Plan Review Stops For Permit 17120404 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2017-12-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-12-12 |
Time |
11:43 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-12-12 |
Time |
11:43 |
Sent To |
|
|
Notes |
2017-12-12 11:45:04 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. FBC EB 708.1.1, NOT MORE THAN 25 PERCENT OF THE | | TOTAL ROOF AREA OR ROOF SECTION OF ANY EXISTING | | BUILDING OR STRUCTURE SHALL BE REPAIRED, REPLACED OR | | RECOVERED IN ANY 12 MONTH PERIOD UNLESS THE ENTIRE | | ROOFING SYSTEM OR ROOF SECTION CONFORMS TO THE | | REQUIREMENTS OF THIS CODE. | | | | |
|
|