Plan Review Stops For Permit 17120624 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2018-03-23 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-03-23 |
Time |
07:58 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-03-17 |
Time |
07:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-01-10 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-01-10 |
Time |
10:52 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-01-08 |
Time |
16:41 |
Sent To |
Z |
|
Notes |
2018-01-10 11:16:15 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 1ST REVIEW | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. ROOFING PERMIT REQUIRED. | | 2. PALM BEACH COUNTY IMPACT FEES REQUIRED. | | 3. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS. | | | | IMPACT FEES | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | IMPACT FEES AT (561) 233-5025. | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS. | | | | OPTION | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | THE DEFERRED SUBMITTALS ON | | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING | | OFFICIAL. | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | OFFICIAL. | | | | | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-03-07 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-03-06 |
Time |
16:23 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-03-06 |
Time |
16:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-01-08 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-01-08 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-01-08 |
Time |
11:39 |
Sent To |
|
|
Notes |
2018-01-08 14:47:56 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PANEL SCHEDULE SHOWS THE NEW PANEL AS A MAIN LUG | | ONLY PANEL. A MAIN BREAKER IS REQUIRED IN THIS PANEL, | | OR PROVIDE A DISCONNECT AHEAD OF PANEL. PROVIDE | | CORRECTION. NEC 230.70, 230.71; FBC RE 3601.6.2, 3601.7 | | 2. PROVIDE ACCURATE LOAD CALCULATION. THE PROVIDED | | CALCULATION DOES NOT INCLUDE BOTH AC SYSTEMS, DOES NOT | | INCLUDE ALL OF THE EQUIPMENT IN THE HOME SUCH AS ICE | | MAKER AND WINE COOLER, AND INCLUDES SOME LOADS NOT | | CORRECT SUCH AS WATER HEATER (WHICH IS NOW GAS). | | PROVIDE CORRECTION. FBC RE 3602.2 | | 3. PROVIDE FLOOR PLAN SHOWING SMOKE/CO ALARMS IN EACH | | LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL EXISTING | | ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS | | NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1 | | 4. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE | | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH | | CIRCUITS SHALL HAVE NO OTHER OUTLETS. I DO NOT SEE ANY | | CIRCUIT FOR THIS IN PANEL SCHEDULE FOR NEW BATHROOMS. | | PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE3703.4 | | 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | SERVICE. NEC 250.94; FBC RE3609.3 | | 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. | | FBC EC R404.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2018-01-09 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2018-01-09 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2018-01-09 |
Time |
11:39 |
Sent To |
|
|
Notes |
2018-01-09 11:41:09 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL | | 1ST REVIEW FBC 2014 EXISTING BUILDING | | | | A COMPLETE GAS PLAN HAS NOT BEEN INCLUDED IN THIS | | SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN | | PERFORMED AT THIS TIME. A GAS PERMIT IS REQUIRED FOR A | | CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE | | COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS | | WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1. | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | FBC-R, SEC. G2404.3. | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | GAS SEC. 301.3. | | | | STEVEN KENNEDY, CBO | | ASSISTANT BUILDING OFFICIAL | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-03-23 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-03-23 |
Time |
07:59 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-02-13 |
Time |
14:19 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-01-17 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-01-17 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2017-12-15 |
Time |
11:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2018-03-23 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-03-23 |
Time |
07:58 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-03-17 |
Time |
07:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2018-01-10 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-01-10 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-01-08 |
Time |
16:41 |
Sent To |
|
|
Notes |
2018-01-10 10:29:38 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 1ST REVIEW | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | IMPACT FEES | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | IMPACT FEES AT (561) 233-5025. | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2018-03-12 |
|
|
Cont ID |
|
Sent By |
cmontell |
Date |
2018-03-12 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
cmontell |
Date |
2018-03-12 |
Time |
14:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-01-03 |
|
|
Cont ID |
|
Sent By |
cmontell |
Date |
2018-01-03 |
Time |
14:42 |
Rev Time |
0.00 |
Received By |
cmontell |
Date |
2018-01-03 |
Time |
14:42 |
Sent To |
|
|
Notes |
2018-01-03 14:43:43 | ENERGY CALCULATIONS NEED TO BE SIGNED PER FEC SEC | | 405.4.2 CM 1/3/18 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2018-03-13 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-03-13 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-03-13 |
Time |
15:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2018-01-09 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2018-01-09 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2018-01-09 |
Time |
11:39 |
Sent To |
|
|
Notes |
2018-01-09 11:42:56 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL | | 1ST REVIEW FBC 2014 EXISTING BUILDING | | | | THE PLUMBING SANITARY RISER WAS RED-LINED TO SHOW | | PROPER VENTING AND W/C ARRANGEMENT. YOU SHOULD UPDATE | | ON RE-SUBMITTAL. | | | | STEVEN KENNEDY, CBO | | ASSISTANT BUILDING OFFICIAL | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2018-01-10 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-01-10 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-01-08 |
Time |
16:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2018-03-23 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2018-03-23 |
Time |
|
Rev Time |
0.00 |
Received By |
awooten |
Date |
2018-03-23 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2018-03-02 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2018-03-02 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
awooten |
Date |
2018-03-02 |
Time |
|
Sent To |
|
|
Notes |
2018-03-02 10:34:38 | ****************************************ZONING REVIEW | | FAILED***************************** | | | | PRIOR TO THE ZONING APPROVAL OF THIS PERMIT A SEPARATE | | LANDSCAPE PERMIT AND IRRIGATION PERMIT SHALL BE | | SUBMITTED SHOWING MATERIAL TO BRING THE SITE INTO | | CONFORMITY. ONCE SEPARATE PERMIT HAS BEEN SUBMITTED, | | ZONING CAN BE PASSED. | | | | THANKS, | | ALANA WOOTEN | | ASSOCIATE PLANNER | | 561-822-1449 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2018-01-17 |
|
|
Cont ID |
|
Sent By |
AW |
Date |
2018-01-17 |
Time |
14:45 |
Rev Time |
0.00 |
Received By |
awooten |
Date |
2018-01-16 |
Time |
15:25 |
Sent To |
|
|
Notes |
2018-01-17 14:45:31 | **********************************ZONING REVIEW FAILED* | | ******************************************************* | | ********* | | | | THE VALUE OF THE CONSTRUCTION ($350,000) EXCEEDS 50% OF | | THE STRUCTURE'S VALUE ACCORDING TO THE P.B.C. PROPERTY | | APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION | | 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | SITE INTO CONFORMITY. | | | | | | IN THE FRONT YARD; HOWEVER, THE LESSER OF 1,000 SQUARE | | FEET OR 75 PERCENT OF THE FRONT YARD AREA SHALL BE | | LANDSCAPED WITH LIVING PLANT MATERIAL (SUCH AS GRASS, | | GROUND COVER, SHRUBS, HEDGES, VINES OR TREES). | | | | NOTE: DRIVEWAY MUST BE SUBMITTED UNDER A SEPARATE | | PERMIT. | | | | ALANA WOOTEN | | ASSOCIATE PLANNER | | PLANNING DIVISION | | 561-822-1449 | | [email protected] | | |
|
|