Plan Review Details - Permit 17111156
Plan Review Stops For Permit 17111156
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-12 Cont ID  
Sent By tklarge Date 2017-12-12 Time 12:15 Rev Time 0.00
Received By tklarge Date 2017-12-12 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-06 Cont ID  
Sent By tklarge Date 2017-12-06 Time 03:36 Rev Time 0.00
Received By tklarge Date 2017-11-30 Time 12:34 Sent To I
Notes
2017-12-01 12:34:22PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-12-12 Cont ID  
Sent By tklarge Date 2017-12-12 Time 12:15 Rev Time 0.00
Received By tklarge Date 2017-12-12 Time 12:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-12-06 Cont ID  
Sent By tklarge Date 2017-12-06 Time 03:36 Rev Time 0.00
Received By tklarge Date 2017-12-06 Time 03:07 Sent To  
Notes
2017-12-06 03:09:311) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LIFT
 STATION. WPB AMEND. TO FBC SEC. 107.2.1. A SEPARATE
 PERMIT WILL BE REQUIRED FOR ANY ELECTRICAL WORK.
 2) THE APPLICATION NOTES WORK TO BE DONE ON A 4 INCH
 SEWER LINE BUT THERE IS NOTHING ON THE SUBMITTED PLANS
 FOR THE REPLACEMENT OF A SEWER LINE. A DRAINAGE OR SOIL
 STACK IS NOT A SEWER LINE.SUBMIT A DRAWING OF THE
 BUILDING FOOTPRINT SHOWING THE LOCATION AND LENGTH OF
 THE BUILDING SEWER TO BE REPLACED IF APPLICABLE. WPB
 AMEND. TO FBC SEC. 107.2.1. NOTE: THE BUILDING SEWER
 BEGINS 30 INCHES OUTSIDE THE EXTERIOR WALL OF THE
 BUILDING.
 3) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE WORK
 TO BE DONE. WPB AMEND. TO FBC SEC. 107.2.1.
 4) A CHECK VALVE AND FULL OPEN VALVE LOCATED ON THE
 DISCHARGE SIDE OF THE CHECK VALVE SHALL INSTALLED IN
 THE PUMP OR EJECTOR DISCHARGE PIPING BETWEEN THE PUMP
 OR EJECTOR AND THE GRAVITY DRAINAGE SYSTEM. VALVES
 SHALL BE ACCESSIBLE.FBC-PLUMBING SEC.712.2.
 5) THE DRAWING SHOWS THE DRAIN DISCHARGING INTO A 4
 INCH VENT. IF THIS IS A VENT STACK, THE DRAIN CANNOT
 DISCHARGE INTO THIS STACK.
 6) THE PERMIT APPLICATION REFERS TO THE INSTALLATION OF
 A WATER LINE. SHOW THIS ON THE PLANS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 7) THE SUBMITTED APPLICATION REFERS TO A 2 INCH SEWER
 LINE BUT THE SUBMITTED PLUMBING DRAWING SHOWS AN 1 1/ 2
 LINE. CLARIFY. SEE COMMENTT #2 FOR EXPLANATION OF
 BUILDING SEWER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  