Plan Review Details - Permit 17120769
Plan Review Stops For Permit 17120769
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-09-20 Cont ID  
Sent By rmcdouga Date 2018-09-20 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2018-09-20 Time 16:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-07-25 Cont ID  
Sent By rmcdouga Date 2018-07-25 Time 08:15 Rev Time 0.00
Received By rmcdouga Date 2018-07-25 Time 07:44 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-06-21 Cont ID  
Sent By rmcdouga Date 2018-06-21 Time 08:58 Rev Time 0.00
Received By rmcdouga Date 2018-06-21 Time 08:58 Sent To P
Notes
2018-06-21 08:57:58PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE VALUE OF $9,200.00 STATED ON THE REVISION
 APPLICATION IS NOT ADEQUATE FOR THE ADDITIONAL SCOPE
 SPECIFIED ON THE DRAWING THAT WAS SUBMITTED. PROVIDE AN
 ITEMIZED COST BREAK DOWN FOR THE PROPOSED REVISED SCOPE
 OF WORK WITH AN ACCURATE TOTAL VALUE. FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5)THE PRODUCT APPROVAL (NOA NO. 17-1108.23) THAT IS
 SPECIFIED ON THE PLANS FOR THE EXTERIOR DOORS IS FOR A
 BI-FOLDING WINDOW. PLEASE REVISE PLANS AND SUBMIT THE
 PRODUCT APPROVALS FOR THE OUTSWING EXTERIOR DOORS. FBC
 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR
 THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001
 PER FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA
 NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM
 DESIGN PRESSURES FOR EACH OF THE WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES. IF THE
 WINDOWS ARE NOT LARGE MISSILE IMPACT RATED, THEN SUBMIT
 PRODUCT APPROVALS FOR THE STORM PANELS ALONG WITH A KEY
 PLAN AND INSTALLATION SCHEDULE.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) THE APPROVED PLANS WILL NEED TO BE REVIEWED BY PALM
 BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE.
 SEE THE IMPACT FEE REVIEW FOR DETAILS.
  
 10) COMPLIED.
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-01 Cont ID  
Sent By rmcdouga Date 2018-05-01 Time 19:04 Rev Time 0.00
Received By rmcdouga Date 2018-04-25 Time 17:55 Sent To I
Notes
2018-04-25 16:37:32PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE VALUE OF $9,200.00 STATED ON THE REVISION
 APPLICATION IS NOT ADEQUATE FOR THE ADDITIONAL SCOPE
 SPECIFIED ON THE DRAWING THAT WAS SUBMITTED. PROVIDE AN
 ITEMIZED COST BREAK DOWN FOR THE PROPOSED REVISED SCOPE
 OF WORK WITH AN ACCURATE TOTAL VALUE. FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) SUBMIT TWO SETS OF A FLOOR PLAN THAT ACCURATELY
 SHOWS AND DESCRIBES THE EXISTING CONDITIONS. FBC
 107.2.1 (INDICATE ON THE PLANS THE 598 SQFT. OF STORAGE
 AREA THAT WILL BE CONVERTED TO LIVING AREA.)
  
 3) THE PLANS THAT WERE SUBMITTED DO NOT MATCH THE PALM
 BEACH COUNTY PROPERTY APPRAISER'S RECORDS. SHOW THE
 ENTIRE STRUCTURE THAT IS UNDER ROOF ON THE PLANS
 INCLUDING CARPORTS, PORCHES, ETC. IF THE EXISTING
 STRUCTURE DOES NOT MATCH THE PROPERTY APPRAISER'S
 DIAGRAM, EXPLAIN THE DIFFERENCES. FBC 107.2.1 ( THE
 ROOM CONTAINING THE WATER HEATER AND WASHER IS NOT
 SHOWN ON THE PROPERTY APPRAISER'S DRAWINGS AND THE CITY
 HAS NO RECORD OF IT. UNLESS YOU CAN PROVIDE PROOF THAT
 IT WAS CONSTRUCTED WITH THE PROPER PERMITS AND
 INSPECTIONS, IT WILL NEED TO BE REMOVED OR BROUGHT INTO
 COMPLIANCE.)
  
 4) COMPLIED.
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE
 WINDOW/GLASS TYPES, STRUCTURAL MULLIONS AND EXTERIOR
 DOOR TYPES. IF THE WINDOWS ARE NOT LARGE MISSILE IMPACT
 RATED, THEN SUBMIT PRODUCT APPROVALS FOR THE STORM
 PANELS ALONG WITH A KEY PLAN AND INSTALLATION SCHEDULE.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) THE APPROVED PLANS WILL NEED TO BE REVIEWED BY PALM
 BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE.
 SEE THE IMPACT FEE REVIEW FOR DETAILS.
  
 10) (NEW COMMENT) THE PERMIT THAT IS BEING REVISED WAS
 ISSUED UNDER THE 2014 FBC, FIFTH EDITION AND THE 2011
 NEC. REVISE THE DESIGN CRITERIA ON THE PLANS
 ACCORDINGLY.
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-04 Cont ID  
Sent By rmcdouga Date 2018-01-04 Time 16:12 Rev Time 0.00
Received By rmcdouga Date 2018-01-03 Time 11:40 Sent To  
Notes
2018-01-04 14:33:30PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE VALUE OF $9,200.00 STATED ON THE REVISION
 APPLICATION IS NOT ADEQUATE FOR THE ADDITIONAL SCOPE
 SPECIFIED ON THE DRAWING THAT WAS SUBMITTED. PROVIDE AN
 ITEMIZED COST BREAK DOWN FOR THE PROPOSED REVISED SCOPE
 OF WORK WITH AN ACCURATE TOTAL VALUE. FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) SUBMIT TWO SETS OF A FLOOR PLAN THAT ACCURATELY
 SHOWS AND DESCRIBES THE EXISTING CONDITIONS. FBC
 107.2.1
  
 3) THE PLANS THAT WERE SUBMITTED DO NOT MATCH THE PALM
 BEACH COUNTY PROPERTY APPRAISER'S RECORDS. SHOW THE
 ENTIRE STRUCTURE THAT IS UNDER ROOF ON THE PLANS
 INCLUDING CARPORTS, PORCHES, ETC. IF THE EXISTING
 STRUCTURE DOES NOT MATCH THE PROPERTY APPRAISER'S
 DIAGRAM, EXPLAIN THE DIFFERENCES. FBC 107.2.1
  
 4) PROVIDE EXISTING AND PROPOSED AREA TABULATIONS ON
 THE PLANS. FBC 107.2.1
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE
 WINDOW/GLASS TYPES, STRUCTURAL MULLIONS AND EXTERIOR
 DOOR TYPES. IF THE WINDOWS ARE NOT LARGE MISSILE IMPACT
 RATED, THEN SUBMIT PRODUCT APPROVALS FOR THE STORM
 PANELS ALONG WITH A KEY PLAN AND INSTALLATION SCHEDULE.
  
 6) SHOW HOW THE BEDROOM WINDOWS WILL COMPLY WITH
 FBC-R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED.
 BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM
 SHALL HAVE AT LEAST ONE OPERABLE EMERGENCY ESCAPE AND
 RESCUE OPENING.
  
 FBC-R310.1.1 MINIMUM OPENING AREA. ALL EMERGENCY ESCAPE
 AND RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR
 OPENING OF 5.7 SQUARE FEET. EXCEPTION: GRADE FLOOR
 OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5
 SQUARE FEET.
  
 FBC-R310.1.2 MINIMUM OPENING HEIGHT.
 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24
 INCHES.
  
 FBC-R310.1.3 MINIMUM OPENING WIDTH.
 THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES.
  
 7) SPECIFY THE OCCUPANCY TYPE ON THE PLANS. FBC 107.2.1
  
 8) SPECIFY THE EXPOSURE CATEGORY OF THE PROJECT ON THE
 PLANS. FBC-R301.2.1.4
  
 9) THE APPROVED PLANS WILL NEED TO BE REVIEWED BY PALM
 BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE.
 SEE THE IMPACT FEE REVIEW FOR DETAILS.
  
 10) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-07-26 Cont ID  
Sent By jleahy Date 2018-07-26 Time 10:38 Rev Time 0.00
Received By jleahy Date 2018-07-26 Time 10:38 Sent To  
Notes
2018-07-26 11:02:54FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVISO!!!!
  
 LOAD CALCULATION IS NOT IN ACCORDANCE WITH ARTICLE 220
 OF THE NEC, OR FBC RESIDENTIAL E3602.2 SERVICE LOAD.
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-06-20 Cont ID  
Sent By jleahy Date 2018-06-20 Time 17:45 Rev Time 0.00
Received By jleahy Date 2018-06-20 Time 17:45 Sent To B
Notes
2018-06-20 17:51:50FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 OUTLET SPACING TO MEET CODE..
  
 WALL SPACING/OUTLETS REQUIRED:
  
 E3901.2.1 SPACING. RECEPTACLES SHALL BE INSTALLED SO
 THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR
 LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET. [210.52(A)(1)]
  
 E3901.2.2 WALL SPACE.
 AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE
 FOLLOWING: [210.52(A)(2)]
 .1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN WIDTH,
 INCLUDING SPACE MEASURED AROUND CORNERS, AND THAT IS
 UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND SIMILAR
 OPENINGS, FIREPLACES, AND FIXED CABINETS.
 .2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR
 WALLS, EXCLUDING SLIDING PANELS.
 .3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS
 RAILINGS AND FREESTANDING BAR-TYPE COUNTERS
  
 VLAUE FOR THE ADDITIONAL WORK LOW.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA
 OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-19 Cont ID  
Sent By jleahy Date 2018-04-19 Time 16:39 Rev Time 0.00
Received By jleahy Date 2018-04-19 Time 16:39 Sent To  
Notes
2018-04-19 16:44:30FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PLAN SHOWS NEW SERVICE, LOOKS TO BE MORE THAN 8' OF
 SERVIE CONDUCTOR INSTALLED WITHIN THE BUILDING.
  
 PLAN LOOKS TO BE A COMPLETE REWIRE? IS IT?
  
 NEED PANEL SCHEDULE
  
 IF THIS IS A REWIRE ADDITIONAL COMMENTS WILL BE GIVEN.
  
 IF THIS IS A REWIRE THEN THE VALUE OF THE WORK HAS NOT
 BEEN UPDATED FOR THE REWIRE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-04 Cont ID  
Sent By jleahy Date 2018-01-04 Time 16:57 Rev Time 0.00
Received By jleahy Date 2018-01-04 Time 16:57 Sent To I
Notes
2018-01-04 17:02:27 
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW EXISTING FROM NEW ELECTRICAL WORK
  
 SHOW LOCATION OF SERVICE
  
 NO LIGHTING CIRCUITS OR OUTLETS ARE SHOWN
  
 OUTLET SPACING TO BE PER CODE.
 SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET.
 PROVIDE CORRECTION. NEC 210.52; FBC RE3901.2.1

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-09-20 Cont ID  
Sent By rmcdouga Date 2018-09-20 Time 16:18 Rev Time 0.00
Received By rmcdouga Date 2018-09-19 Time 16:03 Sent To  
Notes
2018-09-20 16:03:30IMPACT FEES ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-07-26 Cont ID  
Sent By jleahy Date 2018-07-26 Time 11:03 Rev Time 0.00
Received By jleahy Date 2018-07-11 Time 13:52 Sent To  
Notes
2018-07-19 13:52:50RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-21 Cont ID  
Sent By tklarge Date 2018-06-21 Time 11:23 Rev Time 0.00
Received By tklarge Date 2018-06-14 Time 16:16 Sent To  
Notes
2018-06-14 16:16:35RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-01 Cont ID  
Sent By rmcdouga Date 2018-05-01 Time 19:04 Rev Time 0.00
Received By rmcdouga Date 2018-04-18 Time 16:03 Sent To  
Notes
2018-04-18 16:03:29RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-04 Cont ID  
Sent By jleahy Date 2018-01-04 Time 17:02 Rev Time 0.00
Received By jleahy Date 2017-12-20 Time 13:32 Sent To  
Notes
2017-12-21 13:32:17REVISION ROUTED TO RMCDOUGAL

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-09-20 Cont ID  
Sent By rmcdouga Date 2018-09-20 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2018-09-20 Time 16:17 Sent To  
Notes
2018-09-20 16:18:42MU-2018-27295, PAID $180.65

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-01-04 Cont ID  
Sent By rmcdouga Date 2018-01-04 Time 16:14 Rev Time 0.00
Received By rmcdouga Date 2018-01-04 Time 16:13 Sent To  
Notes
2018-01-04 16:14:33BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-07-24 Cont ID  
Sent By lcrespo Date 2018-07-24 Time 16:46 Rev Time 0.00
Received By lcrespo Date 2018-07-24 Time 16:19 Sent To  
Notes
2018-07-24 16:47:0307/24/18 APPROVED BY PLUMBING AND SENT TO MCDOUGAL, LAC

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-06-21 Cont ID  
Sent By rmcdouga Date 2018-06-21 Time 11:23 Rev Time 0.00
Received By tklarge Date 2018-06-21 Time 11:21 Sent To I
Notes
2018-06-21 11:23:41SUBMIT A CODE COMPLIANT SANITARY RISER DIAGRAM FOR
 REVIEW. THERE ARE TOO MANY CODE VIOLATIONS ON THIS
 DRAWING TO LIST. WPB AMEND. TO FBC SEC. 107.3.5.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-04-25 Cont ID  
Sent By rmcdouga Date 2018-04-25 Time 16:39 Rev Time 0.00
Received By rmcdouga Date 2018-04-25 Time 16:39 Sent To  
Notes
2018-04-25 17:51:06PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY PLUMBING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLUMBING RISER DIAGRAM CONTAINS NUMEROUS CODE
 VIOLATIONS. BASED ON THE PLUMBING DRAWING THAT WAS
 SUBMITTED IT APPEARS THE PERSON THAT PRODUCED THE
 PLUMBING RISER DIAGRAM IS NOT PROFICIENT WITH THESE
 DRAWINGS. PLEASE CONSULT A DESIGN PROFESSIONAL WITH A
 WORKING KNOWLEDGE OF PRODUCING PLUMBING CODE COMPLIANT
 RISER DIAGRAMS. FBC 107.2.1
  
 2) NO MORE THAN TWO WATER CLOSETS ARE ALLOWED TO BE WET
 VENTED. FBCR-P3108.1
  
 3) ONE OF THE WATER CLOSETS IS DRAWN WITH A TRAP. WATER
 CLOSETS HAVE INTEGRAL TRAPS. FBCR-P3201.6 FIXTURES
 SHALL NOT BE DOUBLE TRAPPED.
  
 4) THE KITCHEN SINK IS DRAWN AS A VENT WITH A TRAP AT
 THE BOTTOM OF IT. THE P-TRAPS ARE LOCATED ON THE WASTE
 ARMS. FBCR-P3201.6
  
 5) THE WASHING MACHINE IS DRAWN WITH THE TRAP AT THE
 LEVEL OF THE BUILDING DRAIN. THE CLOTHES WASHER STAND
 PIPE TYPICALLY TIES INTO ITS VENT PIPE ABOVE THE FLOOR
 LEVEL BECAUSE THE STAND PIPE CAN BE NO LONGER THAN 42
 INCHES. FBCR-P2706.2
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-04 Cont ID  
Sent By rmcdouga Date 2018-01-04 Time 16:13 Rev Time 0.00
Received By rmcdouga Date 2018-01-04 Time 16:13 Sent To E
Notes
2018-01-04 16:34:46PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY PLUMBING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF A PLUMBING RISER DIAGRAM.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-07-25 Cont ID  
Sent By rmcdouga Date 2018-07-25 Time 08:35 Rev Time 0.00
Received By rmcdouga Date 2018-07-25 Time 08:35 Sent To  
Notes
2018-07-25 08:35:47NO ROOFING PRODUCT APPROVALS WERE SUBMITTED.