Plan Review Details - Permit 17120303
Plan Review Stops For Permit 17120303
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-12-19 Cont ID  
Sent By hhall Date 2017-12-19 Time 11:18 Rev Time 0.00
Received By hhall Date 2017-12-19 Time 11:18 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-12-08 Cont ID  
Sent By cpuell Date 2017-12-19 Time 12:40 Rev Time 0.00
Received By pleduc Date 2017-12-08 Time 12:52 Sent To ENG
Notes
2017-12-08 13:24:25THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) INSTALL PER NFPA 24, STANDARD FOR THE INSTALLATION
 OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES,
 2010 EDITION.
  
  
 2) DO NOT COVER ANY UNDERGROUND.
  
  
 3) PROVIDE SPEC SHEETS FOR ALL BOLT TORQUE
 REQUIREMENTS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-19 Cont ID  
Sent By cpuell Date 2017-12-19 Time 12:40 Rev Time 0.00
Received By cpuell Date 2017-12-07 Time 18:08 Sent To FIRE
Notes
***NONE***