Plan Review Details - Permit 17120605
Plan Review Stops For Permit 17120605
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-12-22 Cont ID  
Sent By cthroop Date 2017-12-22 Time 16:07 Rev Time 0.00
Received By cthroop Date 2017-12-22 Time 15:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-15 Cont ID  
Sent By shill Date 2017-12-15 Time 14:58 Rev Time 0.00
Received By shill Date 2017-12-15 Time 14:58 Sent To  
Notes
2017-12-15 15:00:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. ON THE PRODUCT APPROVAL, INDICATE FASTENING PROPOSED
 FOR TILE (PADDY SIZE), FBC R 301.
  
 2. PROVIDE THE MEAN ROOF HEIGHT, FBC R 301. FASTENING
 PATTERN FOR THE FLAT ROOF WAS NOT INDICATED. THIS CAN
 BE DONE FOR YOU, BUT MRH IS REQUIRED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-22 Cont ID  
Sent By cthroop Date 2017-12-22 Time 16:07 Rev Time 0.00
Received By cthroop Date 2017-12-19 Time 11:33 Sent To I
Notes
2017-12-20 11:33:27RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-15 Cont ID  
Sent By shill Date 2017-12-15 Time 15:00 Rev Time 0.00
Received By shill Date 2017-12-15 Time 13:42 Sent To  
Notes
2017-12-15 13:43:03SHILL