Plan Review Details - Permit 17120722
Plan Review Stops For Permit 17120722 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-06-05 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2018-06-05 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2018-06-01 |
Time |
14:08 |
Sent To |
I |
|
Notes |
2018-06-04 14:08:12 | RESUB ROUTED TO THUNT |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-05-23 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2018-05-23 |
Time |
07:13 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2018-05-18 |
Time |
13:23 |
Sent To |
|
|
Notes |
2018-05-21 13:23:43 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-12-29 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2017-12-29 |
Time |
05:29 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2017-12-19 |
Time |
12:49 |
Sent To |
I |
|
Notes |
2017-12-20 12:49:13 | ROUTED TO PLUMB <5K |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2018-06-05 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2018-06-05 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2018-06-05 |
Time |
14:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2018-05-23 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2018-05-23 |
Time |
06:51 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2018-05-23 |
Time |
06:51 |
Sent To |
|
|
Notes |
2018-05-23 07:13:40 | 05/23/2018 PLUMBING 2ND REVIEW**DENIED** | | | | ALL OF THESE COMMENTS HAD BEEN LEFT ON-SITE WITH THE | | STOP WORK ORDER ON 04/20/2018. YOU HAVE ONLY 7 DAYS | | LEFT TO COMPLY WITH THE STOP WORK ORDER TO OBTAIN | | PERMIT WITH APPROVED INSPECTIONS. | | | | 1) THE HAND SINK IS CONNECTED TO THE INTERCEPTOR AS | | REQUIRED BUT IS NOT INCLUDED ON EITHER YOUR SANITARY | | ISOMETRIC OR STANDARD-G101 DETAIL.FBC 107.2.1 | | | | 2) THE PIPE SIZE 2" IS UNDERSIZED AS YOU HAVE 8 DFU'S | | ON THE SYSTEM WITHT THE MAX BEING 6. FBC P 710.1 (2). | | | | 3) MIN VENT SIZE IS 1 1/4"AND AAV'S ARE NOT PERMITTED | | ON ANY INTERCEPTORS. FBC P 906.1, 918.8, 1003.9 | | | | 4) SINKS ARE REQUIRED TO BE INDIRECTLY WASTED INTO A | | FLOOR SINK BEFOR THE INTERCEPTOR AND NOT CONNECTED | | DIRECTLY. FBC 802.1 AND HEALTH DEPT REG. | | | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2017-12-29 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2017-12-29 |
Time |
05:28 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2017-12-29 |
Time |
05:06 |
Sent To |
I |
|
Notes |
2017-12-28 15:11:28 | 1) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS | | AND INSTALLATION MANUAL FOR THE UNIT TO BE INSTALLED. | | WPB AMEND. TO FBC SEC. 107.2.1. | | 2) SUBMIT SIZING CALCULATIONS FOR THE GREASE UNIT. 2014 | | FBC-PLUMBING SEC.1003.2, 1003.3.4.1. | | 3) THE TRIPLE COMPARTMENT SHALL BE INDIRECTLY WASTED | | INTO THE GREASE UNIT. 2014 FBC-PLUMBING SEC.802.1.8. | | 4) THE GREASE INTERCEPTOR SHALL BE EQUIPPED WITH A RATE | | OF FLOW CONTROL DEVICE PER 2014 FBC-PLUMBING SEC. | | 1003.3.4.2. | | | | ADDITIONAL COMMENTS MAY BE GENERATED ON RESUBMITTAL OF | | REQUESTED INFORMATION. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|
|
|