Plan Review Stops For Permit 17120788 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-03-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-03-22 |
Time |
10:52 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-03-22 |
Time |
10:52 |
Sent To |
I |
|
Notes |
2018-03-22 10:55:08 | BUILDING PROVISO | | PLEASE CORRECT THE ITEMS LISTED BELOW: | | | | 1) THE BUILDING CODE AND WIND CODE IS INCORRECTLY | | SPECIFIED AS FBC 6TH EDITION ON THE COVERSHEET CS-1. | | THE 2014 FBC- RESIDENTIAL APPLIES TO THIS PROJECT, THE | | 2017 FBC APPLIES TO PREMITS THAT ARE APPLIED FOR AFTER | | JANUARY 1, 2018. FS CHAPTER 553 | | | | 2) THE TRUSS LAYOUT PLAN IS REQUIRED TO BE REVIEWED AND | | APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT. FAC | | 61G15-30.005 & 61G15-31.003 | | | | 3) THE ENERGY CALCULATIONS ARE REQUIRED TO BE SIGNED | | AND DATED BY THE OWNER AGENT. 2014 FBC ENERGY | | CONSERVATION SECTION R103.1.1.2 THE JURISDICTION NUMBER | | ON THE FORM IS NOT CORRECT. IT SHOULD BE 604700 AND NOT | | 6047010. THE 2014 FBC- RESIDENTIAL APPLIES TO THIS | | PROJECT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-03-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-03-22 |
Time |
10:42 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-03-22 |
Time |
07:15 |
Sent To |
I |
|
Notes |
2018-03-22 09:48:58 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE BUILDING CODE AND WIND CODE IS INCORRECTLY | | SPECIFIED AS FBC 6TH EDITION ON THE COVERSHEET CS-1. | | THE 2014 FBC- RESIDENTIAL APPLIES TO THIS PROJECT, THE | | 2017 FBC APPLIES TO PREMITS THAT ARE APPLIED FOR AFTER | | JANUARY 1, 2018. FS CHAPTER 553 | | | | 2) THE TRUSS LAYOUT PLAN IS REQUIRED TO BE REVIEWED AND | | APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT. FAC | | 61G15-30.005 & 61G15-31.003 | | | | 3) THE ENERGY CALCULATIONS ARE REQUIRED TO BE SIGNED | | AND DATED BY THE OWNER AGENT. 2014 FBC ENERGY | | CONSERVATION SECTION R103.1.1.2 THE JURISDICTION NUMBER | | ON THE FORM IS NOT CORRECT. IT SHOULD BE 604700 AND NOT | | 6047010. THE 2014 FBC- RESIDENTIAL APPLIES TO THIS | | PROJECT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-02-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-02-28 |
Time |
17:38 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-02-27 |
Time |
17:29 |
Sent To |
I |
|
Notes |
2018-02-28 17:38:17 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE LOCATION OF THE JOB IS INCORRECTLY IDENTIFIED AS | | 807 - 5TH STREET ON THE COVERSHEET, CS-1 AND IN THE | | TITLE BLOCKS OF THE OTHER SHEETS. PLEASE CORRECT. FBC | | 107.2.1 | | | | 2) THE DIGITAL FOLDER LABELED SOIL REPORT IS EMPTY. | | PLEASE CLARIFY. FBC 107.2.1 | | | | 3) THE PRODUCT APPROVAL NUMBER THAT IS LISTED ON SHEET | | A-3.0 FOR THE LOMANCO ROOF VENTS DOES NOT MATCH THE | | PRODUCT APPROVALS THAT WERE SUBMITTED (NOA | | NO.16-0510.28). FS 553.842 | | | | 4) THE TRUSS LAYOUT PLAN AND THE TRUSS DRAWINGS | | REFERENCE THE DESIGN CODE AS THE 2017 FBC. THE PERMIT | | WAS APPLIED FOR ON DECEMBER 20, 2017 AND THE 2014 FBC | | IS THE CODE THAT APPLIES TO THIS PROJECT. THE PLANS | | SPECIFY THE 2014 FBC. PLEASE REVISE TRUSS DOCUMENTS | | ACCORDINGLY. FS CHAPTER 553 | | | | 5) THE PERMIT VALUATION HAS BEEN INCREASED FROM | | $137,200.00 TO $162,135.00 BASED ON THE CURRENT ICC | | VALUATION DATA. FBC 109.3 | | | | 6) THE ENERGY CALCULATIONS ARE ON THE 2017 FBC FORMS | | AND THE EQUIPMENT SIZING CALCULATIONS ARE BASED ON THE | | 2017 FBC. THE 2014 FBC- RESIDENTIAL APPLIES TO THIS | | PROJECT, THE 2017 FBC APPLIES TO PREMITS THAT ARE | | APPLIED FOR AFTER JANUARY 1, 2018. FS CHAPTER 553 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-03-19 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-03-19 |
Time |
07:16 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-03-19 |
Time |
07:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-02-06 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-02-06 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-02-06 |
Time |
16:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2018-02-02 |
|
|
Cont ID |
|
Sent By |
destabro |
Date |
2018-02-02 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
destabro |
Date |
2018-02-02 |
Time |
11:12 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-03-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-03-22 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-03-12 |
Time |
14:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-02-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-02-28 |
Time |
17:38 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-01-19 |
Time |
12:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
P |
Date |
2018-02-27 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-02-27 |
Time |
18:30 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-02-27 |
Time |
17:29 |
Sent To |
|
|
Notes |
2018-02-27 18:30:12 | MU-2017-35265, PAID $9,585.84 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2018-03-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-03-22 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-03-22 |
Time |
09:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2018-02-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-02-28 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-02-28 |
Time |
14:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2018-03-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-03-22 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-03-22 |
Time |
09:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2018-02-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-02-28 |
Time |
11:44 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-02-28 |
Time |
11:44 |
Sent To |
|
|
Notes |
2018-02-28 13:36:20 | PLANS WERE REDLINED AND APPROVED BY TIM LARGE ON | | 2/21/2018. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2018-03-01 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-03-01 |
Time |
10:15 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-03-01 |
Time |
10:15 |
Sent To |
|
|
Notes |
2018-03-01 10:19:02 | FL10674-R12 OWENS CORNING ASPHALT SHINGLES | | NOA NO. 16-0510.28 LOMANCO 700 SERIES LOUVERED ROOF | | VENTS |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2018-02-02 |
|
|
Cont ID |
|
Sent By |
destabro |
Date |
2018-02-02 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
destabro |
Date |
2018-02-02 |
Time |
11:13 |
Sent To |
B |
|
Notes |
|
|