Plan Review Details - Permit 17120788
Plan Review Stops For Permit 17120788
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-22 Cont ID  
Sent By rmcdouga Date 2018-03-22 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2018-03-22 Time 10:52 Sent To I
Notes
2018-03-22 10:55:08BUILDING PROVISO
 PLEASE CORRECT THE ITEMS LISTED BELOW:
  
 1) THE BUILDING CODE AND WIND CODE IS INCORRECTLY
 SPECIFIED AS FBC 6TH EDITION ON THE COVERSHEET CS-1.
 THE 2014 FBC- RESIDENTIAL APPLIES TO THIS PROJECT, THE
 2017 FBC APPLIES TO PREMITS THAT ARE APPLIED FOR AFTER
 JANUARY 1, 2018. FS CHAPTER 553
  
 2) THE TRUSS LAYOUT PLAN IS REQUIRED TO BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT. FAC
 61G15-30.005 & 61G15-31.003
  
 3) THE ENERGY CALCULATIONS ARE REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER AGENT. 2014 FBC ENERGY
 CONSERVATION SECTION R103.1.1.2 THE JURISDICTION NUMBER
 ON THE FORM IS NOT CORRECT. IT SHOULD BE 604700 AND NOT
 6047010. THE 2014 FBC- RESIDENTIAL APPLIES TO THIS
 PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-22 Cont ID  
Sent By rmcdouga Date 2018-03-22 Time 10:42 Rev Time 0.00
Received By rmcdouga Date 2018-03-22 Time 07:15 Sent To I
Notes
2018-03-22 09:48:58PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE BUILDING CODE AND WIND CODE IS INCORRECTLY
 SPECIFIED AS FBC 6TH EDITION ON THE COVERSHEET CS-1.
 THE 2014 FBC- RESIDENTIAL APPLIES TO THIS PROJECT, THE
 2017 FBC APPLIES TO PREMITS THAT ARE APPLIED FOR AFTER
 JANUARY 1, 2018. FS CHAPTER 553
  
 2) THE TRUSS LAYOUT PLAN IS REQUIRED TO BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT. FAC
 61G15-30.005 & 61G15-31.003
  
 3) THE ENERGY CALCULATIONS ARE REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER AGENT. 2014 FBC ENERGY
 CONSERVATION SECTION R103.1.1.2 THE JURISDICTION NUMBER
 ON THE FORM IS NOT CORRECT. IT SHOULD BE 604700 AND NOT
 6047010. THE 2014 FBC- RESIDENTIAL APPLIES TO THIS
 PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-28 Cont ID  
Sent By rmcdouga Date 2018-02-28 Time 17:38 Rev Time 0.00
Received By rmcdouga Date 2018-02-27 Time 17:29 Sent To I
Notes
2018-02-28 17:38:17PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE LOCATION OF THE JOB IS INCORRECTLY IDENTIFIED AS
 807 - 5TH STREET ON THE COVERSHEET, CS-1 AND IN THE
 TITLE BLOCKS OF THE OTHER SHEETS. PLEASE CORRECT. FBC
 107.2.1
  
 2) THE DIGITAL FOLDER LABELED SOIL REPORT IS EMPTY.
 PLEASE CLARIFY. FBC 107.2.1
  
 3) THE PRODUCT APPROVAL NUMBER THAT IS LISTED ON SHEET
 A-3.0 FOR THE LOMANCO ROOF VENTS DOES NOT MATCH THE
 PRODUCT APPROVALS THAT WERE SUBMITTED (NOA
 NO.16-0510.28). FS 553.842
  
 4) THE TRUSS LAYOUT PLAN AND THE TRUSS DRAWINGS
 REFERENCE THE DESIGN CODE AS THE 2017 FBC. THE PERMIT
 WAS APPLIED FOR ON DECEMBER 20, 2017 AND THE 2014 FBC
 IS THE CODE THAT APPLIES TO THIS PROJECT. THE PLANS
 SPECIFY THE 2014 FBC. PLEASE REVISE TRUSS DOCUMENTS
 ACCORDINGLY. FS CHAPTER 553
  
 5) THE PERMIT VALUATION HAS BEEN INCREASED FROM
 $137,200.00 TO $162,135.00 BASED ON THE CURRENT ICC
 VALUATION DATA. FBC 109.3
  
 6) THE ENERGY CALCULATIONS ARE ON THE 2017 FBC FORMS
 AND THE EQUIPMENT SIZING CALCULATIONS ARE BASED ON THE
 2017 FBC. THE 2014 FBC- RESIDENTIAL APPLIES TO THIS
 PROJECT, THE 2017 FBC APPLIES TO PREMITS THAT ARE
 APPLIED FOR AFTER JANUARY 1, 2018. FS CHAPTER 553

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-19 Cont ID  
Sent By jpearson Date 2018-03-19 Time 07:16 Rev Time 0.00
Received By jpearson Date 2018-03-19 Time 07:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-02-06 Cont ID  
Sent By jleahy Date 2018-02-06 Time 16:49 Rev Time 0.00
Received By jleahy Date 2018-02-06 Time 16:49 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-02-02 Cont ID  
Sent By destabro Date 2018-02-02 Time 11:12 Rev Time 0.00
Received By destabro Date 2018-02-02 Time 11:12 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-22 Cont ID  
Sent By rmcdouga Date 2018-03-22 Time 10:47 Rev Time 0.00
Received By rmcdouga Date 2018-03-12 Time 14:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-28 Cont ID  
Sent By rmcdouga Date 2018-02-28 Time 17:38 Rev Time 0.00
Received By rmcdouga Date 2018-01-19 Time 12:36 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2018-02-27 Cont ID  
Sent By rmcdouga Date 2018-02-27 Time 18:30 Rev Time 0.00
Received By rmcdouga Date 2018-02-27 Time 17:29 Sent To  
Notes
2018-02-27 18:30:12MU-2017-35265, PAID $9,585.84

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-03-22 Cont ID  
Sent By rmcdouga Date 2018-03-22 Time 09:14 Rev Time 0.00
Received By rmcdouga Date 2018-03-22 Time 09:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-02-28 Cont ID  
Sent By rmcdouga Date 2018-02-28 Time 14:40 Rev Time 0.00
Received By rmcdouga Date 2018-02-28 Time 14:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-22 Cont ID  
Sent By rmcdouga Date 2018-03-22 Time 09:27 Rev Time 0.00
Received By rmcdouga Date 2018-03-22 Time 09:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-02-28 Cont ID  
Sent By rmcdouga Date 2018-02-28 Time 11:44 Rev Time 0.00
Received By rmcdouga Date 2018-02-28 Time 11:44 Sent To  
Notes
2018-02-28 13:36:20PLANS WERE REDLINED AND APPROVED BY TIM LARGE ON
 2/21/2018.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-03-01 Cont ID  
Sent By rmcdouga Date 2018-03-01 Time 10:15 Rev Time 0.00
Received By rmcdouga Date 2018-03-01 Time 10:15 Sent To  
Notes
2018-03-01 10:19:02FL10674-R12 OWENS CORNING ASPHALT SHINGLES
 NOA NO. 16-0510.28 LOMANCO 700 SERIES LOUVERED ROOF
 VENTS

Review Stop Z ZONING
Rev No 1 Status P Date 2018-02-02 Cont ID  
Sent By destabro Date 2018-02-02 Time 11:13 Rev Time 0.00
Received By destabro Date 2018-02-02 Time 11:13 Sent To B
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved