Plan Review Details - Permit 17111083
Plan Review Stops For Permit 17111083
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-01-25 Cont ID  
Sent By tklarge Date 2018-01-25 Time 05:15 Rev Time 0.00
Received By tklarge Date 2018-01-25 Time 05:03 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-12-18 Cont ID  
Sent By tklarge Date 2017-12-18 Time 06:51 Rev Time 0.00
Received By tklarge Date 2017-12-18 Time 06:51 Sent To  
Notes
2017-12-18 06:52:001) CITY RECORDS SHOW A PREVIOUS GAS PERMIT FOR THE
 INSTALLATION OF A GAS POOL HEATER. THE BTU LOAD OF THE
 EXISTING POOL HEATER SHALL BE ADDED TO THE TOTAL BTU
 LOAD OF THE SYSTEM AND THE POOL HEATER SHALL BE SHOWN
 ON THE GAS RISER DIAGRAM WITH ALL EXISTING PIPE SIZES.
 FBC-FUEL GAS SEC. 401.4.
 2) THE DESCRIPTION OF WORK ON THE GAS PERMIT
 APPLICATION REFERS TO CONNECTION TO AN EXISTING NATURAL
 GAS METER YET THE GAS RISER NOTES A NEW 2 LB. METER.
 REVISE THE DESCRIPTION OF WORK TO SHOW A NEW GAS
 METER.WPB AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATOR FOR THE GENERATOR. THE REGULATOR
 SHALL COMPLY WITH FBC-FUEL GAS SEC.410.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-25 Cont ID  
Sent By tklarge Date 2018-01-25 Time 05:15 Rev Time 0.00
Received By tklarge Date 2018-01-25 Time 05:02 Sent To I
Notes
***NONE***