Plan Review Details - Permit 17120719
Plan Review Stops For Permit 17120719 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2018-01-13 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-01-13 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-01-13 |
Time |
10:19 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-01-17 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-01-17 |
Time |
12:58 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-01-17 |
Time |
12:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-01-09 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-01-09 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-01-09 |
Time |
11:22 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2017-12-21 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-12-21 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-12-20 |
Time |
16:38 |
Sent To |
B |
|
Notes |
2017-12-21 11:47:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO DETAILS INDICATED FOR THE GENERATOR, | | SIZE, HOW IT IS FUELED, EXHAUST LOCATION, DIMENSION | | FROM THE TENT(S), HOW WILL CABLES BE PROTECTED, ETC. | | | | | | | | 2) IS THIS AN EVENING EVENT AND WILL THERE BE LIGHTING. | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 3) THERE ARE NO EMERGECNY LIGHTS INDICATED. IN THE | | EVENT THE GENERATOR FAILS HOW WILL THE EXIT AND EXIT | | PATHS REMAIN ILLUMINATED? | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 4) THERE ARE NO INDICATIONS ON HOW THIS TENT WILL BE | | HELD DOWN/SECURED. | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 5) WHAT IS THE AREA INDICATED IN THE BACK OF THE TENT? | | IT PROPOSED USE? THERE ARE NO DIMENSIONS, PLEASE | | PROVIDE. WILL IT BE FENCED IN, HAVE A ROOF OVER THE | | TOP? | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 6) WHAT TYPE OF HARDWARE IS ON EACH OF THE DOORS? THE | | HARDWARE SHALL COMPLY WITH THE REQUIRMENTS OF NFPA 101, | | CHAPTER12 AND CHAPTER 7. | | | | PLEASE PROVIDE DETAILS. | | | | | | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-01-17 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-01-17 |
Time |
12:58 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2017-12-19 |
Time |
11:05 |
Sent To |
|
|
Notes |
2017-12-20 11:06:06 | ROUTED TO TEMP TENT |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2017-12-28 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-12-28 |
Time |
07:39 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-12-28 |
Time |
07:18 |
Sent To |
B |
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |