Plan Review Details - Permit 17120742
Plan Review Stops For Permit 17120742
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-12-28 Cont ID  
Sent By skennedy Date 2017-12-28 Time 12:19 Rev Time 0.00
Received By skennedy Date 2017-12-28 Time 12:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-12-28 Cont ID  
Sent By skennedy Date 2017-12-28 Time 12:19 Rev Time 0.00
Received By skennedy Date 2017-12-28 Time 12:19 Sent To  
Notes
2017-12-28 12:25:15RECORDS ON FILE FOR 03071807 ARE ADEQUATE TO DETERMINE
 SUFFICIENTCY OF SERVICE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-22 Cont ID  
Sent By jpearson Date 2017-12-22 Time 08:19 Rev Time 0.00
Received By jpearson Date 2017-12-22 Time 08:19 Sent To  
Notes
2017-12-22 08:19:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC
 107.2.1
 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 4. PROVIDE FLOOR PLAN SHOWING SMOKE/CO ALARMS IN EACH
 LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-28 Cont ID  
Sent By skennedy Date 2017-12-28 Time 12:19 Rev Time 0.00
Received By skennedy Date 2017-12-20 Time 14:41 Sent To  
Notes
2017-12-21 14:42:03R13

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-12-28 Cont ID  
Sent By skennedy Date 2017-12-28 Time 09:18 Rev Time 0.00
Received By skennedy Date 2017-12-28 Time 09:18 Sent To  
Notes
2017-12-28 09:18:40SEE 17120678.

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-12-28 Cont ID  
Sent By skennedy Date 2017-12-28 Time 09:25 Rev Time 0.00
Received By skennedy Date 2017-12-28 Time 09:25 Sent To  
Notes
2017-12-28 09:29:22THE PLUMBER SHALL PROVIDE A RISER DIAGRAM TO THE FIELD
 INSPECTOR IF REQUESTED.