Plan Review Details - Permit 17120722
Plan Review Stops For Permit 17120722
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-05 Cont ID  
Sent By thunt Date 2018-06-05 Time 14:51 Rev Time 0.00
Received By thunt Date 2018-06-01 Time 14:08 Sent To I
Notes
2018-06-04 14:08:12RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-23 Cont ID  
Sent By thunt Date 2018-05-23 Time 07:13 Rev Time 0.00
Received By thunt Date 2018-05-18 Time 13:23 Sent To  
Notes
2018-05-21 13:23:43RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-29 Cont ID  
Sent By tklarge Date 2017-12-29 Time 05:29 Rev Time 0.00
Received By tklarge Date 2017-12-19 Time 12:49 Sent To I
Notes
2017-12-20 12:49:13ROUTED TO PLUMB <5K

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-06-05 Cont ID  
Sent By thunt Date 2018-06-05 Time 14:51 Rev Time 0.00
Received By thunt Date 2018-06-05 Time 14:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-05-23 Cont ID  
Sent By thunt Date 2018-05-23 Time 06:51 Rev Time 0.00
Received By thunt Date 2018-05-23 Time 06:51 Sent To  
Notes
2018-05-23 07:13:4005/23/2018 PLUMBING 2ND REVIEW**DENIED**
  
 ALL OF THESE COMMENTS HAD BEEN LEFT ON-SITE WITH THE
 STOP WORK ORDER ON 04/20/2018. YOU HAVE ONLY 7 DAYS
 LEFT TO COMPLY WITH THE STOP WORK ORDER TO OBTAIN
 PERMIT WITH APPROVED INSPECTIONS.
  
 1) THE HAND SINK IS CONNECTED TO THE INTERCEPTOR AS
 REQUIRED BUT IS NOT INCLUDED ON EITHER YOUR SANITARY
 ISOMETRIC OR STANDARD-G101 DETAIL.FBC 107.2.1
  
 2) THE PIPE SIZE 2" IS UNDERSIZED AS YOU HAVE 8 DFU'S
 ON THE SYSTEM WITHT THE MAX BEING 6. FBC P 710.1 (2).
  
 3) MIN VENT SIZE IS 1 1/4"AND AAV'S ARE NOT PERMITTED
 ON ANY INTERCEPTORS. FBC P 906.1, 918.8, 1003.9
  
 4) SINKS ARE REQUIRED TO BE INDIRECTLY WASTED INTO A
 FLOOR SINK BEFOR THE INTERCEPTOR AND NOT CONNECTED
 DIRECTLY. FBC 802.1 AND HEALTH DEPT REG.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-12-29 Cont ID  
Sent By tklarge Date 2017-12-29 Time 05:28 Rev Time 0.00
Received By tklarge Date 2017-12-29 Time 05:06 Sent To I
Notes
2017-12-28 15:11:281) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION MANUAL FOR THE UNIT TO BE INSTALLED.
 WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT SIZING CALCULATIONS FOR THE GREASE UNIT. 2014
 FBC-PLUMBING SEC.1003.2, 1003.3.4.1.
 3) THE TRIPLE COMPARTMENT SHALL BE INDIRECTLY WASTED
 INTO THE GREASE UNIT. 2014 FBC-PLUMBING SEC.802.1.8.
 4) THE GREASE INTERCEPTOR SHALL BE EQUIPPED WITH A RATE
 OF FLOW CONTROL DEVICE PER 2014 FBC-PLUMBING SEC.
 1003.3.4.2.
  
 ADDITIONAL COMMENTS MAY BE GENERATED ON RESUBMITTAL OF
 REQUESTED INFORMATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  