Plan Review Details - Permit 17120624
Plan Review Stops For Permit 17120624
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By cthroop Date 2018-03-23 Time 07:58 Rev Time 0.00
Received By cthroop Date 2018-03-17 Time 07:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-10 Cont ID  
Sent By cthroop Date 2018-01-10 Time 10:52 Rev Time 0.00
Received By cthroop Date 2018-01-08 Time 16:41 Sent To Z
Notes
2018-01-10 11:16:15BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 3. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS.
  
 IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS.
  
 OPTION
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-07 Cont ID  
Sent By jpearson Date 2018-03-06 Time 16:23 Rev Time 0.00
Received By jpearson Date 2018-03-06 Time 16:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-08 Cont ID  
Sent By jpearson Date 2018-01-08 Time 14:48 Rev Time 0.00
Received By jpearson Date 2018-01-08 Time 11:39 Sent To  
Notes
2018-01-08 14:47:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PANEL SCHEDULE SHOWS THE NEW PANEL AS A MAIN LUG
 ONLY PANEL. A MAIN BREAKER IS REQUIRED IN THIS PANEL,
 OR PROVIDE A DISCONNECT AHEAD OF PANEL. PROVIDE
 CORRECTION. NEC 230.70, 230.71; FBC RE 3601.6.2, 3601.7
 2. PROVIDE ACCURATE LOAD CALCULATION. THE PROVIDED
 CALCULATION DOES NOT INCLUDE BOTH AC SYSTEMS, DOES NOT
 INCLUDE ALL OF THE EQUIPMENT IN THE HOME SUCH AS ICE
 MAKER AND WINE COOLER, AND INCLUDES SOME LOADS NOT
 CORRECT SUCH AS WATER HEATER (WHICH IS NOW GAS).
 PROVIDE CORRECTION. FBC RE 3602.2
 3. PROVIDE FLOOR PLAN SHOWING SMOKE/CO ALARMS IN EACH
 LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1
 4. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. I DO NOT SEE ANY
 CIRCUIT FOR THIS IN PANEL SCHEDULE FOR NEW BATHROOMS.
 PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE3703.4
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-01-09 Cont ID  
Sent By skennedy Date 2018-01-09 Time 11:39 Rev Time 0.00
Received By skennedy Date 2018-01-09 Time 11:39 Sent To  
Notes
2018-01-09 11:41:091ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING
  
 A COMPLETE GAS PLAN HAS NOT BEEN INCLUDED IN THIS
 SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A GAS PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-23 Cont ID  
Sent By cthroop Date 2018-03-23 Time 07:59 Rev Time 0.00
Received By cthroop Date 2018-02-13 Time 14:19 Sent To I
Notes
2018-02-14 14:20:04R34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-17 Cont ID  
Sent By cpuell Date 2018-01-17 Time 16:34 Rev Time 0.00
Received By cpuell Date 2017-12-15 Time 11:20 Sent To  
Notes
2017-12-18 11:20:31R09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By cthroop Date 2018-03-23 Time 07:58 Rev Time 0.00
Received By cthroop Date 2018-03-17 Time 07:40 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-01-10 Cont ID  
Sent By cthroop Date 2018-01-10 Time 10:28 Rev Time 0.00
Received By cthroop Date 2018-01-08 Time 16:41 Sent To  
Notes
2018-01-10 10:29:38BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 IMPACT FEES
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-03-12 Cont ID  
Sent By cmontell Date 2018-03-12 Time 14:38 Rev Time 0.00
Received By cmontell Date 2018-03-12 Time 14:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-03 Cont ID  
Sent By cmontell Date 2018-01-03 Time 14:42 Rev Time 0.00
Received By cmontell Date 2018-01-03 Time 14:42 Sent To  
Notes
2018-01-03 14:43:43ENERGY CALCULATIONS NEED TO BE SIGNED PER FEC SEC
 405.4.2 CM 1/3/18

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-13 Cont ID  
Sent By gjohnson Date 2018-03-13 Time 15:50 Rev Time 0.00
Received By gjohnson Date 2018-03-13 Time 15:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-01-09 Cont ID  
Sent By skennedy Date 2018-01-09 Time 11:39 Rev Time 0.00
Received By skennedy Date 2018-01-09 Time 11:39 Sent To  
Notes
2018-01-09 11:42:561ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING
  
 THE PLUMBING SANITARY RISER WAS RED-LINED TO SHOW
 PROPER VENTING AND W/C ARRANGEMENT. YOU SHOULD UPDATE
 ON RE-SUBMITTAL.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-01-10 Cont ID  
Sent By cthroop Date 2018-01-10 Time 11:16 Rev Time 0.00
Received By cthroop Date 2018-01-08 Time 16:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-03-23 Cont ID  
Sent By awooten Date 2018-03-23 Time   Rev Time 0.00
Received By awooten Date 2018-03-23 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-03-02 Cont ID  
Sent By awooten Date 2018-03-02 Time 10:34 Rev Time 0.00
Received By awooten Date 2018-03-02 Time   Sent To  
Notes
2018-03-02 10:34:38****************************************ZONING REVIEW
 FAILED*****************************
  
 PRIOR TO THE ZONING APPROVAL OF THIS PERMIT A SEPARATE
 LANDSCAPE PERMIT AND IRRIGATION PERMIT SHALL BE
 SUBMITTED SHOWING MATERIAL TO BRING THE SITE INTO
 CONFORMITY. ONCE SEPARATE PERMIT HAS BEEN SUBMITTED,
 ZONING CAN BE PASSED.
  
 THANKS,
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-01-17 Cont ID  
Sent By AW Date 2018-01-17 Time 14:45 Rev Time 0.00
Received By awooten Date 2018-01-16 Time 15:25 Sent To  
Notes
2018-01-17 14:45:31**********************************ZONING REVIEW FAILED*
 *******************************************************
 *********
  
 THE VALUE OF THE CONSTRUCTION ($350,000) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ACCORDING TO THE P.B.C. PROPERTY
 APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION
 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
  
 IN THE FRONT YARD; HOWEVER, THE LESSER OF 1,000 SQUARE
 FEET OR 75 PERCENT OF THE FRONT YARD AREA SHALL BE
 LANDSCAPED WITH LIVING PLANT MATERIAL (SUCH AS GRASS,
 GROUND COVER, SHRUBS, HEDGES, VINES OR TREES).
  
 NOTE: DRIVEWAY MUST BE SUBMITTED UNDER A SEPARATE
 PERMIT.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  