Plan Review Details - Permit 17110858
Plan Review Stops For Permit 17110858
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By aclange Date 2018-01-18 Time 07:51 Rev Time 0.00
Received By aclange Date 2018-01-17 Time 14:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-05 Cont ID  
Sent By aclange Date 2017-12-05 Time 13:02 Rev Time 0.00
Received By aclange Date 2017-12-05 Time 10:31 Sent To  
Notes
2017-12-05 13:02:42****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. DOOR #200 DOES NOT HAVE 12 INCHES CLEAR ON THE PUSH
 / LATCH SIDE.
  
 ACCESSIBILITY 404.2.4.1 (C) MANEUVERING CLEARANCES. SEE
 DETAIL C.
  
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 2. PROVIDE A PRODUCT APPROVAL FOR STOREFRONT DOOR
 #207A.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 3. ON PAGE A.2.1.1 PLEASE UPDATE DOOR HARDWARE NOTE #2
 TO THE 2014 FBC.
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-02-02 Cont ID  
Sent By jpearson Date 2018-02-02 Time 15:46 Rev Time 0.00
Received By jpearson Date 2018-02-02 Time 15:46 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-21 Cont ID  
Sent By jpearson Date 2017-12-21 Time 16:18 Rev Time 0.00
Received By jpearson Date 2017-12-21 Time 16:18 Sent To  
Notes
2017-12-21 16:18:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN DOES NOT PROVIDE LOCATION OF WORK AT ADDRESS
 STATED. WHICH FLOOR WILL THIS WORK BE ON? SUITE
 NUMBERS? PLEASE CLARIFY ADDRESS ON PLAN. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-01-17 Cont ID  
Sent By pleduc Date 2018-01-17 Time   Rev Time 0.00
Received By pleduc Date 2018-01-16 Time 14:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-27 Cont ID  
Sent By pleduc Date 2017-11-27 Time   Rev Time 0.00
Received By pleduc Date 2017-11-27 Time 09:47 Sent To  
Notes
2017-11-27 12:14:58THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEETS ALS 1.1 AND E 0.1 - ALL FIRE ALARM WORK SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-02-02 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-10 Time 10:17 Sent To  
Notes
2018-01-12 10:19:44C12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-28 Cont ID  
Sent By gjohnson Date 2017-12-28 Time 11:37 Rev Time 0.00
Received By gjohnson Date 2017-11-20 Time 13:43 Sent To  
Notes
2017-11-21 13:43:31C10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-01-29 Cont ID  
Sent By ccole Date 2018-01-29 Time 17:56 Rev Time 0.00
Received By ccole Date 2018-01-29 Time 17:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-19 Cont ID  
Sent By ccole Date 2017-12-19 Time 14:29 Rev Time 0.00
Received By ccole Date 2017-12-19 Time 14:26 Sent To  
Notes
2017-12-19 14:39:461ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110858
 12/19/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: THE CORRIDOR SHALL NOT BE USED TO RETURN
 AIR TO THE MECHANICAL ROOM- SECTION 601.2.
  
 2) M2.1: SHOW THE RETURN AIR OPENING INTO THE
 MECHANICAL ROOM, AND SHOW THE REQUIRED SMOKE
 DETECTOR(S) IN THE ROOM PER SECTION 606.2.2.
  
 3) M2.1: SHOW HOW OUTSIDE AIR IS BEING PROVIDED TO THE
 ROOMS AND SPACES AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS- SECTION 403.
  
 4) M2.1: PROVIDE THE FLEX DUCT SIZES.
  
 5) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 HEAT PUMP- C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-12-28 Cont ID  
Sent By gjohnson Date 2017-12-28 Time 11:32 Rev Time 0.00
Received By gjohnson Date 2017-12-28 Time 11:03 Sent To  
Notes
***NONE***