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- REVISE PLUMBING RISER DIAGRAM ON SHEET P-1:
 A) NO MORE THAN ONE WET-VENTED FIXTURE DRAIN SHALL
 DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN
 CONNECTION. MASTER BATHROOM AND BATHROOM #1 SHOW TWO
 WET-VENTED FIXTURE DRAINS. (THE WATER CLOSET AND SHOWER
 OR TUB). REVISE AS REQUIRED BY SEC. P3108.2.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) PLUMBING RISER DIAGRAM IS MISSING THE DISHWASHER.
 REVISE AS REQUIRED. SEC. P2717 FBC-RESIDENTIAL.
  
 C) VENTING OF THE KITCHEN SINK IS NOT CLEAR. THERE IS
 NOT WALL BEHIND THE SINK. CLARIFY HOW THE VENTING IS
 PROVIDED. SEC. P3104.1 FBC-RESIDENTIAL.
  
 D) THERE ARE TWO SINKS IN THE MASTER BATHROOM. RISER
 ONLY SHOWS ONE. REVISE AS REQUIRED TO MATCH PLANS. SEC.
 107.2.1 CITY AMENDMENTS.
  
 *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE AND HELP EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2018-04-24 Cont ID  
Sent By jgomez Date 2018-04-24 Time 11:48 Rev Time 0.00
Received By jgomez Date 2018-04-24 Time 11:48 Sent To  
Notes
2018-04-24 11:49:38DEFERRED SUBMITTAL
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF SHINGLES.
  
 B) ROOF SHINGLES UNDERLAYMENT AS SPECIFIED ON PLANS.
  
 C) RIDGE VENTS AS SPECIFIED ON PLANS. SEE SHEET A-1.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-01-18 Cont ID  
Sent By jgomez Date 2018-01-18 Time 09:09 Rev Time 0.00
Received By jgomez Date 2018-01-18 Time 09:09 Sent To  
Notes
2018-01-18 09:10:541- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF SHINGLES.
  
 B) ROOF SHINGLES UNDERLAYMENT AS SPECIFIED ON PLANS.
  
 C) RIDGE VENTS AS SPECIFIED ON PLANS. SEE SHEET A-1.

Review Stop Z ZONING
Rev No 3 Status P Date 2018-06-01 Cont ID  
Sent By awooten Date 2018-06-01 Time   Rev Time 0.00
Received By awooten Date 2018-06-01 Time   Sent To  
Notes
2018-06-01 15:58:12******ZONING PROVISO******
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING CONDITIONS SHALL BE ADDRESSED:
 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW.
  
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
  
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2018-04-06 Cont ID  
Sent By awooten Date 2018-04-06 Time 08:41 Rev Time 0.00
Received By awooten Date 2018-04-05 Time 13:56 Sent To  
Notes
2018-04-06 08:41:40*****ZONING REVIEW FAILED********
  
 THE FOLLOWING LANDSCAPING REQUIREMENTS ARE REQUIRED FOR
 NEW RESIDENTIAL DEVELOPMENT:
  
 GENERAL LANDSCAPING STANDARDS FOR SINGLE-FAMILY
 DWELLING UNITS SHALL BE AS FOLLOWS:
 A. SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
 B. PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PLAN WITH TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 THERE IS A SECOND OPTION OF SUBMITING A CONDITIONAL
 LANDSCAPING APPROVAL APPLICATION SO THAT THE PERMIT CAN
 BE APPROVED. HOWEVER, THE CERTIFICATE OF OCCUPANCY
 CANNOT BE GENERATED UNTIL A LANDSCAPE PLAN HAS BEEN
 SUBMITTED AND APPROVED. PLEASE CONTACT ME FOR MORE
 INFORMATION ON THE CONDITIONAL APPROVAL PROCESS.
  
 **************THE CONDITIONAL LANDSCAPE APPROVAL
 APPLIICATION MUST BE SUBMITTED AND PROCESSED, PRIOR TO
 APPROVAL.***********************
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By AV Date 2018-01-09 Time   Rev Time  
Received By   Date 2018-01-09 Time   Sent To  
Notes
2018-01-09 11:33:16*****ZONING REVIEW FAILED********
  
 THE FOLLOWING LANDSCAPING REQUIREMENTS ARE REQUIRED FOR
 NEW RESIDENTIAL DEVELOPMENT:
  
 GENERAL LANDSCAPING STANDARDS FOR SINGLE-FAMILY
 DWELLING UNITS SHALL BE AS FOLLOWS:
 A. SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
 B. PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PLAN WITH TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 THERE IS A SECOND OPTION OF SUBMITING A CONDITIONAL
 LANDSCAPING APPROVAL APPLICATION SO THAT THE PERMIT CAN
 BE APPROVED. HOWEVER, THE CERTIFICATE OF OCCUPANCY
 CANNOT BE GENERATED UNTIL A LANDSCAPE PLAN HAS BEEN
 SUBMITTED AND APPROVED. PLEASE CONTACT ME FOR MORE
 INFORMATION ON THE CONDITIONAL APPROVAL PROCESS.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  