Plan Review Details - Permit 17120042
Plan Review Stops For Permit 17120042
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By kconrad Date 2018-06-27 Time 06:37 Sent To FIRE
Notes
2018-06-27 06:57:37TCO/1ST PHASE CONSTRUCTION/OCCUPANCY SEPARATION PLAN
  
  
 1) ALL WORK SHALL BE COMPLETED WITHIN THE INDICATED
 AREAS OF THE PROPOSED OCCUPANCY AND SHALL COMPLY WITH
 ALLL LIFE SAFETY AND ACCESSIBILITY MINIMUM REQUIRES
 PURSUANT TO THE FLORIDA BUILDING CODE.
  
 2) REQUIRE ELEVATOR #1 CERTIFICATION,
  
 3) ALL CONSTRUCTION AREAS SHALL BE SEPARATED
 APPROPRIATELY FROM THE PROPOSED OCCUPANCY AND SHALL NOT
 COMPROMISE THE INGRESS/EGRESS REQUIREMENTS.:
 CONSTRUCTION SIGNS SHALL BE POSTED IN ALL APPLICABLE
 AREAS PROHIBITING OCCUPANCY. CONSTRUCTION PERSONNEL
 SHALL NOT USE ANY PERMITTED OCCUPIED AREAS.
  
 4) TACTILE EXIT SIGNS SHALL BE INSTALLED PER THE FBC,
 SECTION 1011.
  
 5) ALL WORK IN PROGRESS AT THE FRONT BUILDING ELEVATION
 SHALL BE COMPLETED.
  
 6) ALL MECHANICAL, ELECTRICAL, PLUMBING AND FIRE FINAL
 INSPECTIONS SHALL BE COMPLETED AND APPROVED FOR THE
 REQUESTED TCO.
  
 7) THE NORTH AND SOUTH STAIRS LEADING TO THE 4TH FLOOR
 SHALL HAVE A SIGN POSTED, CONTRUCTION PERSONNEL ONLY.
  
 8) PROVIDE STAIRWAY IDENTIFICATION SIGNS (TACTILE) PER
 THE FBC, SECTION 1022.9.
  
 9) COMPLETE ALL STAIR GUARD/HANDRAIL MODIFICATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By aclange Date 2018-01-18 Time 16:03 Rev Time 0.00
Received By aclange Date 2018-01-18 Time 13:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-22 Cont ID  
Sent By jwitmer Date 2017-12-22 Time 07:58 Rev Time  
Received By jwitmer Date 2017-12-22 Time 06:01 Sent To  
Notes
2017-12-22 07:48:262014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120042
 ADD: 2410 METROCENTRE BLVD.
 CONT: VERDEX CONSTRUCTION LLC
 TEL: 561-440-1600
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. DEC. 22/ 2017
 ACTION: DENIED
  
 1) THE COVERSHEET LIST THIS BUILDING AS A BUSINESS
 OCCUPANCY, CONSTRUCTION TYPE: III-B, FULLY SPRINKLERED
 NFPA-13, 19,951 SQUARE FEET PER FLOOR AND A (4) STORY
 BUILDING.
  
 THE 2014 FBC-B TABLE 503 UNDER HEIGHT AND AREA LIST FOR
 A BUSINESS OCCUPANCY FOR A TYPE III-B BUILDING ONLY 3
 STORIES AND AN ALLOWABLE AREA PER FLOOR OF 19,000
 SQUARE FEET. THE PLANS ARE SILENT IF THE DESIGNER OF
 RECORD HAS TAKEN ADVANTAGE OF GENERAL EXCEPTIONS TO:
  
 TABLE 503 SEE FOOTNOTE (A)
 A. SEE THE FOLLOWING SECTIONS FOR GENERAL EXCEPTIONS TO
 TABLE 503:
 1. SECTION 504.2, ALLOWABLE BUILDING HEIGHT AND STORY
 INCREASE DUE TO AUTOMATIC SPRINKLER SYSTEM
 INSTALLATION.
 2. SECTION 506.2, ALLOWABLE BUILDING AREA INCREASE DUE
 TO STREET FRONTAGE.
 3. SECTION 506.3, ALLOWABLE BUILDING AREA INCREASE DUE
 TO AUTOMATIC SPRINKLER SYSTEM INSTALLATION.
  
 PLEASE PROVIDE AREA INCREASES TAKEN UNDER FBC-B 506.1
 AND EQUATION 5-1.
  
 2) THE COVERSHEET LIST THIS BUILDING AS A 4 STORY
 THRESHOLD BUILDING. THRESHOLD BUILDING / FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 2A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN. THE
 ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
 FORMS E-MAILED TO: [email protected] 12/22/2017
 06:48 AM
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) COMPLIED. NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS
 ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 3A) SHEET A6.1 AND DETAIL # 2 THE PLANS WILL NEED TO
 SHOW COMPLIANCE WITH:
 2014 FBC-B 1009.9.3 ENCLOSURES UNDER INTERIOR
 STAIRWAYS. THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE
 SPACES UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE
 PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION
 OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY
 ENCLOSURE, WHICHEVER IS GREATER. NOTE UNDER THE 2012
 IBC COMMENTARY. NO STORAGE ALLOWED EVEN FOR OPEN
 STAIRS.
  
 3B) THE NORTH STAIR PLAN SHOW 4X4 WOOD POST HOLDING UP
 THE MID-LANDING AT STRINGERS, BUT IN THE CUT SECTION 2
 OF THE STAIRS, THE PLAN DOES NOT SHOW THE 4X4 POST.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3C) SHEET A6.1 SHOWS IN DETAIL 4 THE STAIR GUARDRAIL
 AND HAND RAIL. WHAT THIS DETAIL DOES NOT INDICATE HOW
 THE GUARDRAIL IS TO BE ANCHORED INTO THE WOOD
 STRINGERS, AND OR WOOD TREADS. SHOW COMPLIANCE WITH:
  
 FBC-B 1607.8.1 HANDRAILS AND GUARDS. HANDRAILS AND
 GUARDS SHALL BE DESIGNED TO RESIST A LINEAR LOAD OF 50
 POUNDS PER LINEAR FOOT (PLF) IN ACCORDANCE WITH SECTION
 4.5.1 OF ASCE 7. GLASS HANDRAIL ASSEMBLIES AND GUARDS
 SHALL ALSO COMPLY WITH SECTION 2407.
  
 3C)(1) 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND
 GUARDS SHALL ALSO BE DESIGNED TO RESIST A CONCENTRATED
 LOAD OF 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF
 ASCE 7.
  
 3C)(2) 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE
 RAILS (ALL THOSE EXCEPT THE HANDRAIL), BALUSTERS AND
 PANEL FILLERS SHALL BE DESIGNED TO RESIST A
 CONCENTRATED LOAD OF 50 POUNDS IN ACCORDANCE WITH
 SECTION 4.5.1 OF ASCE 7.
  
 3D) PLEASE REVIEW THE 3RD FLOOR HANDRAIL SYSTEM, THE
 TRANSITION TO A HORIZONTAL POSITION STARTS AT THE 1ST
 TREAD, THIS IS WRONG. THE SLOPE OF THE HANDRAIL IS TO
 CONTINUE THE SLOPE FOR THE DEPTH OF ONE TREAD BEYOND
 THE BOTTOM RISER. PLEASE REVIEW FBC-B 1012.6 HANDRAIL
 EXTENSIONS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-12-21 Cont ID  
Sent By jleahy Date 2017-12-21 Time 14:29 Rev Time 0.00
Received By jleahy Date 2017-12-21 Time 08:37 Sent To  
Notes
2017-12-21 14:32:48FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVISO!
  
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC
 110.10
  
 GFCI REQUIRED WHEN OUTLETS ARE WITHIN 6' OF A SINK.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2018-06-27 Cont ID  
Sent By pleduc Date 2018-06-27 Time   Rev Time 0.00
Received By pleduc Date 2018-06-27 Time 11:54 Sent To  
Notes
2018-06-27 11:30:10TCO PROPOSED SEPARATION REVIEW
  
 THE FOLLOWING IS AN UNOFFICIAL REVIEW BASED ON THE
 LIMITED PLAN SUBMITTAL SHEET.
  
 THE FIRE PREVENTION BUREAU DOES NOT HAVE AN OBJECTION
 TO A PROPOSED TCO; HOWEVER, THE FOLLOWING COMMENTS WILL
 NEED TO BE ADDRESSED AND OFFICIAL PLANS WILL NEED TO BE
 SUBMITTED FOR REVIEW AND APPROVAL.
  
 THIS REVIEW DOES NOT GRANT APPROVAL TO OCCUPY ANY SPACE
 OR AREA.
  
  
 1) SHEET A 13.1 - PROVIDE AN OUT OF SERVICE, OOS, SIGN
 AT ELEVATOR # 2.
  
  
  
 2) SHEET 13.1 - THERE ARE TWO STATEMENTS INDICATED AT
 EACH SIDE OF THE SHADED CONSTRUCTION AREAS, "CONTROLLED
 ACCESS TO CONSTRUCTION AREA.
  
 PLEASE PROVIDE A DETAILED EXPLANATION/DESCRIPTION OF
 WHAT THIS STATMENT MEANS AND HOW WILL COMPLY WITH THE
 LIFE SAFETY CODE ON TWO POINTS.
  
 HOW WILL THE GENERAL PUBLIC/OFFICE STAFF BE PROTECTED
 FROM ENETERING THE CONSTRUCTION AREAS?
  
 HOW WILL THESE AREAS PROVIDE FOR EXITING OF
 CONSTRUCTION WORKERS IN THE EVENT OF EMERGENCY?
  
  
  
  
 3) SHEET A 13.2 - PROVIDE A DETAILED EXPLANATION ON HOW
 EACH STAIRWELL DOOR TO THE CONSTRUCTION AREAS BE
 SECURED FROM THE CONSTRUCTION AREA ON TWO POINTS?
  
 HOW WILL THE GENERAL PUBLIC/OFFICE STAFF BE PROTECTED
 FROM ENETERING THE CONSTRUCTION AREAS?
  
 HOW WILL THESE AREAS PROVIDE FOR EXITING OF
 CONSTRUCTION WORKERS IN THE EVENT OF EMERGENCY?
  
  
  
 4) SHEET A 13.2 - PROVIDE A DETAILED EXPLANATION ON HOW
 THE ELEVATOR WILL BE CONTROLLED TO NOT LET PEOPLE OFF
 AT THE 2ND FLOOR CONSTRUCTION AREA.
  
  
  
 5) SHEET A 13.2 - PROVIDE PROVIDE AN OUT OF SERVICE,
 OOS, SIGN AT ELEVATOR # 2.
  
  
  
 6) SHEET A 13.3 - ELEVATOR # 2 IS NOT SHADED AND SHALL
 HAVE A OOS SIGN IN PLACE.
  
  
 7) SHEET A 13.3 - THE IS AN ACCESS STAIR INDICATED TO
 THE 4TH FLOOR. THERE IS NO 4TH FLOOR PLAN ATTACHED.
  
 PROVIDE A DETAILED EXPLANATION REGARDING THE 4TH FLOOR
 USE AND PROVIDE ALL APPLICABLE PLAN SHEETS OR
 CONTROLLED CONSTRUCTION AREA.
  
  
 8) ALL LIFE SAFETY SYSTEMS, FIRE ALARM AND FIRE
 SPRINKLER, SHALL BE FULLY OPERATIONAL, TESTED AND
 APPROVED THROUGH REVISED SHOP DRAWINGS, PRIOR TO ANY
 OCCUPANCY.
  
 THE LIFE SAFETY SYSTEMS SHALL BE MAINTAINED AND
 OPERATIONAL ALL ALL TIMES DURING THE TCO PHASE.
  
 ANY TIME EITHER SYSTEM IS DOWN FOR MORE THAN 4 HOURS
 YOU ARE REQUIRED TO CONDUCT A FIRE WATCH UNTIL IT IS
 FULLY OPERATIONAL.
  
 PLEASE REVIEW AND PROVIDE AN NOTE OF COMPLIANCE AND
 ACKNOWLEDGEMENT.
  
  
 9) PROVIDE DETAILED RESPONSES TO ALL OTHER CITY
 DISCIPLINE COMMENTS WITH APPROVAL.
  
  
 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-01-24 Cont ID  
Sent By pleduc Date 2018-01-22 Time   Rev Time 0.00
Received By pleduc Date 2018-01-22 Time 09:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-12-07 Cont ID  
Sent By pleduc Date 2017-12-07 Time   Rev Time 0.00
Received By pleduc Date 2017-12-06 Time 15:18 Sent To  
Notes
2017-12-07 09:19:03THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ALL FIRE ALARM AND FIRE SPRINKLER WORK SHALL BE DONE
 BY CERTIFIED LIFE SAFETY CONTRACTORS UNDER SEPARATE
 SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-01-31 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-30 Time 13:04 Sent To  
Notes
2018-01-30 13:04:54RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-25 Cont ID  
Sent By ccole Date 2018-01-25 Time 13:56 Rev Time 0.00
Received By ccole Date 2018-01-16 Time 14:40 Sent To I
Notes
2018-01-17 14:40:23C31

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-01-12 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-11 Time 14:46 Sent To  
Notes
2018-01-12 14:46:13RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-12-22 Time   Rev Time 0.00
Received By jwitmer Date 2017-12-22 Time 06:01 Sent To  
Notes
2017-12-04 14:44:53C01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-01-18 Cont ID  
Sent By aclange Date 2018-01-18 Time 14:42 Rev Time 0.00
Received By aclange Date 2018-01-18 Time 14:42 Sent To  
Notes
2018-01-18 14:43:49PALM BEACH COUNTY IMPACT FEES
  
 1/9/18
  
 MM-2018 751

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2018-01-12 Cont ID  
Sent By jwitmer Date 2018-01-12 Time 15:41 Rev Time 0.00
Received By jwitmer Date 2018-01-12 Time 15:40 Sent To  
Notes
2018-01-12 15:41:19PALM BEACH COUNTY IMPACT FEES
 MU-2018-751
 NO FEES DUE.
 J. W.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-22 Cont ID  
Sent By jwitmer Date 2017-12-22 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2017-12-22 Time 06:01 Sent To  
Notes
2017-12-22 07:51:43IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-01-31 Cont ID  
Sent By ccole Date 2018-01-31 Time 12:11 Rev Time 0.00
Received By ccole Date 2018-01-30 Time 17:07 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-01-25 Cont ID  
Sent By ccole Date 2018-01-25 Time 12:45 Rev Time 0.00
Received By ccole Date 2018-01-25 Time 09:39 Sent To  
Notes
2018-01-25 12:50:282ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17120042
 1/25/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENTS #2, 3, 4, & 5 FROM THE 1ST REVIEW STILL
 EXIST. THE REVISED ENERGY AND AC CALCULATIONS WERE NOT
 SUBMITTED-, AND THE SYSTEM RISER DIAGRAM WAS NOT
 CORRECTED. SEE BELOW:
  
 (2) THE ENERGYGAUGE COMPLIANCE REPORT IS LISTING DATA
 FOR ZONES AND AHU IDENTIFICATIONS THAT DO NOT MATCH
 WITH THE PLANS- THERE ARE NO ZONES SHOWN ON THE PLANS,
 AND THE AHU'S SHOWN ON THE PLANS ARE LABELED 1-1, 1-2,
 2-1, 2-2, 3-1, 3-2, AND 4-1.
  
 (3) THE AC CALCULATIONS ARE INDICATING THAT THE SYSTEMS
 SELECTED (AS SHOWN ON THE ENERGY CALCULATIONS ) ARE
 OVERSIZED- SEE SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION.
  
 (4) THE ENERGY REPORT IS MISSING COMPLIANCE DATA FOR
 THE CHILLER, THE 3-TON MINI SPLIT SYSTEM, AND THE
 PIPING SYSTEM.
  
 (5) M7.2: THE SYSTEM RISER DIAGRAM SHOWS TWO CHILLERS,
 TWO ERV'S, AND WFC SYSTEMS THAT ARE NOT SHOWN ON THE
 PLANS - PLEASE CLARIFY.
  
 2) REGARDING THE MAKEUP AIR TRANSFER DUCTS FROM THE
 CORRIDORS TO THE REST ROOMS, PLEASE SEE SECTION 601.2
 EXCEPTION 1 AND PROVIDE CALCULATIONS TO VERIFY
 COMPLIANCE.
  
 3) M0.1 & M6.3: THE EXHAUST AIR CALCULATION TABLE SHOWS
 A TOTAL OF 300 CFMS OF EXHAUST AIR PROVIDED, HOWEVER
 THE EF SCHEDULE SHOWS A TOTAL OF 2500 CFMS PROVIDED.
  
 4) COMMENT #7 FROM THE 1ST REVIEW STILL EXISTS. THE
 REVISED PLANS DO NOT CLARIFY IF ALL OF THE VAV'S
 SHARING THE COMMON RETURN AIR PLENUMS WILL SHUT DOWN IF
 A SMOKE DETECTOR ACTIVATES. PLEASE REVIEW THE EXCEPTION
 LISTED UNDER SECTION 606.2.2.
  
 606.2.2 COMMON SUPPLY AND RETURN AIR SYSTEMS.
 WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY
 OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN
 CAPACITY GREATER THAN 2,000 CFM (0.9 M3/S), THE RETURN
 AIR SYSTEM SHALL BE PROVIDED WITH SMOKE DETECTORS IN
 ACCORDANCE WITH SECTION 606.2.1.
  
 EXCEPTION: INDIVIDUAL SMOKE DETECTORS SHALL NOT BE
 REQUIRED FOR EACH FAN-POWERED TERMINAL UNIT, PROVIDED
 THAT SUCH UNITS DO NOT HAVE AN INDIVIDUAL DESIGN
 CAPACITY GREATER THAN 2,000 CFM (0.9 M3/S) AND WILL BE
 SHUT DOWN BY ACTIVATION OF ONE OF THE FOLLOWING:
  
 1. SMOKE DETECTORS REQUIRED BY SECTIONS 606.2.1 AND
 606.2.3.
  
 2. AN APPROVED AREA SMOKE DETECTOR SYSTEM LOCATED IN
 THE RETURN AIR PLENUM SERVING SUCH UNITS.
  
 3. AN AREA SMOKE DETECTOR SYSTEM AS PRESCRIBED IN THE
 EXCEPTION TO SECTION 606.2.1.
  
 IN ALL CASES, THE SMOKE DETECTORS SHALL COMPLY WITH
 SECTIONS 606.4 AND 606.4.1.
  
 5) THE SUBMITTALS FOR THE FIRE DAMPER AND FIRESTOPPING
 ARE VERY POOR COPIES THAT HAVE LARGE AMOUNTS OF PRINT
 AND DIAGRAMS MISSING- PLEASE PROVIDE GOOD COPIES.
  
 6) REGARDING THE REQUEST FOR THE WIND LOAD ENGINEERING
 TO BA DEFERRED SUBMITTAL PLEASE REVIEW THE FOLLOWING:
  
 1) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 2) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-21 Cont ID  
Sent By ccole Date 2017-12-21 Time 10:15 Rev Time 0.00
Received By ccole Date 2017-12-21 Time 09:06 Sent To  
Notes
2017-12-21 12:25:301ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES.
 PERMIT #17120042
 12/20/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M6.3 & M7.3 WERE NOT SUBMITTED WITH THE PLAN
 SETS, AND THERE ARE TWO DIFFERENT M6.1 SHEETS. DUE TO
 THESE PLAN OMISSIONS, THE AC EQUIPMENT SCHEDULES FOR
 SYSTEMS IN THE OCCUPIED AREAS ARE NOT AVAILABLE TO
 REVIEW AND COMPARE WITH THE CALCULATIONS.
  
 2) THE ENERGYGAUGE COMPLIANCE REPORT IS LISTING DATA
 FOR ZONES AND AHU IDENTIFICATIONS THAT DO NOT MATCH
 WITH THE PLANS- THERE ARE NO ZONES SHOWN ON THE PLANS,
 AND THE AHU'S SHOWN ON THE PLANS ARE LABELED 1-1, 1-2,
 2-1, 2-2, 3-1, 3-2, AND 4-1.
  
 3) THE AC CALCULATIONS ARE INDICATING THAT THE SYSTEMS
 SELECTED (AS SHOWN ON THE ENERGY CALCULATIONS ) ARE
 OVERSIZED- SEE SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION.
  
 4) THE ENERGY REPORT IS MISSING COMPLIANCE DATA FOR THE
 CHILLER, THE 3-TON MINI SPLIT SYSTEM, AND THE PIPING
 SYSTEM.
  
 5) M7.2: THE SYSTEM RISER DIAGRAM SHOWS TWO CHILLERS,
 TWO ERV'S, AND WFC SYSTEMS THAT ARE NOT SHOWN ON THE
 PLANS - PLEASE CLARIFY.
  
 6) M2.1, M2.2, M2.3: THE JUMP DUCTS TRANSFERRING AIR
 INTO THE CORRIDORS ARE NOT PERMITTED PER SECTION 601.2.
  
 7) M2.1, M2.2, M2.3: SHOW COMPLIANCE WITH SECTION
 606.2.2 FOR THE AHU'S AND VAV BOXES SHARING THE COMMON
 RETURN PLENUMS ON EACH FLOOR. INDICATE IF AREA SMOKE
 DETECTORS WILL BE INSTALLED IN THE COMMON PLENUM AND
 THE SEQUENCE OF OPERATION FOR SHUTDOWN OF THE AHU'S AND
 VAV BOXES.
  
 8) M2.1 & M2.2: SHOW COMPLIANCE WITH SECTION 401.4 AND
 401.5 RELATING TO THE O/A INTAKES. SUBMIT A FL. PRODUCT
 APPROVAL OR MIAMI-DADE NOA FOR THE LOUVERS.
  
 9) PROVIDE A SUBMITTAL FOR THE FIRE DAMPER, AND AN
 INSTALLATION DETAIL ON THE PLAN.
  
 10) PROVIDE A UL LISTED AND LABELED FIRESTOPPING SYSTEM
 FOR THE REFRIGERANT PIPING PENETRATIONS.
  
 11) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE CHILLER AND ROOF FAN INCLUDING ATTACHMENT DETAILS
 AND WIND DESIGN CRITERIA- SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By gjohnson Date 2018-01-18 Time 17:11 Rev Time 0.00
Received By gjohnson Date 2018-01-18 Time 17:11 Sent To  
Notes
2018-01-18 17:14:54PROVISO:
  
 1. PROVIDE A VENT ON FIXTURE BRANCH FOR HUB DRAINS FOR
 ELEVATOR SUMP PUMP. PER FBC PL 901.2.1
  
 SHALL COMPLY BEFORE FIRST ROUGH INSPECTION NEED
 REVISION ON PLAN.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-12-21 Cont ID  
Sent By gjohnson Date 2017-12-21 Time 12:15 Rev Time 0.00
Received By gjohnson Date 2017-12-21 Time 08:10 Sent To  
Notes
2017-12-21 14:16:551ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. CS.1 UNDER THE PLUMBING FIXTURE REQUIREMENTS
 THE FBC PL 403.1.1 REQUIRES THAT THE OCCUPANT LOAD BE
 DIVIDED BETWEEN MEN AND WOMEN THEN APPLIED TO TABLE
 403.1 . PER FLOOR THE CODE REQUIRES 3WC FOR MEN AND 3WC
 FOR WOMEN, 3 LAVATORY'S FOR MEN AND 3 LAVATORY'S FOR
 WOMEN WHICH YOU HAVE PROVIDED OVER FOR CLARITY PLEASE
 CORRECT THE CALCULATIONS ON SHT. CS.1
  
 2. PLEASE SHOW THE HEIGHT OF THE GRAB BARS IN THE
 SHOWER. SHALL COMPLY WITH FBC ACC 608.3.1 AND 609.4
  
 3. PLEASE SHOW COMPLIANCE OF THE SHOWER SEAT PER FBC
 ACC 610.3 AND 610.3.1
  
 4. URINALS SHALL NOT BE SET CLOSER THAN 15 INCHES FROM
 ITS CENTER TO ANY SIDE WALL, PARTITION, VANITY OR
 OTHERE OBSTRUCTION, OR CLOSER THAN 30 INCHES CENTER TO
 CENTER BETWEEN ADJACENT FIXTURES. THE DIMENSION OF 24"
 ON SHT A4.2 WILL NOT COMPLY. PER FBC PL 405.3.1
  
 5. SHT. A4.3 SHOW DIMENSIONS OF GRAB BARS IN AMBULATORY
 STALLS. FBC ACC 609.4
  
 6. SHT. A4.2 SHOW THE DIMENSION 7"-9" FOR THE CENTER OF
 THE TOILET PAPER DISPERSER OFF THE FRONT OF THE TOILET.
 FBC ACC 604.7
  
 7. WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. DRY
 WALL WITH WASHABLE PAINT DOES NOT COMPLY. PER FBC
 1210.2.2
  
 8. SHT. P2.1AND P5.1 SHOWS A HORIZONTAL DRY VENT ON THE
 MOP SINK FOR THE FIRCT FLOOR WHICH DOES NOT COMPLY WITH
 CODE PLEASE REMOVE FROM PLAN THAT MOP SINK WILL BE
 VENTED BY THE DRINKING FOUNTAIN STACK. PER FBC PL 905.3
 AND 905.4
  
 9. SHT. P5.1 THE DRAIN FROM ELEVATOR SUMP PUMP SHALL BE
 INDIRECT WASTE AS SHOWN ON DETAIN SHT. P0.1. PER FBC PL
 802.1.5
  
 10. P5.1 SHOWS EACH BANK OF FIXTURES ON EACH FLOOR
 VENTING THROUGH THE ROOF SEPARATELY IS THIS CORRECT 7
 SEPARATE ROOF PENETRATIONS PLEASE CLARIFY PER WPB AMEND
 TO FBC 107.2.1
  
 11. SHT. P0.1 ON THE WATER HEATER DETAIL THE NOTE AT
 THE BOTTOM IS INCORRECT THE FBC ENERGY CODE SEC SHOULD
 BR C404.3 AND A MIXING VALVE ON THE LAVATORY'S DOES NOT
 COMPLY WITH FBC PL 604.3 TEMPERED WATER SHALL BE
 DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3. IF THESE LAVATORY'S ON THIS PROJECT ARE NOT
 PUBLIC THEY DO NOT HAVE TO COMPLY.
  
 12. SHT. P5.1 THE HANDICAP WC IN THE MENS BATHROOM ON
 THE FIRST FLOOR SHALL BE VENTED BY THE LAVATORY
 CONNECTED TO THE WC FIXTURE BRANCH DRAIN. PER FBC PL
 912.1
  
 13. ARE THER ANY STORM DRAIN ON THIS BUILDING OR ARE
 THEY EXISTING PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By aclange Date 2018-01-18 Time 14:52 Rev Time 0.00
Received By aclange Date 2018-01-18 Time 14:52 Sent To  
Notes
2018-01-18 14:53:14LICENSES ARE CURRENT. SENT ONE COPY TO KEN CONRAD.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-12-22 Cont ID  
Sent By jwitmer Date 2017-12-22 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2017-12-22 Time 06:01 Sent To  
Notes
2017-12-22 07:50:472014 FBC- BUILDING/ THRESHOLD BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120042
 ADD: 2410 METROCENTRE BLVD.
 CONT: VERDEX CONSTRUCTION LLC
 TEL: 561-440-1600
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. DEC. 22/ 2017
 ACTION: DENIED
  
 1) THE COVERSHEET LIST THIS BUILDING AS A 4 STORY
 THRESHOLD BUILDING. THRESHOLD BUILDING / FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 1A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN. THE
 ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
 FORMS E-MAILED TO: [email protected] 12/22/2017
 06:48 AM
  
 1C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) COMPLIED. NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS
 ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 1I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  