Plan Review Stops For Permit 17120310 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2021-04-19 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-04-19 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-04-19 |
Time |
15:07 |
Sent To |
|
|
Notes |
2021-04-19 16:14:25 | BUILDING REVIEW APPROVED WITH PROVISO: | | NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO | | INSTALLATION TO AVOID CONFLICTS/DELAYS. : | | 1-DEFERRED SUBMITTALS: | | WINDOWS, DOORS, ROOFING AND ROOF VENTS, ALUMINUM | | SOFFITS, | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | RESPONSIBLE CHARGE FOR REVIEW PRIOR TO SUBMITTAL TO | | THIS OFFICE. SEC. 107.3.4.1 CITY AMENDMENTS. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2021-03-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-03-08 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-03-08 |
Time |
09:11 |
Sent To |
|
|
Notes |
2021-03-08 09:43:32 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW | | COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | ORIGINAL COMMENT: | | 1- ENERGY CALCULATIONS: | | THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED AND | | DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY | | DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS | | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, | | 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO | | BEGIN CONSTRUCTION. | | | | RESPONSE: | | SIGNED ENERGY CALCULATIONS SUBMITTED ARE FOR ANOTHER | | HOUSE. ENERGY CALCULATIONS SUBMITTED ARE FOR 425 HOGANS | | ST. THIS PERMIT APPLICATION IS FOR 422 20TH ST. PROVIDE | | CORRECT ENERGY CALCULATIONS. | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, | | | | 2- OK. | | | | 3- OK. | | | | ORIGINAL COMMENT: | | 4- PROVIDE BOUNDARY LINE SURVEY AS REQUIRED BY SEC. | | 107.2.5 CITY AMENDMENTS. | | PROVIDE SURVEY WITH ORIGINAL SEAL/SIGNATURE (DIGITAL | | SIGNATURE OR HARDCOPY ORIGINAL) AS REQUIRED BY CHAPTER | | 472 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS FOR | | PUBLIC RECORDS. | | | | RESPONSE: | | SURVEY UPLOADED IS FOR LOT 4. THIS PERMIT APPLICATION | | IS FOR LOT 2. PROVIDE CORRECT SURVEY. NOTE: PLEASE | | UPLOAD THE SURVEY IN THE "DRAWINGS" FOLDER NOT IN THE | | "SUPPORTING DOCUMENTS" FOLDER AS REQUIRED BY THE CITY | | GUIDELINES FOR DIGITAL SUBMITTALS. | | SEC. 107.2.1 CITY AMENDMENTS. | | | | ORIGINAL COMMENT: | | 5- MERRY PLACE LOT GRADING SHEET C1: | | A) DRAWING C1 WAS UPLOADED IN THE "SUPPORTING | | DOCUMENTS" FOLDER INSTEAD OF THE "DRAWINGS" FOLDER. ALL | | DRAWINGS NEED TO BE UPLOADED IN THE "DRAWINGS" FOLDER | | (WITH PROPER DIGITAL SIGNATURE) AS REQUIRED BY THE CITY | | DIGITAL PLAN REVIEW INSTRUCTIONS AND SEC. 107.2.1.3 | | CITY AMENDMENTS FOR PROPER RECORDS RETENTION. | | | | RESPONSE: | | NOW WE ARE MISSING DRAWING C1. PLEASE UPLOAD DRAWING C1 | | INTO THE DRAWINGS FOLDER. | | | | 6-DEFERRED SUBMITTALS: | | WINDOWS, DOORS, ROOFING AND ROOF VENTS, ALUMINUM | | SOFFITS, RAILINGS AND GUARDRAILS. | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | RESPONSIBLE CHARGE FOR REVIEW PRIOR TO SUBMITTAL TO | | THIS OFFICE. SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | 7- NEW COMMENT FOR CLARIFICATION: | | THERE ARE TWO SITE PLANS SUBMITTED. ONE OF THEM IS | | SHEET A-0.1 AND THE OTHER ONE IS SHEET SP-1. CLARIFY | | WHY SUBMITTING 2 DIFFERENT DRAWINGS FOR THE SITE PLAN | | AND WHICH ONE IS THE CORRECT ONE. PLEASE PROVIDE ONLY | | THE ONE TO BE CONSIDERED TO AVOID CONFLICTS/DELAYS. | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-10-30 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-10-30 |
Time |
18:06 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-10-30 |
Time |
16:53 |
Sent To |
|
|
Notes |
2020-10-30 18:07:07 | NEW SINGLE FAMILY RESIDENCE R3) BUILDING REVIEW | | COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- ENERGY CALCULATIONS: | | THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED AND | | DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY | | DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS | | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, | | 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO | | BEGIN CONSTRUCTION. | | | | 2- STRUCTURAL DRAWINGS S1, S2, S3 AND S4 WERE NOT | | UPLOADED FOR REVIEW. NEED TO UPLOAD THESE DRAWINGS. | | SEC. 107.2.1 CITY AMENDMENTS. | | | | 3- 03/08/21 COMMENT WAS OMITTED. THIS IS ONE STORY | | HOUSE. JG. | | | | 4- PROVIDE BOUNDARY LINE SURVEY AS REQUIRED BY SEC. | | 107.2.5 CITY AMENDMENTS. | | PROVIDE SURVEY WITH ORIGINAL SEAL/SIGNATURE (DIGITAL | | SIGNATURE OR HARDCOPY ORIGINAL) AS REQUIRED BY CHAPTER | | 472 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS FOR | | PUBLIC RECORDS. | | | | 5- MERRY PLACE LOT GRADING SHEET C1: | | A) DRAWING C1 WAS UPLOADED IN THE "SUPPORTING | | DOCUMENTS" FOLDER INSTEAD OF THE "DRAWINGS" FOLDER. ALL | | DRAWINGS NEED TO BE UPLOADED IN THE "DRAWINGS" FOLDER | | (WITH PROPER DIGITAL SIGNATURE) AS REQUIRED BY THE CITY | | DIGITAL PLAN REVIEW INSTRUCTIONS AND SEC. 107.2.1.3 | | CITY AMENDMENTS FOR PROPER RECORDS RETENTION. | | | | B) DRAWING C1 SHOWS DETAIL SECTIONS A/C2 AND B/C2. | | WHERE ARE THESE DETAILS?. SHEET C2 WAS NOT UPLOADED. | | PROVIDE THESE DETAILS AND REVISE DETAIL REFERENCE | | ACCORDINGLY. SEC. 107.2.1 CITY AMENDMENTS. | | | | 6-DEFERRED SUBMITTALS: | | WINDOWS, DOORS, ROOFING AND ROOF VENTS, ALUMINUM | | SOFFITS, RAILINGS AND GUARDRAILS. | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | RESPONSIBLE CHARGE FOR REVIEW PRIOR TO SUBMITTAL TO | | THIS OFFICE. SEC. 107.3.4.1 CITY AMENDMENTS. | | | | 7- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW. | | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S | | OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS | | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS | | UPDATED TO $199,160. THE PERMIT FEE BALANCE IS $3801.84 | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2021-03-09 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-03-09 |
Time |
07:09 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-03-09 |
Time |
06:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2020-10-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-10-28 |
Time |
07:32 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-10-28 |
Time |
07:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
Rev No |
1 |
Status |
P |
Date |
2020-10-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-10-28 |
Time |
07:31 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-10-28 |
Time |
07:26 |
Sent To |
|
|
Notes |
2020-10-28 07:32:05 | LOW VOLTAGE FOR TVS ONLY JLEAHY |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-04-22 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-04-22 |
Time |
11:53 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-04-15 |
Time |
13:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-04-09 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2021-04-09 |
Time |
09:04 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2021-02-26 |
Time |
08:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-11-04 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2020-11-04 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2020-10-26 |
Time |
12:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2021-04-25 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-04-25 |
Time |
08:14 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-04-25 |
Time |
08:14 |
Sent To |
|
|
Notes |
2021-04-25 08:14:24 | RECEIPT MU-2021-19509 - $0.00 DUE |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2020-11-02 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-11-02 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-11-02 |
Time |
13:06 |
Sent To |
|
|
Notes |
2020-11-02 13:07:22 | IMPACT FEES - DIGITAL SUBMITTALS | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2020-10-29 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-10-29 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-10-29 |
Time |
15:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2021-03-09 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-03-09 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-03-09 |
Time |
10:25 |
Sent To |
|
|
Notes |
2021-03-09 10:56:19 | 03/09/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2020-10-27 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-10-27 |
Time |
09:12 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-10-27 |
Time |
09:12 |
Sent To |
|
|
Notes |
2020-10-27 09:12:51 | 10/27/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. PLEASE HAVE YOUR PLANS THAT ARE SIGNED AND SEALED BE | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - | | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL | | SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE | | ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN | | REVIEW REQUEST FORM" EXPLAINING THE REASON FOR | | SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW | | REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND | | ASKING FOR THE FORM. | | | | 2. ON THE P-1 SHEET, THE WASHING MACHINE IS ON A 2" | | DRAIN AND THERE IS NO CODE REFERENCE FOR THE SIZE IN | | THE RESIDENTIAL CODE BUT IN THE 2017 FBC RESIDENTIAL | | 2601.1, IT SAYS THAT ANY NOT ADDRESSED BY THIS CODE | | SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF THE | | FLORIDA BUILDING CODE, PLUMBING. IN THE 2017 FLORIDA | | BUILDING CODE ? PLUMBING TABLE TABLE 709.1 DRAINAGE | | FIXTURE UNITS FOR FIXTURES AND GROUPS FOR AUTOMATIC | | CLOTHE WASHERS THE RESIDENTIAL HAS A FOOT NOT (G) THAT | | SENDS YOU TO 406.2 FOR SIZING REQUIREMENTS FOR FIXTURE | | DRAIN, BRANCH DRAIN, AND DRAINAGE STACK FOR AN | | AUTOMATIC CLOTHES WASHER STANDPIPE. THE FIXTURE DRAIN | | FOR THE STANDPIPE SERVING AN AUTOMATIC CLOTHES WASHER | | SHALL CONNECT TO A 3-INCH PER THE 2017 FBC SEC. 406.2 | | WASTE CONNECTION. | | | | 3. IT IS ALSO RECOMMENDED THAT THE TOILET ON THE BRANCH | | FOR THE WASHING MACHINE BE MOVED TO THE BATHROOM GROUP | | BUT NOT ENFORCED. THIS IS TO PREVENT SUDS FROM CHOKING | | THE TRAP OF THE TOILET WHICH WILL MAKE IT REGURGITATE | | FOR AIR. THE VENT SHOWN WILL NOT WORK AS IT WILL NOT | | HAVE A WALL. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
N |
Date |
2020-11-02 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-11-02 |
Time |
13:09 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-11-02 |
Time |
13:09 |
Sent To |
|
|
Notes |
2020-11-02 13:10:15 | ROOFING PRODUCT APPROVALS AND ROOFING VENTS SHOWN ON | | PLANS WILL BE SUBMITTED LATER AS DEFERRED SUBMITTALS. | | JG. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2021-04-19 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-04-19 |
Time |
16:23 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-04-19 |
Time |
16:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2021-03-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-03-08 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-03-08 |
Time |
10:49 |
Sent To |
|
|
Notes |
2021-03-08 10:34:18 | SITE PLAN DRAWING SP-1 UPLOADED ON 01/20/21 DOESN'T | | HAVE A DIGITAL SIGNATURE. PLEASE PROVIDE DIGITAL | | SIGNATURE AS DONE WITH THE OTHER DRAWINGS. | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-11-02 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-11-02 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-11-02 |
Time |
13:07 |
Sent To |
|
|
Notes |
2020-11-02 13:09:38 | SIGNATURE: | | DRAWINGS SUBMITTED: | | DRAWINGS HAVE COPY OF THE DESIGN PROFESSIONAL | | SEAL/SIGNATURE. PLEASE RESUBMIT ALL DRAWINGS WITH | | DESIGN PROFESSIONAL ORIGINAL SEAL/SIGNATURE. SINCE THIS | | IS AN ELECTRONIC SUBMITTAL, IT IS BETTER TO RESUBMIT | | WITH THE DESIGN PROFESSIONAL DIGITAL SIGNATURE. | | OTHERWISE, HARDCOPIES OF PLANS WITH DESIGN PROFESSIONAL | | ORIGINAL SEAL/SIGNATURE MAY BE DROPPED OFF IN CITY | | HALL. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2021-04-22 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2021-04-22 |
Time |
11:01 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2021-04-22 |
Time |
11:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2021-04-08 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2021-04-08 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2021-04-08 |
Time |
10:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-11-04 |
|
|
Cont ID |
|
Sent By |
avann |
Date |
2020-11-04 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2020-11-04 |
Time |
09:27 |
Sent To |
|
|
Notes |
2020-11-04 09:27:31 | 11/4/20-FAILED. THE CORNER SETBACK REQIUREMENT FOR | | MERRYPLACE SMALL COTTAGE HOMES IS 6.5 FEET. | | | | ANGELLA VANN, AICP | | 561-822-1441 | | [email protected] |
|
|