Plan Review Details - Permit 17120551
Plan Review Stops For Permit 17120551
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2018-07-07 Cont ID  
Sent By shill Date 2018-07-07 Time 17:42 Rev Time 0.00
Received By shill Date 2018-07-07 Time 17:42 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2018-04-30 Cont ID  
Sent By shill Date 2018-04-30 Time 08:45 Rev Time 0.00
Received By shill Date 2018-04-30 Time 08:45 Sent To  
Notes
2018-04-30 08:45:25SEE REVIEW UNDER 17120550

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2017-12-19 Cont ID  
Sent By skennedy Date 2017-12-19 Time 11:23 Rev Time 0.00
Received By skennedy Date 2017-12-19 Time 11:23 Sent To  
Notes
2017-12-19 11:25:451ST REVIEW FBC 2014 EXISTING BUILDING
  
 APPLICANT TO ASSURE PERMIT APPLICATIONS CONTAIN CORRECT
 ADDRESS INFORMATION AS FOLLOWS:
  
 THE ADDRESS FOR THE SOUTH BUILDING IS 3805 BROADWAY
 WHICH INCLUDES THE NEW UNITS 1 THROUGH 15.
 THE NEW ADDRESS FOR THE NORTH BUILDING IS 3809 BROADWAY
 WHICH INCLUDES THE NEW UNITS 16 THROUGH 20.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 14:25 Rev Time 0.00
Received By shill Date 2018-09-02 Time 14:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-07 Cont ID  
Sent By shill Date 2018-07-07 Time 17:42 Rev Time 0.00
Received By shill Date 2018-07-07 Time 17:42 Sent To  
Notes
2018-07-07 17:43:02PROVISO - ADDRESS COMMENTS FROM OTHER TRADES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-30 Cont ID  
Sent By shill Date 2018-04-30 Time 08:45 Rev Time 0.00
Received By shill Date 2018-04-30 Time 08:45 Sent To  
Notes
2018-04-30 08:45:48SEE REVIEW UNDER 17120550

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-02 Cont ID  
Sent By aclange Date 2018-01-02 Time 14:22 Rev Time 0.00
Received By aclange Date 2018-01-02 Time 07:42 Sent To  
Notes
2018-01-02 14:22:08****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
 1. DESCRIPTION OF WORK SHOWN IS FOR CABINET
 REPLACEMENT. THIS SHOULD BE SHOWN AS A CHANGE OF
 OCCUPANCY FROM R-1 TO R-2 AND INCLUDE A DESCRIPTION OF
 ALL WORK. FBC 105.3
  
 2. PERMIT VALUE APPEARS TOO LOW. ADJUST ACCORDINGLY.
  
 FBC 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 3. ADDRESSING:
  
 ADJUST THE PLANS TO INCLUDE THE TWO FOLLOWING
 ADDRESSES. SOUTH BUILDING WILL BE 3805 BROADWAY AND THE
 NORTHERN BUILDING SHOULD BE SHOWN AS 3809 BROADWAY.
 THESE ADDRESSES HAVE BEEN UPDATED IN OUR SYSTEM
 ALREADY.
  
 4. EXISTING BUILDING CODE:
  
 THIS PROJECT IS A CHANGE OF OCCUPANCY WITHIN A GROUP
 AND SHOULD SHOW COMPLIANCE WITH THE FOLLOWING AREAS OF
 THE EXISTING BUILDING CODE IN SECTION 1012.
  
 1012.1 GENERAL.
  
 THE PROVISIONS OF THIS SECTION SHALL APPLY TO BUILDINGS
 OR PORTIONS THEREOF UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP. SUCH BUILDINGS SHALL ALSO COMPLY WITH SECTIONS
 1002 THROUGH 1011. THE APPLICATION OF REQUIREMENTS FOR
 THE CHANGE OF OCCUPANCY SHALL BE AS SET FORTH IN
 SECTIONS 1012.1.1 THROUGH 1012.1.4. A CHANGE OF
 OCCUPANCY, AS DEFINED IN SECTION 202, WITHOUT A
 CORRESPONDING CHANGE OF OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH SECTION 1001.2.
  
 SEE ALSO SECTIONS 1012.2 FIRE PROTECTION SYSTEMS AND
 1012.2.1 FIRE SPRINKLER SYSTEM.
  
 5. COMMENT ADDRESSED. NO ACTION REQUIRED.
  
 6. COMMENT ADDRESSED. NO ACTION REQUIRED.
  
 7. PROVIDE THE USE OF THE UTILITY ROOM AND SHOW
 COMPLIANCE WITH FBC 509.4 SEPARATION AND PROTECTION.
 THE INCIDENTAL USES LISTED IN TABLE 509 SHALL BE
 SEPARATED FROM THE REMAINDER OF THE BUILDING OR
 EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM, OR BOTH,
 IN ACCORDANCE WITH THE PROVISIONS OF TABLE 508.4.
  
 8. IMPACT FEE: BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES, REQUIRED BY PALM BEACH COUNTY,
 SHALL BE PAID. UPON FINAL APPROVAL OF PLANS, ONE SET OF
 PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM BEACH
 COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH THE
 IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT MUST BE
 RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE THE
 BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 9. ADDITIONAL INFORMATION REQUIRED.
  
 A) PROVIDE ELEVATIONS FOR THE KITCHEN AREA.
  
 B) SHOW LOCATIONS OF NEW WALLS. ARE THE WALLS AROUND
 THE KITCHENS NEW? IF SO PROVIDE WALL DETAILS.
  
 C) PROVIDE DETAIL FOR BATHROOM SHOWERS AND INCLUDE
 FRAMING SPACING.
  
 D) PARKING LOT REPAVING OR STRIPING WILL REQUIRE A
 SEPARATE PERMIT.
  
 E) PAGE A.3 SUBMITTED IS NOT LEDGIBLE.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2018-10-02 Cont ID  
Sent By dharvey Date 2018-10-02 Time 14:42 Rev Time 0.00
Received By dharvey Date 2018-10-02 Time 14:42 Sent To  
Notes
2018-10-02 14:43:29SEE NOTES ON 17121550, THEY APPLY TO THIS SUBMISSION AS
 WELL.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2018-08-20 Cont ID  
Sent By jpearson Date 2018-08-20 Time 13:08 Rev Time 0.00
Received By jpearson Date 2018-08-20 Time 13:08 Sent To  
Notes
2018-08-20 11:44:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. 3 PHASE PANEL ON SINGLE PHASE SERVICE. (THIS HAS NOT
 BEEN ADDRESSED IN THE RISER DIAGRAM. RISER DIAGRAM MUST
 ACCURATELY REFLECT THE CURRENT ELECTRICAL SERVICE. HOW
 COULD A 3 PHASE SERVICE BE FED FROM A SINGLE PHASE
 SERVICE? PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; WPB FBC 107.2.1
  
 NEW COMMENT:
  
 2. PLAN HAS A BLOCK NOTE THAT STATES THERE IS NOW WORK
 TO BE INTENDED UNDER THIS PERMIT, BUT PLAN SHOWS
 EXHAUST FANS BEING INSTALLED. CORRECT DISCREPANCY. WPB
 FBC 107.2.1
 3. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. LOAD CALCULATION SHOULD SHOW LOADS
 BASED ON THE WATTAGE DEMAND FOR EACH LOAD, AND THEN
 DIVIDED BY THE APPROPRIATE VOLTAGE. LOAD CALCULATION
 PROVIDED SWITCHES BETWEEN AMPERAGE OF LOADS AND
 WATTAGE, AND THEREFORE IS DIFFICULT TO UNDERSTAND.
 BASED ON THE NUMBERS PROVIDED, THE SERVICE TO SOUTH
 BUILDING IS OVERLOADED AS IS, AND NOW THERE WILL BE
 ADDITIONAL LOAD FOR EXHAUST FANS. THERE IS ALSO NO LOAD
 SHOWN FOR SMALL APPLIANCE CIRCUITS, WATER HEATERS, AND
 EXHAUST HOODS. NEC 215.2, 220, 408.30
 4. PROVIDE PANEL SCHEDULE(S) INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4; WPB FBC 107.3.5
 5. EACH OCCUPANT SHALL HAVE READY ACCESS TO ALL
 OVERCURRENT DEVICES PROTECTING THE CONDUCTORS SUPPLYING
 THAT OCCUPANCY. LOCATION OF ELECTRICAL PANELS NOT SHOWN
 ON PLAN, THEREFORE IT IS IMPOSSIBLE TO DETERMINE
 COMPLIANCE WITH THIS REQUIREMENT. PROVIDE CORRECTION.
 NEC 240.24(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-06-27 Cont ID  
Sent By ppetty Date 2018-06-27 Time 13:14 Rev Time 0.00
Received By ppetty Date 2018-06-27 Time 13:13 Sent To  
Notes
2018-06-27 13:14:303 PHASE PANEL ON SINGLE PHASE SERVICE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-27 Cont ID  
Sent By jpearson Date 2018-04-27 Time 09:00 Rev Time 0.00
Received By jpearson Date 2018-04-26 Time 13:26 Sent To  
Notes
2018-04-27 09:00:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ADDRESS ON PLAN SHOW 3805 BROADWAY, BUT SHOWS BOTH
 BUILDINGS. THESE PLANS SHOULD BE SEPARATED SO THAT EACH
 PLAN HAS THE PROPER ADDRESS AND CORRESPONDING PLAN.
 PROVIDE CORRECTION. WPB FBC 107.2.1
 2. PROVIDE ELECTRICAL PLAN SHOWING ANY NEW WORK
 REQUIRED PER MECHANICAL COMMENTS. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-03 Cont ID  
Sent By jpearson Date 2018-01-03 Time 07:42 Rev Time 0.00
Received By jpearson Date 2018-01-03 Time 07:42 Sent To  
Notes
2018-01-03 07:41:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE LICENSED DESIGN PROFESSIONAL RESPONSIBLE
 FOR DESIGN. FS 471.003(2)(H); 471.025; FBC 107.2.1,
 107.3.5
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30
 3. PROVIDE PANEL SCHEDULE FOR EACH PANEL, INDICATING
 ANY NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE
 FOR THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 215.5, 408.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-06-22 Cont ID  
Sent By pleduc Date 2018-06-22 Time   Rev Time 0.00
Received By pleduc Date 2018-06-22 Time 11:49 Sent To  
Notes
2018-06-22 14:41:39THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY WORK ON THE FIRE SPRINKLER OR SPRINKLER
 MONITORING ALARM SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-16 Cont ID  
Sent By pleduc Date 2018-04-16 Time   Rev Time 0.00
Received By pleduc Date 2018-04-16 Time 13:22 Sent To  
Notes
2018-04-16 14:55:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) PREVIOUS FIRE COMMENTS WERE NOT ADDRESS.
  
 THE PREVIOUS FIRE COMMENTS ARE RESUBMITTED:
  
 *******************************************************
 *******************************************************
 ***************
  
 1) THE APPLCATIONSTATES THE PROPOSED WORK IS TO REPLACE
 THE KITCHEN CABINETS. SHEET A 1 - STATES THAT THE
 PROPOSED WORK IS A CHANGE OF OCCUPANCY FROM MOTEL TO
 MULTI- RESIDENTIAL.
  
 PER THE FLORIDA FIRE PREVENTION CODE IT IS FROM
 EXISTING HOTEL TO NEW APARTMENT OCCUPANCY
  
 PLEASE CLARIFY.
  
  
  
 2) THERE IS A REFERENCE INDICATING A FIRE ALARM IS NOT
 REQUIRED PER THE FBC; HOWEVER, A FIRE ALARM IS REQUIRED
 PER THE FLORIDA FIRE PREVENTION CODE, NFPA 101, CHPATER
 30, NEW APARTMENT BUILDINGS. YOUR PROJECT INDICATES 14
 UNITS.
  
 30.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 30.3.4.1 GENERAL.
 30.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR WITH MORE THAN 11 DWELLING UNITS, OTHER THAN
 THOSE MEETING THE REQUIREMENTS OF 30.3.4.1.2, SHALL BE
 PROVIDED WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH
 SECTION 9.6, EXCEPT AS MODIFIED BY 30.3.4.2 THROUGH
 30.3.4.5.
  
 HOWEVER,
  
 30.3.4.1.2 A FIRE ALARM SYSTEM SHALL NOT BE REQUIRED IN
 BUILDINGS WHERE EACH DWELLING UNIT IS SEPARATED FROM
 OTHER CONTIGUOUS DWELLING UNITS BY FIRE BARRIERS (SEE
 SECTION 8.3) HAVING A MINIMUM 1-HOUR FIRE RESISTANCE
 RATING, AND WHERE EACH DWELLING UNIT HAS EITHER ITS OWN
 INDEPENDENT EXIT OR ITS OWN INDEPENDENT STAIRWAY OR
 RAMP DISCHARGING AT THE FINISHED GROUND LEVEL.
  
 PLEASE REVIEW, CORRECT OR JUSTIFY WITH DETAILS AND/OR A
 SIGNED AND SEALED ENGINEEER REVIEW OF THE CONSTRUCTION,
 THAT THE CODE REQUIREMENTS ARE PROVIDED FOR.
  
  
  
  
 3) THERE IS A REFERENCE INDICATING A FIRE SPRINKLER
 SYSTEM IS NOT REQUIRED PER THE FBC; HOWEVER, A FIRE
 SPRINKLER SYSTEM IS REQUIRED PER THE FLORIDA FIRE
 PREVENTION CODE, NFPA 101, CHPATER 30, NEW APARTMENT
 BUILDINGS.
  
 30.3.5 EXTINGUISHMENT REQUIREMENTS.
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH 30.3.5.2.
  
 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, EITHER FOR TOTAL OR PARTIAL BUILDING
 COVERAGE, THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE
 WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 AND 30.3.5.4.
 IN BUILDINGS FOUR OR FEWER STORIES ABOVE GRADE PLANE,
 SYSTEMS IN ACCORDANCE WITH NFPA 13R, STANDARD FOR THE
 INSTALLATION OF SPRINKLER SYSTEMS IN LOW-RISE
 RESIDENTIAL OCCUPANCIES, SHALL BE PERMITTED.
  
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH ALL
 APPLICABLE FIRE CODE REFERENCES.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-12-20 Cont ID  
Sent By pleduc Date 2017-12-20 Time   Rev Time 0.00
Received By pleduc Date 2017-12-19 Time 11:33 Sent To  
Notes
2017-12-19 12:38:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE APPLCATIONSTATES THE PROPOSED WORK IS TO REPLACE
 THE KITCHEN CABINETS. SHEET A 1 - STATES THAT THE
 PROPOSED WORK IS A CHANGE OF OCCUPANCY FROM MOTEL TO
 MULTI- RESIDENTIAL.
  
 PER THE FLORIDA FIRE PREVENTION CODE IT IS FROM
 EXISTING HOTEL TO NEW APARTMENT OCCUPANCY
  
 PLEASE CLARIFY.
  
  
  
 2) THERE IS A REFERENCE INDICATING A FIRE ALARM IS NOT
 REQUIRED PER THE FBC; HOWEVER, A FIRE ALARM IS REQUIRED
 PER THE FLORIDA FIRE PREVENTION CODE, NFPA 101, CHPATER
 30, NEW APARTMENT BUILDINGS. YOUR PROJECT INDICATES 14
 UNITS.
  
 30.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 30.3.4.1 GENERAL.
 30.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR WITH MORE THAN 11 DWELLING UNITS, OTHER THAN
 THOSE MEETING THE REQUIREMENTS OF 30.3.4.1.2, SHALL BE
 PROVIDED WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH
 SECTION 9.6, EXCEPT AS MODIFIED BY 30.3.4.2 THROUGH
 30.3.4.5.
  
 HOWEVER,
  
 30.3.4.1.2 A FIRE ALARM SYSTEM SHALL NOT BE REQUIRED IN
 BUILDINGS WHERE EACH DWELLING UNIT IS SEPARATED FROM
 OTHER CONTIGUOUS DWELLING UNITS BY FIRE BARRIERS (SEE
 SECTION 8.3) HAVING A MINIMUM 1-HOUR FIRE RESISTANCE
 RATING, AND WHERE EACH DWELLING UNIT HAS EITHER ITS OWN
 INDEPENDENT EXIT OR ITS OWN INDEPENDENT STAIRWAY OR
 RAMP DISCHARGING AT THE FINISHED GROUND LEVEL.
  
 PLEASE REVIEW, CORRECT OR JUSTIFY WITH DETAILS AND/OR A
 SIGNED AND SEALED ENGINEEER REVIEW OF THE CONSTRUCTION,
 THAT THE CODE REQUIREMENTS ARE PROVIDED FOR.
  
  
  
  
 3) THERE IS A REFERENCE INDICATING A FIRE SPRINKLER
 SYSTEM IS NOT REQUIRED PER THE FBC; HOWEVER, A FIRE
 SPRINKLER SYSTEM IS REQUIRED PER THE FLORIDA FIRE
 PREVENTION CODE, NFPA 101, CHPATER 30, NEW APARTMENT
 BUILDINGS.
  
 30.3.5 EXTINGUISHMENT REQUIREMENTS.
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH 30.3.5.2.
  
 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, EITHER FOR TOTAL OR PARTIAL BUILDING
 COVERAGE, THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE
 WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 AND 30.3.5.4.
 IN BUILDINGS FOUR OR FEWER STORIES ABOVE GRADE PLANE,
 SYSTEMS IN ACCORDANCE WITH NFPA 13R, STANDARD FOR THE
 INSTALLATION OF SPRINKLER SYSTEMS IN LOW-RISE
 RESIDENTIAL OCCUPANCIES, SHALL BE PERMITTED.
  
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH ALL
 APPLICABLE FIRE CODE REFERENCES.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-10-18 Cont ID  
Sent By cthroop Date 2018-10-18 Time 16:53 Rev Time 0.00
Received By cthroop Date 2018-10-09 Time 10:12 Sent To  
Notes
2018-10-11 10:12:21IMPACT FEES ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 14:26 Rev Time 0.00
Received By shill Date 2018-08-06 Time 15:56 Sent To  
Notes
2018-08-07 15:56:27C25
 **TRAVELLING WITH 17120550**

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-07 Cont ID  
Sent By lmarchan Date 2018-08-07 Time 15:54 Rev Time 0.00
Received By lmarchan Date 2018-06-18 Time 16:37 Sent To  
Notes
2018-06-20 16:37:54C10
 **TRAVELLING WITH 17120550**

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-30 Cont ID  
Sent By shill Date 2018-04-30 Time 08:46 Rev Time 0.00
Received By shill Date 2018-04-12 Time 15:37 Sent To  
Notes
2018-04-13 15:37:24C11 - *TRAVELLING WITH 17120550*

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-25 Cont ID  
Sent By cpuell Date 2018-01-25 Time 10:10 Rev Time 0.00
Received By cpuell Date 2017-12-14 Time 10:57 Sent To  
Notes
2017-12-18 10:57:26C04 - TRAVELLING WITH 17120550

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-10-18 Cont ID  
Sent By cthroop Date 2018-10-18 Time 16:53 Rev Time 0.00
Received By cthroop Date 2018-10-18 Time 16:53 Sent To  
Notes
2018-10-18 16:53:39IMPACT FEES $0.00 PLANS ARE STAMPED. CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 14:25 Rev Time 0.00
Received By shill Date 2018-09-02 Time 14:25 Sent To  
Notes
2018-09-02 14:26:01PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-01-02 Cont ID  
Sent By aclange Date 2018-01-02 Time 13:59 Rev Time 0.00
Received By aclange Date 2018-01-02 Time 13:59 Sent To  
Notes
2018-01-02 14:00:33BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-08-23 Cont ID  
Sent By ccole Date 2018-08-23 Time 15:48 Rev Time 0.00
Received By ccole Date 2018-08-23 Time 15:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-06-26 Cont ID  
Sent By ccole Date 2018-06-26 Time 14:35 Rev Time 0.00
Received By ccole Date 2018-06-26 Time 14:34 Sent To  
Notes
2018-06-26 14:35:283RD REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17120551
 6/26/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: AS NOTED IN THE PREVIOUS REVIEW,
 MECHANICAL VENTILATION IS REQUIRED FOR THE BATHROOMS IN
 ACCORDANCE WITH TABLE 403.3 FBC-14 MECHANICAL. THIS IS
 A COMMERCIAL R2 OCCUPANCY, NOT A SINGLE FAMILY R3
 OCCUPANCY WHERE NATURAL VENTILATION OF BATHROOMS IS
 ALLOWED PER THE FBC-14 RESIDENTIAL. PLEASE REVIEW THE
 FOLLOWING CODES THAT ARE ALSO APPLICABLE TO THE
 PROPOSED PROJECT:
  
 A) SECTION 1011.1 FBC-14 EXISTING BUILDING WHICH STATES
 A CHANGE OF OCCUPANCY SHALL HAVE LIGHT AND VENTILATION
 IN COMPLIANCE WITH THE FLORIDA BUILDING CODE.
  
 B) SECTION 1203.4.2.1 FBC-14 BUILDING WHICH STATES
 BATHROOMS SHALL BE "MECHANICALLY VENTILATED".
  
 2) M1: THE MODEL NUMBER AEE12DT LISTED IN SCHEDULE IS
 NOT A FRIDGIDAIRE MODEL NUMBER. IT IS A GE NUMBER-
 PLEASE CORRECT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-24 Cont ID  
Sent By ccole Date 2018-04-24 Time 12:33 Rev Time 0.00
Received By ccole Date 2018-04-24 Time 12:33 Sent To  
Notes
2018-04-24 12:42:592ND REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17120551
 4/24/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENTS #2, 3, & 4 FROM THE 1ST REVIEW STILL EXIST.
 I HAVE PRINTED THEM BELOW WITH SOME ADDITIONAL NOTES-
 PLEASE COMPLY.
  
 2) SPACE HEATING SYSTEMS ARE REQUIRED FOR THE SUITES
 PER SECTION 309.1 FBC -14 MECHANICAL. PLEASE INDICATE
 HOW COMPLIANCE IS BEING MET. (THE NEW AC EQUIPMENT
 SCHEDULE ON THE M1 PLAN DOESN'T INDICATE IF THE SYSTEMS
 PROVIDE HEAT, AND NO CUT SHEETS FOR THE SYSTEMS HAVE
 BEEN PROVIDED FOR CLARIFICATION).
  
 3) VENTILATION IS REQUIRED FOR THE SUITES- EITHER
 NATURALLY OR MECHANICALLY- PER SECTION 401.2. PLEASE
 INDICATE HOW COMPLIANCE IS BEING MET. (THE PLAN APPEARS
 TO SHOW NATURAL VENTILATION. PLEASE SEE SECTION 402.2
 AN PROVIDE CALCULATIONS TO INDICATE COMPLIANCE).
  
 4) EXHAUST VENTILATION SYSTEMS ARE REQUIRED FOR BOTH
 THE KITCHENS AND THE BATHROOMS PER TABLE 403.3.
 INDICATE HOW COMPLIANCE IS BEING MET.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-28 Cont ID  
Sent By ccole Date 2017-12-27 Time 14:02 Rev Time 0.00
Received By ccole Date 2017-12-27 Time 13:45 Sent To  
Notes
2017-12-27 14:13:071ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17120551
 12/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A SCOPE OF WORK FOR MECHANICAL
 ALTERATIONS (IF APPLICABLE) WITH CORRESPONDING DRAWINGS
 AND DETAILS- SECTION 1009.1 EXISTING BUILDING CODE.
  
 2) SPACE HEATING SYSTEMS ARE REQUIRED FOR THE SUITES
 PER SECTION 309.1 FBC -14 MECHANICAL. PLEASE INDICATE
 HOW COMPLIANCE IS BEING MET.
  
 3) VENTILATION IS REQUIRED FOR THE SUITES- EITHER
 NATURALLY OR MECHANICALLY- PER SECTION 401.2. PLEASE
 INDICATE HOW COMPLIANCE IS BEING MET.
  
 4) EXHAUST VENTILATION SYSTEMS ARE REQUIRED FOR BOTH
 THE KITCHENS AND THE BATHROOMS PER TABLE 403.3.
 INDICATE HOW COMPLIANCE IS BEING MET.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-07-10 Cont ID  
Sent By gjohnson Date 2018-07-10 Time 14:20 Rev Time 0.00
Received By gjohnson Date 2018-07-10 Time 14:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2018-04-24 Cont ID  
Sent By gjohnson Date 2018-04-24 Time 07:47 Rev Time 0.00
Received By gjohnson Date 2018-04-21 Time 10:59 Sent To  
Notes
2018-04-24 07:48:06NO PLUMBING UNDER THIS PERMIT/GPJ

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-10 Cont ID  
Sent By gjohnson Date 2018-01-10 Time 08:28 Rev Time 0.00
Received By gjohnson Date 2018-01-10 Time 08:28 Sent To  
Notes
2018-01-10 08:28:571ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT.A-4 AND A-5 PLEASE SHOW GRAB BARS TO BE MEASURED
 TO THE TOP OF THE GRIPPING SURFACE. PER FBC PL 609.4
  
 2. SHOW DIMENSIONS FOR FBC ACC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS
  
 3. PLEASE SHOW HOT AND COLD AND LABEL PIPING ON WATER
 RISER. PER WPB AMEND TO FBC 107.2.1
  
 4. BECAUSE OF THE AGE OF THE BUILDING AND THIS BEING A
 CHANGE OF OCCUPANCY THE SAFETY PIPING ON THE WATER
 HEATER WILL NEED TO BE BROUGHT UP TO CODE, THE T+P
 RELIEF VALVE AND DRAIN LINE AND THERMAL EXPANSION. PER
 FBC PL CH 504 AND 607.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-07-17 Time   Rev Time 0.00
Received By pgreilic Date 2018-07-17 Time 10:19 Sent To  
Notes
2018-07-17 15:55:31PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-04-19 Time   Rev Time 0.00
Received By pgreilic Date 2018-04-19 Time 16:46 Sent To  
Notes
2018-04-19 16:47:23PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By PG Date 2018-01-24 Time   Rev Time 0.00
Received By pgreilic Date 2018-01-24 Time 15:07 Sent To  
Notes
2018-01-24 15:09:08FAILED
  
 1.) CORRECT DESCRIPTION OF WORK ON PERMIT
 2.) UNCLEAR WHAT CHANGES ARE BEING PROPOSED TO THE
 SOUTH BUILDING
 3.) PAVING/RESTRIPING WILL REQUIRE A SEPARATE PERMIT,
 STANDARD CITY OF WEST PALM BEACH DETAILS MUST BE
 PROVIDED
  
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
  