Plan Review Details - Permit 17120526
Plan Review Stops For Permit 17120526
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-01-25 Cont ID  
Sent By jleahy Date 2018-01-25 Time 13:01 Rev Time 0.00
Received By jleahy Date 2018-01-25 Time 13:01 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-15 Cont ID  
Sent By jleahy Date 2017-12-15 Time 15:31 Rev Time 0.00
Received By jleahy Date 2017-12-15 Time 15:31 Sent To  
Notes
2017-12-15 15:34:02ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER SHOWS #2 PANEL SCHEDULE SHOWS #1
  
 ONLY ONE SET OF FLOOR PLAN DRAWINGS.
  
 PLEASE INDICATE TYPE OF WIRE USED COPPER OR ALUMINUM
  
 PROVIDE LOAD CALCULATION FOR THE RISER UP TO FPL..
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-25 Cont ID  
Sent By jleahy Date 2018-01-25 Time 13:01 Rev Time 0.00
Received By jleahy Date 2018-01-17 Time 14:19 Sent To  
Notes
2018-01-18 14:19:29RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-15 Cont ID  
Sent By jleahy Date 2017-12-15 Time 15:34 Rev Time 0.00
Received By jleahy Date 2017-12-13 Time 09:06 Sent To  
Notes
2017-12-14 09:06:49ELEC <5K