Plan Review Details - Permit 17111142
Plan Review Stops For Permit 17111142
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2018-12-10 Cont ID  
Sent By rmcdouga Date 2018-12-10 Time 10:21 Rev Time 0.00
Received By rmcdouga Date 2018-12-07 Time 16:11 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2018-11-14 Cont ID  
Sent By rmcdouga Date 2018-11-14 Time 09:21 Rev Time 0.00
Received By rmcdouga Date 2018-11-13 Time 18:58 Sent To I
Notes
2018-11-14 09:21:14PLAN
 REVIEW COMMENTS
 3611 S. FLAGLER DRIVE
 "THE CRYSTAL" 6 UNIT, 7 STOREY R-2 (CONDO)
 AE FLOOD ZONE
  
 5TH REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT ADDRESSED. NEW COMMENTS: THRESHOLD BUILDINGS
 REQUIRE THREE SETS OF CONSTRUCTION DOCUMENTS. ONLY TWO
 SETS OF THE PILE SURVEYS WERE SUBMITTED. THE LETTER
 FROM THE ENGINEER, RONALD M. JEZERINAC P.E., STATES
 THAT THE PILE SURVEYS THAT THEY REVIEWED HAVE HIS SHOP
 DRAWING APPROVAL STAMP. THE ONES THAT WERE SUBMITTED DO
 NOT HAVE SHOP DRAWING REVIEW STAMPS ON THEM.
 -FBC 107.2.1.3 PROVIDE CERTIFICATION DOCUMENTS FROM THE
 THRESHOLD INSPECTOR THAT HAVE BEEN REVIEWED AND
 ACCEPTED BY THE DESIGNER OF RECORD ATTESTING THAT THE
 PRODUCTION PILES AND PILE CAPS HAVE BEEN INSPECTED AND
 ARE INSTALLED PER THE PLANS FROM THE DESIGNER OF
 RECORD.
  
 2) NOT ADDRESSED. NEW COMMENT: THE (3) THRESHOLD
 INPECTION PLANS THAT WERE SUBMITTED HAVE DIGITAL
 SIGNATURES, WHICH ARE ONLY ACCEPTABLE FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
 -FBC 110.3.7 SUBMIT THREE SETS OF A THRESHOLD
 INSPECTION PLAN FROM THE NEW DESIGNER OF RECORD. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURES ARE REQUIRED
 ON PAPER DOCUMENTS PER FAC 61G15-23.003
  
 3) NOT ADDRESSED. NEW COMMENT: I DID NOT SEE TERMITE
 PROTECTION SPECIFIED ON THE PLANS.
 -SHOW COMPLIANCE WITH FBC1816.1 TERMITE PROTECTION.
  
 4) ADDRESSED. I REDLINED SHEET A101 TO REFER TO REVISED
 SHEETS A101 AND S3.1.
 -FBC 107.2.1THERE ARE SOME DISCREPANCIES BETWEEN THE
 ARCHITECTURAL PLANS AND THE STRUCTURAL PLANS THAT NEED
 TO BE ADDRESSED. ON SHEET S3.1 THE OPENING AND STAIRS
 ARE SHOWN ON THE WEST SIDE OF THE FIRE PUMP ROOM. THE
 SITE PLANS AND SHEETS A101 AND A201 SHOW THE DOOR ON
 THE SOUTH END OF THE FIRE PUMP ROOM.
  
 5) NEW COMMENTS: THRESHOLD BUILDINGS REQUIRE THREE (3)
 SETS OF CONSTRUCTION DOCUMENTS TO BE SUBMITTED FOR
 REVIEW. ONLY TWO SETS OF THE GEOTECHNICAL REPORT, THE
 SITE-SPECIFIC FLOOD ZONE ANALYSIS THE LETTERS FROM
 NUTTING ENGINEERS AND JEZERINAC GROUP WERE SUBMITTED.
 FBC 107.1
  
 6) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-10-25 Cont ID  
Sent By rmcdouga Date 2018-10-25 Time 17:32 Rev Time 0.00
Received By rmcdouga Date 2018-10-25 Time 17:32 Sent To I
Notes
2018-10-25 17:14:29PLAN
 REVIEW COMMENTS
 3611 S. FLAGLER DRIVE
 "THE CRYSTAL" 6 UNIT, 7 STOREY R-2 (CONDO)
 AE FLOOD ZONE
  
 4TH REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1.3 PROVIDE CERTIFICATION DOCUMENTS FROM
 THE THRESHOLD INSPECTOR THAT HAVE BEEN REVIEWED AND
 ACCEPTED BY THE DESIGNER OF RECORD ATTESTING THAT THE
 PRODUCTION PILES AND PILE CAPS HAVE BEEN INSPECTED AND
 ARE INSTALLED PER THE PLANS FROM THE DESIGNER OF
 RECORD.
  
 2) FBC 110.3.7 SUBMIT THREE SETS OF A THRESHOLD
 INSPECTION PLAN FROM THE NEW DESIGNER OF RECORD. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURES ARE REQUIRED
 ON PAPER DOCUMENTS PER FAC 61G15-23.003
  
 3) SHOW COMPLIANCE WITH FBC1816.1 TERMITE PROTECTION.
  
 4) FBC 107.2.1THERE ARE SOME DISCREPANCIES BETWEEN THE
 ARCHITECTURAL PLANS AND THE STRUCTURAL PLANS THAT NEED
 TO BE ADDRESSED. ON SHEET S3.1 THE OPENING AND STAIRS
 ARE SHOWN ON THE WEST SIDE OF THE FIRE PUMP ROOM. THE
 SITE PLANS AND SHEETS A101 AND A201 SHOW THE DOOR ON
 THE SOUTH END OF THE FIRE PUMP ROOM.
  
 5) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-05-29 Cont ID  
Sent By rmcdouga Date 2018-05-29 Time 11:37 Rev Time 0.00
Received By rmcdouga Date 2018-05-23 Time 08:04 Sent To  
Notes
2018-05-29 11:37:46PLAN
 REVIEW COMMENTS
 3611 S. FLAGLER DRIVE
 "THE CRYSTAL" 6 UNIT, 7 STOREY R-2 (CONDO)
 AE FLOOD ZONE
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 SEE SAME REVIEW COMMENTS FOR REVISION TO CHANGE PILE
 FOUNDATION SCOPE OF WORK TO INCLUDE BUILDING SHELL
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1.3 PROVIDE CERTIFICATION DOCUMENTS FROM
 THE THRESHOLD INSPECTOR THAT HAVE BEEN REVIEWED AND
 ACCEPTED BY THE DESIGNER OF RECORD ATTESTING THAT THE
 PRODUCTION PILES AND PILE CAPS HAVE BEEN INSPECTED AND
 ARE INSTALLED PER THE PLANS FROM THE DESIGNER OF
 RECORD.
  
 2) ADDRESS THE IMPACT FEE REVIEW COMMENTS. BEFORE A
 PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES MUST BE
 PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE SET OF
 PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM BEACH
 COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH THE
 IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT MUST BE
 RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE THE
 BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 3) FBC 110.3.7 SUBMIT THREE SETS OF A THRESHOLD
 INSPECTION PLAN FROM THE NEW DESIGNER OF RECORD.
  
 4) NOTE: POST TENSION SLABS. 107.3.4.2 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5) FBC 3306.1 PROTECTION REQUIRED. PEDESTRIANS SHALL BE
 PROTECTED DURING CONSTRUCTION, REMODELING AND
 DEMOLITION ACTIVITIES AS REQUIRED BY THIS CHAPTER AND
 TABLE 3306.1. SIGNS SHALL BE PROVIDED TO DIRECT
 PEDESTRIAN TRAFFIC.
 FBC 3306.2 WALKWAYS. A WALKWAY SHALL BE PROVIDED FOR
 PEDESTRIAN TRAVEL IN FRONT OF EVERY CONSTRUCTION AND
 DEMOLITION SITE UNLESS THE APPLICABLE GOVERNING
 AUTHORITY AUTHORIZES THE SIDEWALK TO BE FENCED OR
 CLOSED. WALKWAYS SHALL BE OF SUFFICIENT WIDTH TO
 ACCOMMODATE THE PEDESTRIAN TRAFFIC, BUT IN NO CASE
 SHALL THEY BE LESS THAN 4 FEET (1219 MM) IN WIDTH.
 WALKWAYS SHALL BE PROVIDED WITH A DURABLE WALKING
 SURFACE. WALKWAYS SHALL BE ACCESSIBLE IN ACCORDANCE
 WITH CHAPTER 11 AND SHALL BE DESIGNED TO SUPPORT ALL
 IMPOSED LOADS AND IN NO CASE SHALL THE DESIGN LIVE LOAD
 BE LESS THAN 150 POUNDS PER SQUARE FOOT (PSF) (7.2
 KN/M2).
 FBC 3306.5 BARRIERS. BARRIERS SHALL BE NOT LESS THAN 8
 FEET (2438 MM) IN HEIGHT AND SHALL BE PLACED ON THE
 SIDE OF THE WALKWAY NEAREST THE CONSTRUCTION. BARRIERS
 SHALL EXTEND THE ENTIRE LENGTH OF THE CONSTRUCTION
 SITE. OPENINGS IN SUCH BARRIERS SHALL BE PROTECTED BY
 DOORS WHICH ARE NORMALLY KEPT CLOSED.
 FBC 3306.7 COVERED WALKWAYS. COVERED WALKWAYS SHALL
 HAVE A CLEAR HEIGHT OF NOT LESS THAN 8 FEET (2438 MM)
 AS MEASURED FROM THE FLOOR SURFACE TO THE CANOPY
 OVERHEAD. ADEQUATE LIGHTING SHALL BE PROVIDED AT ALL
 TIMES. COVERED WALKWAYS SHALL BE DESIGNED TO SUPPORT
 ALL IMPOSED LOADS. IN NO CASE SHALL THE DESIGN LIVE
 LOAD BE LESS THAN 150 PSF (7.2 KN/M2) FOR THE ENTIRE
 STRUCTURE.
 FBC 3306.8 REPAIR, MAINTENANCE AND REMOVAL. PEDESTRIAN
 PROTECTION REQUIRED BY THIS CHAPTER SHALL BE MAINTAINED
 IN PLACE AND KEPT IN GOOD ORDER FOR THE ENTIRE LENGTH
 OF TIME PEDESTRIANS ARE SUBJECT TO BEING ENDANGERED.
 THE OWNER OR THE OWNER?S AGENT, UPON THE COMPLETION OF
 THE CONSTRUCTION ACTIVITY, SHALL IMMEDIATELY REMOVE
 WALKWAYS, DEBRIS AND OTHER OBSTRUCTIONS AND LEAVE SUCH
 PUBLIC PROPERTY IN AS GOOD A CONDITION AS IT WAS BEFORE
 SUCH WORK WAS COMMENCED.
  
 6) FBC 3307.1 PROTECTION REQUIRED. ADJOINING PUBLIC AND
 PRIVATE PROPERTY SHALL BE PROTECTED FROM DAMAGE DURING
 CONSTRUCTION, REMODELING AND DEMOLITION WORK.
 PROTECTION SHALL BE PROVIDED FOR FOOTINGS, FOUNDATIONS,
 PARTY WALLS, CHIMNEYS, SKYLIGHTS AND ROOFS. PROVISIONS
 SHALL BE MADE TO CONTROL WATER RUNOFF AND EROSION
 DURING CONSTRUCTION OR DEMOLITION ACTIVITIES. THE
 PERSON MAKING OR CAUSING AN EXCAVATION TO BE MADE SHALL
 PROVIDE WRITTEN NOTICE TO THE OWNERS OF ADJOINING
 BUILDINGS ADVISING THEM THAT THE EXCAVATION IS TO BE
 MADE AND THAT THE ADJOINING BUILDINGS SHOULD BE
 PROTECTED. SAID NOTIFICATION SHALL BE DELIVERED NOT
 LESS THAN 10 DAYS PRIOR TO THE SCHEDULED STARTING DATE
 OF THE EXCAVATION.
  
 7) 3310.1 STAIRWAYS REQUIRED. WHERE A BUILDING HAS BEEN
 CONSTRUCTED TO A BUILDING HEIGHT OF 50 FEET (15 240 MM)
 OR FOUR STORIES, OR WHERE AN EXISTING BUILDING
 EXCEEDING 50 FEET (15 240 MM) IN BUILDING HEIGHT IS
 ALTERED, NO FEWER THAN ONE TEMPORARY LIGHTED STAIRWAY
 SHALL BE PROVIDED UNLESS ONE OR MORE OF THE PERMANENT
 STAIRWAYS ARE ERECTED AS THE CONSTRUCTION PROGRESSES.
  
 8) FBC 107.2.1 THE SLAB ON GRADE NOTE ON SHEET S3.1 IS
 INCOMPLETE.
  
 9) FBC 107.2.1THERE ARE SOME DISCREPANCIES BETWEEN THE
 ARCHITECTURAL PLANS AND THE STRUCTURAL PLANS THAT NEED
 TO BE ADDRESSED.
 A) SPIRAL STAIRS ARE SHOWN ON STRUCTURAL SHEETS S3.1
 AND S3.2 IN THE GROUND FLOOR UNIT. ARCHITECTURAL SHEETS
 A101 AND A201 SHOW A CONVENTIAL STAIRWAY IN THE UNIT
 AND A WATER PUMP ROOM THAT IS NOT SHOWN ON THE
 STRUCTURAL SHEETS.
 B) A WATER FEATURE IS SHOWN ON THE ROOF ON SHEET S3.4
 AND IS NOT SHOWN ON SHEET A701.
  
 10) ADDRESS THE ART IN PUBLIC PLACES COMMENTS. THE CITY
 OF WEST PALM BEACH ART IN PUBLIC PLACES ORDINANCE
 REQUIREMENT THAT APPLIES TO ANY REMODEL OR NEW
 CONSTRUCTION PROJECT FOR WHICH THE PERMIT APPLICATION
 WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL PROJECT
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. FOR
 CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-23 Cont ID  
Sent By aclange Date 2018-03-23 Time 13:43 Rev Time 0.00
Received By aclange Date 2018-03-23 Time 10:59 Sent To  
Notes
2018-03-23 13:38:37****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
 SECOND REVIEW FOUNDATION FOR THE CRYSTAL 17111142
  
 DATE: MARRCH 23,2018
  
 PLAN REVIEW RESPONSES ARE ON TO IN CAPS.
  
 1. OK ADDRESSED
  
 2. OK RECIEVED FLOOD ZONE SITE SPEPCIFIC FLOD ZONE
 ANALYSIS AND ELEVATION CERTIFICATE.
  
 FLOOD ZONE CERTIFICATES
  
 3. PARTIALLY ADDRESSED.
  
 SUBMIT ONLY THE DOCUMENTS REQUIRED FOR A FOUNDATION
 PERMIT. THE ENTIRE SET OF PLANS FOR THE MAIN BUILDING
 HAS BEEN SUBMITTED.
 SEE LIST ADDED BELOW. THIS IS A TYPICAL LIST OF
 REQUIRED ITEMS FOR A FOUNDATION PERMIT FOR YOUR
 REFERENCE.
 PERMIT APPLICATION WHICH STATES SCOPE (FOR FOUNDATION
 PERMIT, TYPICALLY FOOTINGS OR FOOTINGS AND SLAB)
 GEOTECHNICAL REPORT
 SURVEY DRAWING
 STORM WATER POLLUTION PREVENTION PLAN
 SITE PLAN
 1ST FLOOR ARCHITECTURAL PLAN
 ARCHITECTURAL CROSS SECTION(S) OF THE BUILDING
 FOUNDATION PLAN
 FOUNDATION DETAILS AND CROSS SECTIONS
 STRUCTURAL ENGINEER'S GENERAL NOTES
 UNDERGROUND PLUMBING PLAN (IF APPLICABLE)
 ELECTRICAL PLAN SHOWING ANY UNDERGROUND CONDUIT (IF
 APPLICABLE)
 ELECTRICAL GROUNDING TO STEEL DETAIL, IF APPLICABLE (OR
 EXPLAIN WHY THIS IS NOT APPLICABLE FOR THIS PROJECT).
 IF REQUIRED, A DETAIL IS REQUIRED AS A REVIEW, PERMIT,
 AND INSPECTION ARE REQUIRED PRIOR TO CONCRETE POUR
 PLAN SHOWING UNDERGROUND FIRE LINE
 THRESHOLD INSPECTION PLAN OR RESIDENT INSPECTION PLAN
 (AS APPLICABLE)
 SI OR RESIDENT INSPECTOR AGREEMENT (AS APPLICABLE)
 THRESHOLD STATEMENT ON PLAN (IF APPLICABLE)
 THREE SETS OF PLANS FOR RESIDENT INSPECTOR OR THRESHOLD
 PROJECT
  
 PROVIDE ONLY THE INFORMATION REQUIRED FOR A FOUNDATION
 PLAN REVIEW. THE ENTIRE BUILDING PACKAGE WAS SUBMITTED.
 INCLUDE THE ABOVE INFORMATION AS WELL AS ALL STRUCTURAL
 DETAILS AND ELEVATIONS ALONG WITH THE ELECTRICAL AND
 PLUMBING PAGES AS NEEDED.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 4. OK ADDRESSED.
 THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 THRESHOLD BUILDING MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION THAT EXCEEDS
 5,000 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF
 GREATER THAN 500 PERSONS.
  
 4A. OK ADDRESSED
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7). 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 109.3.6.1 THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 4B. OK ADDRESSED
 THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 4C. OK ADDRESSED
 FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 5. OK ADDRESSED
 PLEASE SHOW HOW SLOPE LIMITS WILL BE ACHIEVED. FBC
 3304.1.1 SLOPE LIMITS. SLOPES FOR PERMANENT FILL SHALL
 NOT BE STEEPER THAN ONE UNIT VERTICAL IN TWO UNITS
 HORIZONTAL (50-PERCENT SLOPE). CUT SLOPES FOR PERMANENT
 EXCAVATIONS SHALL NOT BE STEEPER THAN ONE UNIT VERTICAL
 IN TWO UNITS HORIZONTAL (50-PERCENT SLOPE). DEVIATION
 FROM THE FOREGOING LIMITATIONS FOR CUT SLOPES SHALL BE
 PERMITTED ONLY UPON THE PRESENTATION OF A SOIL
 INVESTIGATION REPORT ACCEPTABLE TO THE BUILDING
 OFFICIAL.
  
 6. OK ADDRESSED
 WHEN EXCAVATING WILL THE EXCESS SOILS BE STORED ON
 SITE? FBC 3304.1.2 SURCHARGE. NO FILL OR OTHER
 SURCHARGE LOADS SHALL BE PLACED ADJACENT TO ANY
 BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR STRUCTURE
 IS CAPABLE OF WITHSTANDING THE ADDITIONAL LOADS CAUSED
 BY THE FILL OR SURCHARGE. EXISTING FOOTINGS OR
 FOUNDATIONS WHICH CAN BE AFFECTED BY ANY EXCAVATION
 SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE PROTECTED
 AGAINST SETTLEMENT AND SHALL BE PROTECTED AGAINST LATER
 MOVEMENT.
  
 7. OK ADDRESSED
 PLEASE PROVIDE COMPLIANCE WITH: POLLUTION PREVENTION
 PLAN. FBC 3307.1 PROTECTION REQUIRED. ADJOINING PUBLIC
 AND PRIVATE PROPERTY SHALL BE PROTECTED FROM DAMAGE
 DURING CONSTRUCTION, REMODELING AND DEMOLITION WORK.
 PROVISIONS SHALL BE MADE TO CONTROL WATER RUNOFF AND
 EROSION DURING CONSTRUCTION OR DEMOLITION ACTIVITIES.
 THE PERSON MAKING OR CAUSING AN EXCAVATION TO BE MADE
 SHALL PROVIDE WRITTEN NOTICE TO THE OWNERS OF ADJOINING
 BUILDINGS ADVISING THEM THAT THE EXCAVATION IS TO BE
 MADE AND THAT THE ADJOINING BUILDINGS SHOULD BE
 PROTECTED. SAID NOTIFICATION SHALL BE DELIVERED NOT
 LESS THAN 10 DAYS PRIOR TO THE SCHEDULED STARTING DATE
 OF THE EXCAVATION.
 FBC 109.3.10 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ.
 FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 8. OK ADDRESSED
 FBC 3306.9 ADJACENT TO EXCAVATIONS. EVERY EXCAVATION ON
 A SITE LOCATED 5 FEET (1524 MM) OR LESS FROM THE STREET
 LOT LINE SHALL BE ENCLOSED WITH A BARRIER NOT LESS THAN
 6 FEET (1829 MM) HIGH. WHERE LOCATED MORE THAN 5 FEET
 (1524 MM) FROM THE STREET LOT LINE, A BARRIER SHALL BE
 ERECTED WHEN REQUIRED BY THE BUILDING OFFICIAL.
 BARRIERS SHALL BE OF ADEQUATE STRENGTH TO RESIST WIND
 PRESSURE AS SPECIFIED IN CHAPTER 16.
  
 9. OK ADDRESSED TRAILER PERMIT IN APPLICATION
 ALL CONSTRUCTION TRAILERS (MOBILE OR MODULAR BUILDINGS)
 THAT ARE GOING TO HAVE MEETING IN THEM WILL BE REQUIRED
 TO GET A PERMIT, 102.2(E) MOBILE OR MODULAR STRUCTURES
 USED AS TEMPORARY OFFICES, EXCEPT THAT THE PROVISIONS
 OF PART V FS 553.501-553.513, FLORIDA STATUTES,
 RELATING TO ACCESSIBILITY BY PERSONS WITH DISABILITIES,
 AND PERMITS SHALL BE REQUIRED FOR STRUCTURAL SUPPORT
 AND TIE DOWN, ELECTRICAL SUPPLY, AND ALL UTILITY
 CONNECTIONS TO SUCH MOBILE OR MODULAR STRUCTURES.
  
 10. OK ADDRESSED RECEIVED SOILS REPORT.
 PROVIDE SOILS EXPLORATION REPORT THAT WAS COMPLETED BY
 NUTTING ENGINEERING.
 GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN
 ACCORDANCE WITH FBC SECTION 1803.2 AND REPORTED IN
 ACCORDANCE WITH SECTION 1803.6. WHERE REQUIRED BY THE
 BUILDING OFFICIAL OR WHERE GEOTECHNICAL INVESTIGATIONS
 INVOLVE IN-SITU TESTING, LABORATORY TESTING OR
 ENGINEERING CALCULATIONS, SUCH INVESTIGATIONS SHALL BE
 CONDUCTED BY A REGISTERED DESIGN PROFESSIONAL.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 11. NOT ADDRESSED. SEE IMPACT FEE STOP ADDED.
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 12. OK ADDRESSED
 FBC 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF
 THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDERS OWN RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-05 Cont ID  
Sent By aclange Date 2017-12-05 Time 09:25 Rev Time 0.00
Received By aclange Date 2018-03-23 Time 11:16 Sent To  
Notes
2017-12-05 08:55:39****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
 1ST REVIEW FOUNDATION FOR THE CRYSTAL 17111142
  
 DATE: DECEMBER 5, 2017
  
 1. NOTICE ONLY; THE CITY OF WEST PALM BEACH ART IN
 PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO ANY
 REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE
 PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE
 TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $500,000. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2. FLOOD ZONE CERTIFICATES
  
 FBC 1612 AND CITY OF WPB CODE OF ORDINANCES SECTION
 94-546. STRUCTURE IS LOCATED IN FLOOD ZONE "A". A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 THE FLOOD ZONE MAPS WERE UPDATED OCTOBER 5, 2017.
 PLEASE UPDATE THE SURVEY AND PLANS TO NAV 88.
  
 AFTER OCTOBER 11, 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR 2 FEET OF FREE BOARD ABOVE
 THE DESIGN FLOOD ELEVATION.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
  
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
  
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
  
 3. IT APPEARS THAT THESE PLANS HAVE BEEN SUBMITTED TO
 LOCK INTO THE CURRENT CODE CYCLE. PLEASE UPDATE THE
 PLANS TO REFLECT THE FLOOD ZONE INFORMATION MENTIONED
 ABOVE.
 PROVIDE ONLY THE INFORMATION REQUIRED FOR A FOUNDATION
 PLAN REVIEW. THE ENTIRE BUILDING PACKAGE WAS SUBMITTED.
 INCLUDE THE ABOVE INFORMATION AS WELL AS ALL STRUCTURAL
 DETAILS AND ELEVATIONS ALONG WITH THE ELECTRICAL AND
 PLUMBING PAGES AS NEEDED.
  
 INCLUDE AT WHAT LEVEL THE FOUNDATION BE BUILT TO. WILL
 IT INCLUDE JUST THE SLAB AND SUPPORTING STRUCTURE OR
 WILL COLUMNS BE INCLUDED FOR EXAMPLE.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 4. THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION THAT EXCEEDS
 5,000 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF
 GREATER THAN 500 PERSONS.
  
 4A. THRESHOLD INSPECTION PLAN FL S. S. 553.71(7). 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1 THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 4B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 4C. FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 5. PLEASE SHOW HOW SLOPE LIMITS WILL BE ACHIEVED. FBC
 3304.1.1 SLOPE LIMITS. SLOPES FOR PERMANENT FILL SHALL
 NOT BE STEEPER THAN ONE UNIT VERTICAL IN TWO UNITS
 HORIZONTAL (50-PERCENT SLOPE). CUT SLOPES FOR PERMANENT
 EXCAVATIONS SHALL NOT BE STEEPER THAN ONE UNIT VERTICAL
 IN TWO UNITS HORIZONTAL (50-PERCENT SLOPE). DEVIATION
 FROM THE FOREGOING LIMITATIONS FOR CUT SLOPES SHALL BE
 PERMITTED ONLY UPON THE PRESENTATION OF A SOIL
 INVESTIGATION REPORT ACCEPTABLE TO THE BUILDING
 OFFICIAL.
  
 6. WHEN EXCAVATING WILL THE EXCESS SOILS BE STORED ON
 SITE? FBC 3304.1.2 SURCHARGE. NO FILL OR OTHER
 SURCHARGE LOADS SHALL BE PLACED ADJACENT TO ANY
 BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR STRUCTURE
 IS CAPABLE OF WITHSTANDING THE ADDITIONAL LOADS CAUSED
 BY THE FILL OR SURCHARGE. EXISTING FOOTINGS OR
 FOUNDATIONS WHICH CAN BE AFFECTED BY ANY EXCAVATION
 SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE PROTECTED
 AGAINST SETTLEMENT AND SHALL BE PROTECTED AGAINST LATER
 MOVEMENT.
  
 7. PLEASE PROVIDE COMPLIANCE WITH: POLLUTION PREVENTION
 PLAN. FBC 3307.1 PROTECTION REQUIRED. ADJOINING PUBLIC
 AND PRIVATE PROPERTY SHALL BE PROTECTED FROM DAMAGE
 DURING CONSTRUCTION, REMODELING AND DEMOLITION WORK.
 PROVISIONS SHALL BE MADE TO CONTROL WATER RUNOFF AND
 EROSION DURING CONSTRUCTION OR DEMOLITION ACTIVITIES.
 THE PERSON MAKING OR CAUSING AN EXCAVATION TO BE MADE
 SHALL PROVIDE WRITTEN NOTICE TO THE OWNERS OF ADJOINING
 BUILDINGS ADVISING THEM THAT THE EXCAVATION IS TO BE
 MADE AND THAT THE ADJOINING BUILDINGS SHOULD BE
 PROTECTED. SAID NOTIFICATION SHALL BE DELIVERED NOT
 LESS THAN 10 DAYS PRIOR TO THE SCHEDULED STARTING DATE
 OF THE EXCAVATION.
 FBC 109.3.10 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ.
 FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 8. FBC 3306.9 ADJACENT TO EXCAVATIONS. EVERY EXCAVATION
 ON A SITE LOCATED 5 FEET (1524 MM) OR LESS FROM THE
 STREET LOT LINE SHALL BE ENCLOSED WITH A BARRIER NOT
 LESS THAN 6 FEET (1829 MM) HIGH. WHERE LOCATED MORE
 THAN 5 FEET (1524 MM) FROM THE STREET LOT LINE, A
 BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE BUILDING
 OFFICIAL. BARRIERS SHALL BE OF ADEQUATE STRENGTH TO
 RESIST WIND PRESSURE AS SPECIFIED IN CHAPTER 16.
  
 9. ALL CONSTRUCTION TRAILERS (MOBILE OR MODULAR
 BUILDINGS) THAT ARE GOING TO HAVE MEETING IN THEM WILL
 BE REQUIRED TO GET A PERMIT, 102.2(E) MOBILE OR MODULAR
 STRUCTURES USED AS TEMPORARY OFFICES, EXCEPT THAT THE
 PROVISIONS OF PART V FS 553.501-553.513, FLORIDA
 STATUTES, RELATING TO ACCESSIBILITY BY PERSONS WITH
 DISABILITIES, AND PERMITS SHALL BE REQUIRED FOR
 STRUCTURAL SUPPORT AND TIE DOWN, ELECTRICAL SUPPLY, AND
 ALL UTILITY CONNECTIONS TO SUCH MOBILE OR MODULAR
 STRUCTURES.
  
 10. PROVIDE SOILS EXPLORATION REPORT THAT WAS COMPLETED
 BY NUTTING ENGINEERING.
 GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN
 ACCORDANCE WITH FBC SECTION 1803.2 AND REPORTED IN
 ACCORDANCE WITH SECTION 1803.6. WHERE REQUIRED BY THE
 BUILDING OFFICIAL OR WHERE GEOTECHNICAL INVESTIGATIONS
 INVOLVE IN-SITU TESTING, LABORATORY TESTING OR
 ENGINEERING CALCULATIONS, SUCH INVESTIGATIONS SHALL BE
 CONDUCTED BY A REGISTERED DESIGN PROFESSIONAL.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 11. BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 12. FBC 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL
 OF THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-05-18 Cont ID  
Sent By jpearson Date 2018-05-18 Time 13:27 Rev Time 0.00
Received By jpearson Date 2018-05-18 Time 12:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-02 Cont ID  
Sent By jpearson Date 2018-04-02 Time 14:35 Rev Time 0.00
Received By jpearson Date 2018-04-02 Time 10:47 Sent To  
Notes
2018-04-02 14:34:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 BE ADVISED THIS PLAN REVIEW IS NOT A FULL REVIEW AND IS
 BASED ON ITEMS NECESSARY FOR FOUNDATION PERMIT ONLY.
 THE FULL REVIEW WILL BE COMPLETED UNDER THE MAIN
 PERMIT.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE DETAILS OF THE SECOND POWER SOURCE REQUIRED
 FOR FIRE PUMP. NEC 695.3(B) (NOT PROVIDED. FIRE PUMP
 REQUIRES A RELIABLE POWER SOURCE AND THE CITY DOES NOT
 CONSIDER FPL AS RELIABLE, THEREFORE A GENERATOR OR
 OTHER MEANS OF ALTERNATE POWER IS REQUIRED.)
 2. FEEDER TO THE FIRE PUMP IS NOT PERMITTED TO BE RUN
 THROUGH THE BUILDING. PROVIDE CORRECTION. NEC 695.6,
 695.4(B)(2), 230.79 (NO COMMENT RESPONSE PROVIDED. IF
 THIS FEED IS INSTALLED AS SHOWN CURRENTLY, IT: "SHALL
 BE INSTALLED USING ONE OF THE FOLLOWING METHODS: (1) BE
 ENCASED IN A MINIMUM 50 MM (2 IN.) OF CONCRETE
 (2) BE PROTECTED BY A FIRE-RATED ASSEMBLY LISTED TO
 ACHIEVE A MINIMUM FIRE RATING OF 2 HOURS AND DEDICATED
 TO THE FIRE PUMP CIRCUIT(S)(3) BE A LISTED ELECTRICAL
 CIRCUIT PROTECTIVE SYSTEM WITH A MINIMUM 2-HOUR FIRE
 RATING." NEC 695.6(A)(2) )
 3. IF A DISCONNECT FOR THE FIRE PUMP IS TO BE INSTALLED
 EVEN THOUGH IT IS NOT REQUIRED, IT MUST BE IN A REMOTE
 LOCATION FROM THE SERVICE DISCONNECTS. PROVIDE
 CORRECTION. NEC 695.4(B)(3), 230.72(B) (STILL SHOWN IN
 SAME LOCATION AS MAIN # 1, IT IS ALSO SHOWN WITH 2
 MEANS OF DISCONNECTTHAT ARE NOT FUSED, WHICH IS A CODE
 VIOLATION)
 4. PROVIDE FIRE PUMP SPEC SHEET, DETAILING THE LOCKED
 ROTOR CURRENT OF FIRE PUMP MOTOR. INCLUDE ANY DETAILS
 OF ELECTRICAL LOAD FOR ASSOCIATED EQUIPMENT. NEC 110.3,
 695.10 (NOT PROVIDED)
 5. RISER DIAGRAM SHOWS THE FIRE PUMP CONTROLLER IN THE
 PUMP ROOM. HOWEVER, THE PLUMBING PLAN SHOW THE DOMESTIC
 WATER PUMPS IN THIS ROOM, AND IT APPEARS THAT THE
 CLEARANCES REQUIRED ARE NOT POSSIBLE FOR THIS SIZE
 ROOM. PROVIDE CLARIFICATION. NEC 110.26; FBC 107.2.1
 (NO RESPONSE PROVIDED)
 6. PROVIDE ACCURATE LOAD CALCULATION FOR ENTIRE
 SERVICE. THE LOAD CALCULATION PROVIDED REFERENCES NEC
 220.32, WHICH DOES NOT EXIST. ADDITIONALLY, THE FULL
 HOUSE LOAD IS NOT INCLUDED IN THE CALCULATION. PROVIDE
 CLARIFICATION AND CORRECTIONS. NEC 220 (LOAD
 CALCULATION INCORRECT, ALL LOADS IN HOUSE PANEL NOT
 INCLUDED IN LOAD CALC , NEC 220.32 SHOWN FOR MAIN # 1
 LOAD CALC DOES NOT EXIST, PROVIDE CORRECT CODE
 REFERENCE.)
  
 NEW COMMENTS:
  
 7. COVER SHEET STATES THAT PLAN IS DESIGNED PER THE
 2014 FBC RESIDENTIAL. THE PROVISIONS OF THE FLORIDA
 BUILDING CODE, RESIDENTIAL SHALL APPLY TO THE
 CONSTRUCTION, ALTERATION, MOVEMENT, ENLARGEMENT,
 REPLACEMENT, REPAIR, EQUIPMENT, USE AND OCCUPANCY,
 LOCATION, REMOVAL AND DEMOLITION OF DETACHED ONE- AND
 TWO-FAMILY DWELLINGS AND TOWNHOUSES NOT MORE THAN THREE
 STORIES ABOVE GRADE PLANE IN HEIGHT WITH A SEPARATE
 MEANS OF EGRESS AND THEIR ACCESSORY STRUCTURES NOT MORE
 THAN THREE STORIES ABOVE GRADE PLANE IN HEIGHT. PROVIDE
 CORRECTION. FBC RE R101.2
 8. PLEASE BE ADVISED THAT SOME COMMENT HAV NOT BEEN
 ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF
 IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD
 TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS
 REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-14 Cont ID  
Sent By jpearson Date 2017-12-14 Time 14:07 Rev Time 0.00
Received By jpearson Date 2017-12-14 Time 08:24 Sent To  
Notes
2017-12-14 14:07:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 BE ADVISED THIS PLAN REVIEW IS NOT A FULL REVIEW AND IS
 BASED ON ITEMS NECESSARY FOR FOUNDATION PERMIT ONLY.
 THE FULL REVIEW WILL BE COMPLETED UNDER THE MAIN
 PERMIT.
  
 1. PROVIDE DETAILS OF THE SECOND POWER SOURCE REQUIRED
 FOR FIRE PUMP. NEC 695.3(B)
 2. FEEDER TO THE FIRE PUMP IS NOT PERMITTED TO BE RUN
 THROUGH THE BUILDING. PROVIDE CORRECTION. NEC 695.6,
 695.4(B)(2), 230.79
 3. IF A DISCONNECT FOR THE FIRE PUMP IS TO BE INSTALLED
 EVEN THOUGH IT IS NOT REQUIRED, IT MUST BE IN A REMOTE
 LOCATION FROM THE SERVICE DISCONNECTS. PROVIDE
 CORRECTION. NEC 695.4(B)(3), 230.72(B)
 4. PROVIDE FIRE PUMP SPEC SHEET, DETAILING THE LOCKED
 ROTOR CURRENT OF FIRE PUMP MOTOR. INCLUDE ANY DETAILS
 OF ELECTRICAL LOAD FOR ASSOCIATED EQUIPMENT. NEC 110.3,
 695.10
 5. RISER DIAGRAM SHOWS THE FIRE PUMP CONTROLLER IN THE
 PUMP ROOM. HOWEVER, THE PLUMBING PLAN SHOW THE DOMESTIC
 WATER PUMPS IN THIS ROOM, AND IT APPEARS THAT THE
 CLEARANCES REQUIRED ARE NOT POSSIBLE FOR THIS SIZE
 ROOM. PROVIDE CLARIFICATION. NEC 110.26; FBC 107.2.1
 6. PROVIDE ACCURATE LOAD CALCULATION FOR ENTIRE
 SERVICE. THE LOAD CALCULATION PROVIDED REFERENCES NEC
 220.32, WHICH DOES NOT EXIST. ADDITIONALLY, THE FULL
 HOUSE LOAD IS NOT INCLUDED IN THE CALCULATION. PROVIDE
 CLARIFICATION AND CORRECTIONS. NEC 220
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-04-09 Cont ID  
Sent By mgonzale Date 2018-04-09 Time   Rev Time 1.00
Received By mgonzale Date 2018-04-09 Time   Sent To ENG
Notes
2018-04-09 15:35:00CALL 811 LOCATES
  
 SWPPP SHOULD BE ON-SITE AT ALL TIMES.
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-12-14 Cont ID  
Sent By shill Date 2017-12-14 Time 09:10 Rev Time 0.00
Received By shill Date 2017-12-14 Time 09:10 Sent To  
Notes
2017-12-14 09:11:03CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-28 Cont ID  
Sent By pleduc Date 2018-03-28 Time   Rev Time 0.00
Received By pleduc Date 2018-03-27 Time 16:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-12-07 Cont ID  
Sent By pleduc Date 2017-12-07 Time   Rev Time 0.00
Received By pleduc Date 2017-12-05 Time 11:49 Sent To  
Notes
2017-12-07 09:52:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO CIVIL DRAWINGS OR ANY OTHER DRAWING
 INDICATING THE LOCATION OF A FDC, FIRE HYDRANT OR
 PROPOSED UNDERGROUND FIRE LINE.
  
 ADDITIONALLY, PROVIDE A NOTE INDICATING THAT ALL FIRE
 LINE SHALL BE UNDER SEPARATE SHOP DRAWINGS IN
 COMPLINACE WITH NFPA 24, STANDARD FOR THE INSTALLATION
 OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES,
 2010 EDITION.
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
  
 2) THE ARE NO INDICATIONS OF GRADE SLOPES ON THE ACCESS
 ROAD AND/OR THE PREVIOUSLY DISCUSSED LOCATION OF FIRE
 APPARATUS AT THE WEST END OF THE BUILDING. IT WAS
 DISCUSSED THAT THAT AREA WOULD BE FLAT AND HAVE THE FDC
 AND FIRE HYDRANT LOCATED THERE.(SEE # 1)
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2018-12-10 Cont ID  
Sent By rmcdouga Date 2018-12-10 Time 10:22 Rev Time 0.00
Received By rmcdouga Date 2018-11-29 Time 11:17 Sent To  
Notes
2018-12-03 11:18:07RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-11-14 Cont ID  
Sent By rmcdouga Date 2018-11-14 Time 09:21 Rev Time 0.00
Received By rmcdouga Date 2018-11-07 Time 16:04 Sent To  
Notes
2018-11-08 16:04:47RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-10-25 Cont ID  
Sent By rmcdouga Date 2018-10-25 Time 17:32 Rev Time 0.00
Received By rmcdouga Date 2018-10-17 Time 14:04 Sent To  
Notes
2018-10-19 14:04:21RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-04 Cont ID  
Sent By gjohnson Date 2018-06-04 Time 13:47 Rev Time 0.00
Received By gjohnson Date 2018-04-30 Time 15:09 Sent To  
Notes
2018-05-01 15:10:07C02

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-18 Cont ID  
Sent By shill Date 2018-04-18 Time 16:15 Rev Time 0.00
Received By shill Date 2018-03-21 Time 14:45 Sent To  
Notes
2018-03-22 14:45:34C02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-29 Cont ID  
Sent By cpuell Date 2017-12-29 Time 12:43 Rev Time 0.00
Received By cpuell Date 2017-11-30 Time 13:45 Sent To  
Notes
2017-12-01 13:45:59C02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-12-12 Cont ID  
Sent By rmcdouga Date 2018-12-12 Time 15:11 Rev Time 0.00
Received By rmcdouga Date 2018-12-12 Time 15:11 Sent To  
Notes
2018-12-12 15:18:37MU-2018-16270, PAID $7984.78

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-03-23 Cont ID  
Sent By aclange Date 2018-03-23 Time 12:50 Rev Time 0.00
Received By aclange Date 2018-03-23 Time 12:49 Sent To  
Notes
2018-03-23 12:53:35ART LANGE BUILDING PLANS EXAMINER
 561-805-6667 [email protected]
  
  
 PROVIDE AN APPROVAL FROM PALM BEACH COUNTY IMPACT FEE
 OFFICE IF YOU WANT TO DEFER PAYING IMPACT FEES UNTILL
 THE MAIN BUILDING PERMIT IS ISSUED. PROVIDE THIS
 INFORMATION TO OUR OFFICE PRIOR TO ISSUANCE OF THE
 FOUNDATION PERMIT.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-04 Cont ID  
Sent By aclange Date 2017-12-04 Time 14:02 Rev Time 0.00
Received By rmcdouga Date 2017-12-04 Time 14:02 Sent To P
Notes
2017-12-04 14:03:13ART LANGE BUILDING PLANS EXAMINER
 561-805-6667 [email protected]
  
  
  
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status P Date 2018-12-10 Cont ID  
Sent By rmcdouga Date 2018-12-10 Time 17:34 Rev Time 0.00
Received By rmcdouga Date 2018-12-10 Time 17:34 Sent To  
Notes
2018-12-10 17:38:41BUILDING PROVISO
  
 1) SOME OF THE PLANS SHOW THE FINISH FLOOR ELEVATION AT
 0 FEET. SUBMIT REVISED PLANS TO SHOW THE FINISH FLOOR
 ELEVATION AT A MINIMUM OF 9 FEET NAVD AND NOT 0 FEET.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2018-04-18 Cont ID  
Sent By shill Date 2018-04-18 Time 16:08 Rev Time 0.00
Received By shill Date 2018-04-18 Time 16:08 Sent To  
Notes
2018-04-18 16:08:49****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 A SITE PLAN SHOWS PROPOSED FFE AT 9' NAVD88.
  
 THE ARCHITECTURAL PAGES SHOW FFE AT 0'0". PLEASE
 INCORPORATE THE PROPOSED FFE INTO THE ARCHITECTURAL OR
 STRUCTURAL DRAWINGS. THIS IS NOT A REQUIREMENT FOR THE
 FOUNDATION PERMIT, BUT WILL BE A REQUIREMENT FOR THE
 BUILDING PERMIT.
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By aclange Date 2018-03-23 Time 13:45 Rev Time 0.00
Received By aclange Date 2018-03-23 Time 11:08 Sent To  
Notes
2018-03-23 11:16:18SITE SPECIFIC FLOOD ZONE ANALYSIS REPORT HAS BEEN
 RECEIVED.
 THESE DESIGN FLOOD ELEVATION INCLUDING THE 2 FT.
 FREEBOARD IS 9.0 NAVD.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2017-12-14 Cont ID  
Sent By shill Date 2017-12-14 Time 09:11 Rev Time 0.00
Received By shill Date 2017-12-14 Time 09:11 Sent To  
Notes
2017-12-14 09:11:48SEE BUILDING REVIEW
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-06-04 Cont ID  
Sent By gjohnson Date 2018-06-04 Time 13:45 Rev Time 0.00
Received By gjohnson Date 2018-06-04 Time 08:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-04-10 Cont ID  
Sent By gjohnson Date 2018-04-10 Time 08:52 Rev Time 0.00
Received By gjohnson Date 2018-04-10 Time 06:46 Sent To  
Notes
2018-04-10 09:01:152ND REVIEW: FBC 2014 5TH EDITION
  
  
 PREVIOUS COMMENTS NOT ADDRESSED THEY CAN BE ADDRESSED
 UNDER THE MAIN PERMIT IF REFERENCED SHEETS ARE REMOVED
 AND THE FOLLOWING IS PROVIDED .
 1. PROVIDE ISOMETRIC WITH UNDERGROUND PIPING ONLY FOR
 SANITARY, WATER AND STORM SHOWING DFU, PIPE SIZE AND
 SQFT FOR STORM DRAINS. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
 2. PROVIDE FLOOR PLAN WITH UNDER GROUND PIPING ONLY.
 PER WPB AMEND TO FBC 107.2.1
  
 PLUMBING COMMENTS: TO EXPEDITE APPROVAL OF THIS PERMIT
 I SUGGEST SCHEDULING A MEETING TO GO OVER COMMENTS SEE
 MY CONTACT INFO BELOW.
  
 1. THIS BUILDING SHALL COMPLY WITH FHA. PER FAIR
 HOUSING ACCESSIBILITY GUIDELINES : SECTION 3. FAIR
 HOUSING ACT DESIGN AND CONSTRUCTION REQUIREMENTS
  
 THE REGULATIONS ISSUED BY THE DEPARTMENT AT 24 CFR
 100/205 STATE:
  
 SECTION 100.205 DESIGN AND CONSTRUCTION REQUIREMENTS.
 (A) COVERED MULTIFAMILY DWELLINGS FOR FIRST OCCUPANCY
 AFTER MARCH 13, 1991, SHALL BE DESIGNED AND CONSTRUCTED
 TO HAVE AT LEAST ONE BUILDING ENTRANCE ON AN ACCESSIBLE
 ROUTE UNLESS IT IS IMPRACTICAL TO DO SO BECAUSE OF THE
 SITE. FOR PURPOSES OF THIS SECTION, A COVERED
 MULTIFAMILY DWELLING SHALL BE DEEMED TO BE DESIGNED AND
 CONSTRUCTED FOR FIRST OCCUPANCY ON OR BEFORE MARCH 13,
 1991, IF THEY ARE OCCUPIED BY THAT DATE OR IF THE LAST
 BUILDING PERMIT OR RENEWAL THEREOF FOR THE COVERED
 MULTIFAMILY DWELLINGS IS ISSUED BY A STATE, COUNTY OR
 LOCAL GOVERNMENT ON OR BEFORE JANUARY 13, 1990. THE
 BURDEN OF ESTABLISHING IMPRACTICALITY BECAUSE OF
 TERRAIN OR UNUSUAL SITE CHARACTERISTICS IS ON THE
 PERSON OR PERSONS WHO DESIGNED OR CONSTRUCTED THE
 HOUSING FACILITY.
  
 A) INDICATE ON THE PLAN WHICH FHA DESIGN DOCUMENT WILL
 BE USED IN DESIGNING BUILDING TO MEET FHA REQUIREMENTS.
 PER WPB AMEND TO FBC 107.2.1
 B) INDICATE ON THE PLAN HOW FHA REQUIREMENTS 1-5 WILL
 BE MET.
 C) SHOW ON THE PLANS THE DIMENSIONS OF THE MOUNTING
 HEIGHTS FOR THE GRAB BAR BACKING. PER FHA REQUIREMENT 6
 D) INDICATE ON THE PLAN WHICH DESIGN SPEC WILL BE USED
 FOR THE BATHROOMS. PER FHA REQUIREMENT 7
 E) SHOW ON THE PLAN THE CLEAR FLOOR SPACE REQUIRED AT
 THE FIXTURES IN THE BATHROOMS AND KITCHEN. PER FHA
 REQUIREMENT 7
 F) SHOW ON THE PLANS THE DIMENSIONS FOR THE HEIGHT AND
 DEPTH OF THE VANITY OR WING WALL ADJACENT TO THE WATER
 CLOSET. PER FHA REQUIREMENT 7
  
 2. PLEASE INDICATE ON THE PLAN FOR FOUNDATION ONLY. PER
 WPB AMEND TO FBC 107.2.1
  
 3. SHT. A701 SHOW THE SQFT AT EACH ROOF DRAIN. PER WPB
 AMEND TO FBC 107.2.1 AND FBC PL CH 11
  
 4. ON SHT. P-1 AND P-5 IT SHOWS 685 SQFT ON 3 OF THE
 ROOF DRAINS ON SHT A701 IT SHOWS THOSE SAME ROOF AREAS
 AS 3 DIFFERENT SIZES PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 5. SHT. P-1 PLEASE PLACE NOTE ON PLAN A SEPARATE PERMIT
 IS REQUIRED FOR BACKFLOW DEVICES. PER WPB UTILITIES
 DEPARTMENT
  
 6. SHT. P-6 SHOW SIZE ON THE BRANCH'S ON WATER MAIN
 RISER. PER WPB AMEND TO FBC 107.2.1
  
 7.SHT. P-1 SHOWS THE HOT AND COLD WATER PIPING TO THE
 WATER HEATER ON THE GROUND FLOOR AS 1/2" THE ISOMETRIC
 SHOWS IT AT 3/4" PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 8. PLEASE LABEL ALL ALL WASTE AND SOIL STACKS ON
 ISOMETRICS , RISERS AND FLOOR PLANS. PER WPB AMEND TO
 FBC 107.2.1
  
 9. SHT. P-7 SHOW BRANCH'S AND SIZE OF BRANCH ON THE
 RISERS. PER WPB AMEND TO FBC 107.2.1
  
 10. SHT. P-8 SHOWS 2 ROUND ROOF DRAINS FOR OBSERVATION
 DECK SHT. A701 SHOWS 3 LINEAR FLOOR DRAINS ON THE
 OBSERVATION DECK PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 11. LABEL STORM RISER TO MATCH THE FLOOR PLAN. PER WPB
 AMEND TO FBC 107.2.1
  
 12. PLEASE SHOW PUMP AND DRAIN PIPING FOR ELEVATOR
 SUMP. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-12-20 Cont ID  
Sent By gjohnson Date 2017-12-20 Time 07:36 Rev Time 0.00
Received By gjohnson Date 2017-12-20 Time 06:18 Sent To  
Notes
2017-12-20 08:35:081ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: TO EXPEDITE APPROVAL OF THIS PERMIT
 I SUGGEST SCHEDULING A MEETING TO GO OVER COMMENTS SEE
 MY CONTACT INFO BELOW.
  
 1. THIS BUILDING SHALL COMPLY WITH FHA. PER FAIR
 HOUSING ACCESSIBILITY GUIDELINES : SECTION 3. FAIR
 HOUSING ACT DESIGN AND CONSTRUCTION REQUIREMENTS
  
 THE REGULATIONS ISSUED BY THE DEPARTMENT AT 24 CFR
 100/205 STATE:
  
 SECTION 100.205 DESIGN AND CONSTRUCTION REQUIREMENTS.
 (A) COVERED MULTIFAMILY DWELLINGS FOR FIRST OCCUPANCY
 AFTER MARCH 13, 1991, SHALL BE DESIGNED AND CONSTRUCTED
 TO HAVE AT LEAST ONE BUILDING ENTRANCE ON AN ACCESSIBLE
 ROUTE UNLESS IT IS IMPRACTICAL TO DO SO BECAUSE OF THE
 SITE. FOR PURPOSES OF THIS SECTION, A COVERED
 MULTIFAMILY DWELLING SHALL BE DEEMED TO BE DESIGNED AND
 CONSTRUCTED FOR FIRST OCCUPANCY ON OR BEFORE MARCH 13,
 1991, IF THEY ARE OCCUPIED BY THAT DATE OR IF THE LAST
 BUILDING PERMIT OR RENEWAL THEREOF FOR THE COVERED
 MULTIFAMILY DWELLINGS IS ISSUED BY A STATE, COUNTY OR
 LOCAL GOVERNMENT ON OR BEFORE JANUARY 13, 1990. THE
 BURDEN OF ESTABLISHING IMPRACTICALITY BECAUSE OF
 TERRAIN OR UNUSUAL SITE CHARACTERISTICS IS ON THE
 PERSON OR PERSONS WHO DESIGNED OR CONSTRUCTED THE
 HOUSING FACILITY.
  
 A) INDICATE ON THE PLAN WHICH FHA DESIGN DOCUMENT WILL
 BE USED IN DESIGNING BUILDING TO MEET FHA REQUIREMENTS.
 PER WPB AMEND TO FBC 107.2.1
 B) INDICATE ON THE PLAN HOW FHA REQUIREMENTS 1-5 WILL
 BE MET.
 C) SHOW ON THE PLANS THE DIMENSIONS OF THE MOUNTING
 HEIGHTS FOR THE GRAB BAR BACKING. PER FHA REQUIREMENT 6
 D) INDICATE ON THE PLAN WHICH DESIGN SPEC WILL BE USED
 FOR THE BATHROOMS. PER FHA REQUIREMENT 7
 E) SHOW ON THE PLAN THE CLEAR FLOOR SPACE REQUIRED AT
 THE FIXTURES IN THE BATHROOMS AND KITCHEN. PER FHA
 REQUIREMENT 7
 F) SHOW ON THE PLANS THE DIMENSIONS FOR THE HEIGHT AND
 DEPTH OF THE VANITY OR WING WALL ADJACENT TO THE WATER
 CLOSET. PER FHA REQUIREMENT 7
  
 2. PLEASE INDICATE ON THE PLAN FOR FOUNDATION ONLY. PER
 WPB AMEND TO FBC 107.2.1
  
 3. SHT. A701 SHOW THE SQFT AT EACH ROOF DRAIN. PER WPB
 AMEND TO FBC 107.2.1 AND FBC PL CH 11
  
 4. ON SHT. P-1 AND P-5 IT SHOWS 685 SQFT ON 3 OF THE
 ROOF DRAINS ON SHT A701 IT SHOWS THOSE SAME ROOF AREAS
 AS 3 DIFFERENT SIZES PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 5. SHT. P-1 PLEASE PLACE NOTE ON PLAN A SEPARATE PERMIT
 IS REQUIRED FOR BACKFLOW DEVICES. PER WPB UTILITIES
 DEPARTMENT
  
 6. SHT. P-6 SHOW SIZE ON THE BRANCH'S ON WATER MAIN
 RISER. PER WPB AMEND TO FBC 107.2.1
  
 7.SHT. P-1 SHOWS THE HOT AND COLD WATER PIPING TO THE
 WATER HEATER ON THE GROUND FLOOR AS 1/2" THE ISOMETRIC
 SHOWS IT AT 3/4" PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 8. PLEASE LABEL ALL ALL WASTE AND SOIL STACKS ON
 ISOMETRICS , RISERS AND FLOOR PLANS. PER WPB AMEND TO
 FBC 107.2.1
  
 9. SHT. P-7 SHOW BRANCH'S AND SIZE OF BRANCH ON THE
 RISERS. PER WPB AMEND TO FBC 107.2.1
  
 10. SHT. P-8 SHOWS 2 ROUND ROOF DRAINS FOR OBSERVATION
 DECK SHT. A701 SHOWS 3 LINEAR FLOOR DRAINS ON THE
 OBSERVATION DECK PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 11. LABEL STORM RISER TO MATCH THE FLOOR PLAN. PER WPB
 AMEND TO FBC 107.2.1
  
 12. PLEASE SHOW PUMP AND DRAIN PIPING FOR ELEVATOR
 SUMP. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By aclange Date 2018-03-23 Time 11:00 Rev Time 0.00
Received By aclange Date 2018-03-23 Time 11:00 Sent To  
Notes
2018-03-23 11:02:34NUTTING ENGINEERS HAVE BEEN APPROVED WITH 18030237 AND
 WILL BE THE THRESHOLD INSPECTION COMPANY ON THE ENTIRE
 PROJECT. THRESHOLD/SI AGREEMENT PROVIDED TO KEN CONRAD
 AND RICHARD GATHRIGHT.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-12-04 Cont ID  
Sent By aclange Date 2017-12-04 Time 13:58 Rev Time 0.00
Received By aclange Date 2017-12-04 Time 13:58 Sent To  
Notes
2017-12-04 14:00:42ART LANGE BUILDING PLANS EXAMINER
 561-805-6667 [email protected]
  
  
 SEE BUILDING REVIEW FOR THRESHOLD COMMENTS.
  
  
  
  

Review Stop Z ZONING
Rev No 5 Status P Date 2018-12-05 Cont ID  
Sent By llouie Date 2018-12-05 Time   Rev Time 0.00
Received By llouie Date 2018-12-05 Time   Sent To B
Notes
2018-12-05 11:33:24* FOUNDATION PERMIT ONLY.
 * REFERENCE: FSPR 16-03A.

Review Stop Z ZONING
Rev No 4 Status P Date 2018-10-24 Cont ID  
Sent By llouie Date 2018-10-24 Time   Rev Time 0.00
Received By llouie Date 2018-10-24 Time   Sent To B
Notes
2018-10-24 10:20:19REFERENCE: FSPR 16-03A
  

Review Stop Z ZONING
Rev No 3 Status F Date 2018-05-31 Cont ID  
Sent By llouie Date 2018-05-31 Time   Rev Time 0.00
Received By llouie Date 2018-05-31 Time   Sent To  
Notes
2018-05-31 10:21:37** FAILED **
  
 REQUIRES A MINOR AMENDMENT TO THE APPROVED SITE PLAN.
 (NOTE: APPLICATION FOR A SITE PLAN AMENDMENT RECEIVED
 BY THE PLANNING DIVISION; SCHEDULED FOR THE 6/13 PPRC
 MEETING.).
  
 CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status F Date 2018-04-18 Cont ID  
Sent By llouie Date 2018-04-18 Time   Rev Time 0.00
Received By llouie Date 2018-04-18 Time   Sent To  
Notes
2018-04-18 15:49:22** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE PERMIT DESCRIPTION SPECIFIES THAT THE PROPOSED
 SCOPE OF WORK IS FOR THE BUILDING FOUNDATION ONLY;
 HOWEVER, ARCHITECTURAL, ELECTRICAL, PLUMBING PLANS,
 ETC., HAVE BEEN INCLUDED IN THE PERMIT SET. ONLY THE
 PLANS THAT ARE PERTINENT TO THE SCOPE OF WORK SHOULD BE
 INCLUDED IN THE PERMIT SET TO AVOID CONFUSION.
 [12/29/17 COMMENT NOT ADDRESSED]
  
 2.) CHANGES DETECTED IN THE PERMIT PLANS THAT DO NOT
 MATCH THE APPROVED SITE PLAN WHICH MAY IMPACT THE
 FOOTPRINT OF THE FOUNDATION. PLEASE NOTE THAT AN
 AMENDMENT TO THE APPROVED SITE PLAN MUST BE APPROVED BY
 THE PLANNING DIVISION PRIOR TO THE APPROVAL OF THIS
 PERMIT.
  
  
 NOTES:
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * THE PLANS (I.E. SETBACKS AND ELEVATIONS) DO NOT MATCH
 THE APPROVED PLANS FOR THE PROJECT (REFERENCE: FSPR
 16-03). PLEASE NOTE THAT AN AMENDMENT TO THE APPROVED
 PLANS WILL BE REQUIRED IF THE PLANS (I.E. SITE PLAN,
 ARCHITECTURAL PLANS, ETC.) DO NOT MATCH WHAT HAS BEEN
 APPROVED BY STAFF.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: MF32
  
 * REFERENCE: FSPR 16-03
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-12-29 Cont ID  
Sent By LL Date 2017-12-29 Time   Rev Time 0.00
Received By llouie Date 2017-12-21 Time 10:01 Sent To  
Notes
2017-12-29 12:01:09** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE PERMIT DESCRIPTION SPECIFIES THAT THE PROPOSED
 SCOPE OF WORK IS FOR THE BUILDING FOUNDATION ONLY;
 HOWEVER, ARCHITECTURAL, ELECTRICAL, PLUMBING PLANS,
 ETC., HAVE BEEN INCLUDED IN THE PERMIT SET. ONLY THE
 PLANS THAT ARE PERTINENT TO THE SCOPE OF WORK SHOULD BE
 INCLUDED IN THE PERMIT SET TO AVOID CONFUSION.
  
 2.) PROVIDE THE DIMENSION TO THE OVERALL HEIGHT OF THE
 BUILDING (TO THE HIGHEST POINT). THE HEIGHT OF THE
 BUILDING IS CONTINGENT ON THE SETBACKS OF THE BUILDING.
  
 3.) THE PLANS (I.E. SETBACKS AND ELEVATIONS) DO NOT
 MATCH THE APPROVED PLANS FOR THE PROJECT (REFERENCE:
 FSPR 16-03). PLEASE NOTE THAT AN AMENDMENT TO THE
 APPROVED PLANS WILL BE REQUIRED IF THE PLANS (I.E. SITE
 PLAN, ARCHITECTURAL PLANS, ETC.) DO NOT MATCH WHAT HAS
 BEEN APPROVED BY STAFF.
  
  
 NOTES:
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: MF32
  
 * REFERENCE: FSPR 16-03
  


Account Summary | Usage Policy | Privacy Policy