Plan Review Stops For Permit 17110857 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2018-03-06 |
|
|
Cont ID |
|
Sent By |
aclange |
Date |
2018-03-06 |
Time |
10:23 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2018-03-06 |
Time |
10:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2017-12-13 |
|
|
Cont ID |
|
Sent By |
aclange |
Date |
2017-12-13 |
Time |
12:56 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2017-12-13 |
Time |
12:56 |
Sent To |
|
|
Notes |
2017-12-13 12:58:42 | PLANS SUBMITTED ARE SHOWN AS 185 BANYAN. COMMUNITY PLUS | | HAS THE ADDRESS AS 201 N FLAGLER DR. | | | | ADDRESSING: | | CITY MUNI CODE SEC.78-6 (1-7) | | | | (2) LOCATION, BUILDINGS CONTAINING MORE THAN ONE | | ADDRESS. ALL ADDRESSES SHALL BE POSTED ON THAT PORTION | | OF THE STRUCTURE FRONTING OR FACING UPON THE STREET OR | | PRINCIPAL VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE | | READILY VISIBLE TO APPROACHING VEHICLES. OWNERS OR | | TENANTS OF ALL HOUSES AND BUILDINGS USING A SERVICE | | ALLEY SHALL ALSO POST A NUMBER ON THE SIDE OF THE | | BUILDINGS ADJACENT TO AND FACING SUCH ALLEY. IF THE | | HOUSE OR BUILDING IS OBSTRUCTED BY A FENCE, THEN THE | | NUMBER SHALL BE POSTED ON THE FENCE. THE PLACEMENT OF | | NUMBERS ON BUILDINGS OR FENCES, AS THE CASE MAY BE, | | SHALL BE SUBJECT TO THE DIRECTION OR APPROVAL OF THE | | CITY'S CONSTRUCTION SERVICES DEPARTMENT. BUILDINGS | | WHICH CONTAIN MORE THAN ONE RESIDENTIAL, COMMERCIAL, | | INDUSTRIAL, OR INSTITUTIONAL ADDRESS SHALL POST A | | SEPARATE ADDRESS MEETING THE REQUIREMENTS OF THIS | | SECTION AT THE EXTERIOR ENTRANCE TO EACH INDIVIDUAL | | ADDRESS OR COMMON EXTERIOR ENTRANCE TO SEVERAL | | ADDRESSES THEREIN, AND THE UNIT NUMBER SHALL ALSO BE | | POSTED ON THE EXTERIOR DOOR OF EACH UNIT SERVED BY SUCH | | A COMMON EXTERIOR ENTRANCE. | | | | | | CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/ | | INFORMATION TECHNOLOGY | | TEL: 561-494-1040 | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-05-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-05-27 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-05-27 |
Time |
15:28 |
Sent To |
|
|
Notes |
2018-05-27 16:05:14 | ****PROVISOS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | A. THIS PARCEL IS LOCATED IN A SPECIAL FLOOD HAZARD | | AREA; FLOOD MAP IN EFFECT AT TIME OF FOUNDATION PERMIT | | APPLICATION 1979 FIRMS + 1' FREEBOARD; MINIMUM | | ELEVATION = 8.0' NGVD29, PROPOSED LOWEST FINISHED FLOOR | | ELEVATION = 9.0' NGVD29 | | A "CONSTRUCTION DRAWING" ELEVATION CERTIFICATE IS | | RECOMMENDED AT THIS TIME TO AVOID FUTURE DELAYS | | (CORRECTIONS, IF APPLICABLE, WILL NOT DELAY PERMIT | | ISSUANCE) | | A "BUILDING UNDER CONSTRUCTION" ELEVATION CERTIFICATE | | OR FORM BOARD SURVEY IS REQUIRED PRIOR TO CONCRETE | | POUR. THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW | | A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE IS | | REQUIRED PRIOR TO FINAL INSPECTION AND/OR CO AND/OR | | TCO. | | | | B. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE | | FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS | | SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF | | RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR | | PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS, | | STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS | | REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW | | AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION. | | | | COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH | | PRESSURES SHOWN ON SHEET S0.0.5) | | | | C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE | | REQUIRED FOR: | | LIGHT POLES/SITE LIGHTING | | FIRE ALARM | | FIRE SPRINKLER | | LOW VOLTAGE | | ACCESS | | LANDSCAPING | | IRRIGATION | | ALL OTHER ITEMS OTHER THAN BMEP | | | | D. PROVIDE THE RECORDED PLAT WHEN FINALIZED; EITHER A | | PDF VIA EMAIL OR ADVISE BOOK AND PAGE NUMBER VIA EMAIL. | | | | E. AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED | | PRIOR TO C.O. | | | | F. SHORING/RESHORE ENGINEERING IS REQUIRED TO BE | | SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. THE | | ENGINEERING IS TO BE SUBMITTED, REVIEWED AND ISSUED | | PRIOR TO CONCRETE POUR. | | | | G. A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS | | REQUIRED TO BE PROVIDED PRIOR TO INSTALLATION. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2018-03-07 |
|
|
Cont ID |
|
Sent By |
aclange |
Date |
2018-03-06 |
Time |
11:44 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2018-03-06 |
Time |
08:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2017-12-13 |
|
|
Cont ID |
|
Sent By |
aclange |
Date |
2017-12-13 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2017-12-12 |
Time |
09:16 |
Sent To |
|
|
Notes |
2017-12-13 13:05:34 | ****PLAN REVIEW COMMENTS**** | | | | ART LANGE BUILDING PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | 401 CLEMATIS STREET | | WEST PALM BEACH, FL 33402 | | | | 561-805-6718 [email protected] | | | | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE | | 2015 5TH EDITION | | | | 2/26/18 NEW COMMENTS: | | | | THRESHOLD | | | | THRESHOLD BUILDINGS | | | | 1. SPECIAL INSPECTOR AGREEMENT SHALL BE COMPLETED AND | | SUBMITTED IN TRIPLICATE. | | 2. PROVIDE RESUME OF JOB INSPECTOR (P.E., ARCH. OR 468 | | INSPECTOR). | | 3. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY | | CONTRACTOR. | | 4. PROVIDE STRUCTURAL INSPECTION PLAN. | | 5. THIS BUILDING MEETS THE DEFINITION OF: THRESHOLD | | BUILDING F.S. 553.71 (12) | | | | ?THRESHOLD BUILDING? ANY BUILDING WHICH IS GREATER THAN | | (3) STORIES OR 50 FT. IN HEIGHT OR WHICH HAS AN | | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN | | AREA AND HAS AN OCCUPANT CONTENT OF GREATER THAN 500 | | PERSONS. | | | | 5A) THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS PURSUANT TO | | A STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER | | OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE | | SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE | | OF A BUILDING PERMIT. | | | | 5B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. | | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD | | BUILDINGS, A SPECIAL INSPECTOR IS REQUIRED BY F.S. | | 553.79 (5) TO THE MINIMUM INSPECTIONS REQUIRED BY THIS | | CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE | | FILLED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED AND | | RETURNED TO THIS OFFICE AND REVIEWED AND APPROVED | | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. CONTACT KEN | | CONRAD, MANAGER OF SPECIAL INSPECTOR PROGRAM AT (561) | | 805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT MAY | | BE ISSUED. | | | | 5C) MISSING STATEMENT. THRESHOLD BUILDING, REQUIRED. | | W.P.B. AMENDMENT 110.3.7.4.4. ALL PLANS FOR THE | | BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY | | THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT | | THAT, ?TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE | | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | F.S.? | | | | | | _______________________________________ | | | | | | 1. FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOORS | | INCLUDING STOREFRONT AND NANA WALL SYSTEMS AND LOUVERS. | | IF THESE ARE NOT PROVIDED YOU CAN LIST THEM ON THE | | COVER PAGE AS DEFERRED SUBMITTALS. | | | | FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF | | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | FOR REVIEW BY THE BUILDING OFFICIAL. | | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | OFFICIAL. | | | | 2. MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES | | SHALL COMPLY WITH FBC 404.2.4. MANEUVERING CLEARANCES | | SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE | | REQUIRED LATCH SIDE OR HINGE SIDE CLEARANCE. | | | | FBC ACCESSIBILITY 404.2.4.1 SWINGING DOORS AND GATES. | | SWINGING DOORS AND GATES SHALL HAVE MANEUVERING | | CLEARANCES COMPLYING WITH TABLE 404.2.4.1. (A) | | SEE RESTROOM DOORS 102, 103, 302, 303, 304 A / A2.2.2 | | PROVIDE 18? AT THE FRONT APPROACH PULL SIDE. | | | | 3. GATE AND FENCE AT THE WEST STAIRS OBSTRUCTS THE FLOW | | OF THE EGRESS CONTINUITY. SEE 1 / A6.1.1 | | | | FBC 1003.6 MEANS OF EGRESS CONTINUITY. | | THE PATH OF EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL | | NOT BE INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A | | MEANS OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER. | | OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH | | OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY | | THIS CHAPTER. THE REQUIRED CAPACITY OF A MEANS OF | | EGRESS SYSTEM SHALL NOT BE DIMINISHED ALONG THE PATH OF | | EGRESS TRAVEL. | | | | 4. PROVIDE A WPS (WELDING PROCEDURE SPEC). HAVE THIS ON | | SITE AT TIME OF INSPECTION. | | | | WELDED OR BOLTED CONNECTIONS | | THE CONTRACTOR IS REQUIRED TO PROVIDE A (WPS) WELD | | PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | STANDARDS AT TIME OF INSPECTION. | | | | 2014 FBC-B 2204.1 WELDING | | 2014 FBC-B 2204.2 BOLTING. | | | | 5. NOTE: FOUNDATION PERMIT APPLICATION 17090199 HAS | | BEEN REVIEWED AND HAS PLAN REVIEW COMMENTS THAT NEED | | ADDRESSING. | | | | 6. IMPACT FEES | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | IMPACT FEES AT (561) 233-5025. | | | | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: | | | | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 | | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. | | | | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED | | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS | | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE | | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE | | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR | | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN | | THE PERMIT PACKAGE. | | | | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2018-04-26 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-04-26 |
Time |
08:44 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-04-26 |
Time |
08:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-03-05 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-03-05 |
Time |
07:41 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-03-05 |
Time |
07:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2017-12-05 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-12-05 |
Time |
16:37 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-12-05 |
Time |
16:37 |
Sent To |
|
|
Notes |
2017-12-05 16:37:14 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS | | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF | | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE | | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET | | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, | | 107.2.1 | | 2. SHEET E1.1.1: PROVIDE AUTOMATIC LIGHTING CONTROL PER | | FBC EC 405.2.2 | | 3. SHEET E1.2.1: PROVIDE AUTOMATIC LIGHTING CONTROL PER | | FBC EC 405.2.2 | | 4. SHEET E3.0.0: FEEDER ?F-3? SHOULD NOT HAVE ANY | | EQUIPMENT GROUNDING CONDUCTOR, THIS IS STILL THE | | SERVICE LATERAL AND NOT A FEEDER. NEC 250.6, 250.24, | | 250.122 | | 5. SHEET E3.0.0: MAIN # 1 IS SHOWN AS A DISCONNECT IN | | THE RISER DIAGRAM, BUT IS ALSO SHOWN AS A MAIN LUG | | PANEL IN THE PANEL SCHEDULE. CLARIFY AND/OR CORRECT. | | FBC 107.2.1 | | 6. SHEET E3.0.0: PANEL ?A? AND PANEL ?PARK? SHOW | | SEVERAL CIRCUITS CONTROLLED THROUGH PHOTOCELL. FBC | | ENERGY STATES: ?LIGHTING NOT DESIGNATED FOR | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A | | COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN | | ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN | | ASTRONOMICAL TIME SWITCH OR A PHOTOSENSOR.? CLARIFY | | WHAT TYPE OF LOAD THIS IS. FBC 107.2.1; FBC EC 405.2.4 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
4 |
Status |
P |
Date |
2018-06-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-06-20 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-06-20 |
Time |
15:51 |
Sent To |
|
|
Notes |
2018-06-20 15:51:57 | OK PER MG | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
F |
Date |
2018-05-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-05-27 |
Time |
15:38 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-05-27 |
Time |
15:38 |
Sent To |
|
|
Notes |
2018-05-27 15:39:02 | EMAILED MANNY GONZALEZ ON 5/26 RE: APPROVAL FOR PROJECT | | PENDING VERIFICATION THAT ENGINEERING REQUIREMENTS HAVE | | BEEN SATISFIED | | | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
F |
Date |
2018-04-13 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-04-13 |
Time |
12:04 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-04-13 |
Time |
12:04 |
Sent To |
|
|
Notes |
2018-04-13 12:04:35 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | APPLICATION IF REQUIRED | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | /FORMS,-PERMITS-APPLICATIONS | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | MAIN PHONE: (561) 822-1200 | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2017-12-14 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-12-14 |
Time |
09:04 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-12-14 |
Time |
09:03 |
Sent To |
|
|
Notes |
2017-12-14 09:04:27 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | APPLICATION IF REQUIRED | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | /FORMS,-PERMITS-APPLICATIONS | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | MAIN PHONE: (561) 822-1200 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-03-02 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-03-02 |
Time |
09:53 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-03-02 |
Time |
09:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2017-11-28 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2017-11-28 |
Time |
13:32 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2017-11-28 |
Time |
12:02 |
Sent To |
|
|
Notes |
2017-11-28 13:02:07 | 201 NORTH FLAGLER DRIVE | | PERMIT #17110857 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****APPROVED WITH PROVISIONS***** | | | | GENERAL: PLANS INDICATE AN ADDRESS OF 185 BANYAN | | BOULEVARD; HOWEVER, THE PERMIT APPLICATION INDICATES AN | | ADDRESS OF 201 NORTH FLAGLER DRIVE. PLEASE COORDINATE | | THE PROPER ADDRESS. | | | | SHEET FP1.1.1: BACKFLOW PREVENTER SHALL BE LOCATED IN | | ACCORDANCE PER NFPA 24 SECTION 6.2.1, ALL CONNECTIONS | | TO PRIVATE FIRE SERVICE MAINS FOR FIRE PROTECTION | | SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH ONE OF THE | | FOLLOWING SO THAT THEY CAN BE ISOLATED: | | (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 | | FEET FROM THE BUILDING. | | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST | | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED | | CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE | | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST | | INDICATOR VALVE. | | (2) A WALL POST INDICATOR VALVE | | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN | | ACCORDANCE WITH SECTION 6.4 | | (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING | | VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. | | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A | | BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE | | SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET | | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF | | THE WALL FACING THE BACKFLOW PREVENTER. | | (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM | | ACCESSIBLE FROM THE EXTERIOR | | (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE | | ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE | | AUTHORITY HAVING JURISDICTION | | | | SHEET FP1.2.1: A SECOND STANDPIPE RISER WITH FIRE | | DEPARTMENT HOSE VALVES IS NEEDED ON THE EAST SIDE OF | | THE BUILDING TO COMPLY WITH THE COVERAGE REQUIREMENTS | | NFPA 14. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2018-03-15 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-03-15 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-03-15 |
Time |
14:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-05-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-05-27 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-04-16 |
Time |
11:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-04-13 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-04-13 |
Time |
12:05 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-02-22 |
Time |
08:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-01-25 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2018-01-25 |
Time |
14:31 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-11-22 |
Time |
08:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
3 |
Status |
P |
Date |
2018-07-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-07-12 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-12 |
Time |
15:20 |
Sent To |
|
|
Notes |
2018-07-12 15:20:36 | MU2018-24209 | | $0 DUE | | |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
F |
Date |
2018-03-06 |
|
|
Cont ID |
|
Sent By |
aclange |
Date |
2018-03-06 |
Time |
10:24 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2018-03-06 |
Time |
10:24 |
Sent To |
|
|
Notes |
2018-03-06 10:24:45 | IMPACT FEES | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | IMPACT FEES AT (561) 233-5025. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2017-12-13 |
|
|
Cont ID |
|
Sent By |
aclange |
Date |
2017-12-13 |
Time |
12:59 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2017-12-13 |
Time |
12:59 |
Sent To |
|
|
Notes |
2017-12-13 12:59:55 | IMPACT FEES | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | IMPACT FEES AT (561) 233-5025. | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2018-03-06 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-03-06 |
Time |
11:06 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-03-05 |
Time |
17:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2017-12-01 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-12-01 |
Time |
08:19 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-11-30 |
Time |
16:40 |
Sent To |
|
|
Notes |
2017-12-01 08:57:27 | 1ST REVIEW FBC-2014 MECHANICAL /ENERGY CONSERVATION | | CODES | | PERMIT #17110857 | | 12/1/17 | | | | PLAN REVIEW RESULTS: DENIED. | | PLEASE ADDRESS THE FOLLOWING COMMENTS. | | | | 1) SHEETS M1.1.1 & M1.2.1: WHAT STANDARD OR APPROVED | | CALCULATION PROCEDURE WAS USED TO DETERMINE THE AMOUNT | | OF COOLING PER SQUARE FOOT, AND THE 1ST AND 2ND FLOOR | | AC SYSTEM SIZES? PLEASE SHOW COMPLIANCE WITH SECTION | | C403.2.1 FBC-14 ENERGY CONSERVATION. | | | | C403.2.1 CALCULATION OF HEATING AND COOLING LOADS. | | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE | | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR | | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE | | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT | | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE | | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE | | SIZING CALCULATION SHALL BE SUBMITTED WITH THE | | APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND | | COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD | | REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY | | SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE | | WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT HANDBOOK. | | ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN | | APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE | | DESIGN PARAMETERS SPECIFIED IN CHAPTER 3. | | | | EXCEPTION: WHERE MECHANICAL SYSTEMS ARE DESIGNED BY A | | REGISTERED ENGINEER, THE ENGINEER HAS THE OPTION OF | | SUBMITTING A SIGNED AND SEALED SUMMARY SHEET TO THE | | BUILDING DEPARTMENT IN LIEU OF THE COMPLETE SIZING | | CALCULATION(S). SUCH SUMMARY SHEET SHALL INCLUDE THE | | FOLLOWING (BY ZONE): | | | | 1. PROJECT NAME/OWNER | | | | 2. PROJECT ADDRESS | | | | 3. AREA IN SQUARE FEET | | | | 4. SIZING METHOD USED | | | | 5. OUTDOOR DRY BULB USE | | | | 6. INDOOR DRY BULB | | | | 7. OUTDOOR WET BULB USED | | | | 8. GRAINS WATER (DIFFERENCE) | | | | 9. TOTAL SENSIBLE GAIN | | | | 10. TOTAL LATENT GAIN | | | | 11. RELATIVE HUMIDITY | | | | 12. TOTAL COOLING REQUIRED WITH OUTSIDE AIR | | | | 13. TOTAL HEATING REQUIRED WITH OUTSIDE AIR | | | | 2) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED | | IN ACCORDANCE WITH SECTION C408.2. PLEASE SUBMIT A | | COMMISSIONING PLAN IN COMPLIANCE WITH SECTION C408.2.1. | | | | 3) A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR | | SYSTEMS OF THE 5-TON RTU-1 SYSTEM PER SECTION 606.2.1. | | PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE | | MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS | | NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. | | | | 4) PROVIDE A DETAIL FOR INSTALLATION OF THE FIRE/SMOKE | | DAMPERS AND SUBMIT PRODUCT DATA AND SPECIFICATIONS | | SHEETS. | | | | 5) M5.01: NOTE 4 UNDER THE EQUIPMENT SUPPORT CURB | | DETAIL APPEARS TO INDICATE THAT THE CURB AND RTU | | INSTALLATION WILL BE DESIGNED BY A STRUCTURAL ENGINEER. | | IT ALSO REFERENCES DWG. S3.300 WHICH WAS NOT UPLOADED | | WITH THE PLANS SET. PLEASE PROVIDE SITE SPECIFIC | | ENGINEERING FOR INSTALLATION OF RTU-1 IN ACCORDANCE | | WITH SECTION 1609 FBC-14 BUILDING. | | | | 6) PROVIDE A LIST OF DEFERRED SUBMITTALS. | | | | DEFERRED SUBMITTALS | | | | 1) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. | | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS | | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE | | NOT SUBMITTED AT THE TIME OF THE | | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE | | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL | | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF | | THE BUILDING OFFICIAL. THE REGISTERED DESIGN | | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE | | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR | | REVIEW BY THE BUILDING OFFICIAL. | | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | OFFICIAL. | | 2) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT | | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE | | FAC RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FOR JURISDICTIONAL APPROVAL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
P |
Date |
2017-12-14 |
|
|
Cont ID |
|
Sent By |
aclange |
Date |
2017-12-14 |
Time |
09:24 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2017-12-14 |
Time |
09:24 |
Sent To |
|
|
Notes |
2017-12-14 09:24:22 | FLOOD MAP IN EFFECT AT TIME OF FOUNDATION PERMIT | | APPLICATION 1979 FIRMS + 1' FREEBOARD | | MINIMUM ELEVATION = 8.0' NGVD29 | | PROPOSED LOWEST FINISHED FLOOR ELEVATION = 9.0' NGVD29 | | | | PROVISO: | | A "CONSTRUCTION DRAWING" ELEVATION CERTIFICATE IS | | RECOMMENDED AT THIS TIME TO AVOID FUTURE DELAYS | | (CORRECTIONS, IF APPLICABLE, WILL NOT DELAY PERMIT | | ISSUANCE) | | A "BUILDING UNDER CONSTRUCTION" ELEVATION CERTIFICATE | | OR FORM BOARD SURVEY IS REQUIRED PRIOR TO CONCRETE | | POUR. THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW | | A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE IS | | REQUIRED PRIOR TO FINAL INSPECTION AND/OR CO AND/OR | | TCO. | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2018-03-15 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-03-15 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-03-13 |
Time |
17:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2017-12-18 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-12-18 |
Time |
11:25 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-12-16 |
Time |
13:54 |
Sent To |
|
|
Notes |
2017-12-18 13:28:51 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. SHAT. LS.1.1 UNDER THE PLUMBING FIXTURES REQUIRED, | | FIRST FLOOR TERRACE A-2 YOU HAVE FOR YOUR FIXTURE RATIO | | AS 1 PER 125 FOR MEN AND 1 PER 65 FOR WOMEN IT SHALL BE | | 1 PER 75 FOR BOTH SEXES. PER FBC PL TABLE 403.1 | | | | 2. SHAT. LS.1.1 UNDER THE PLUMBING FIXTURES REQUIRED, | | SECOND FLOORR TERRACE A-2 YOU HAVE FOR YOUR FIXTURE | | RATIO AS 1 PER 125 FOR MEN AND 1 PER 65 FOR WOMEN IT | | SHALL BE 1 PER 75 FOR BOTH SEXES. PER FBC PL TABLE | | 403.1 | | | | 3. SHT. LS .1.1 WHAT WILL THE ROOF TERRACE BE USED FOR | | IF IT IS USED FOR THE RESTAURANT PATRONS FOR DINNING IT | | SHALL BE CONSIDERED AN A-2 WITH A FIXTURE RATIO OF 1 | | PER 75 FOR BOTH SEXES. PER FBC PL TABLE 403.1 | | | | 4. SHT LS .1.1 FOR THE A-2 RESTAURANT OCCUPANCY A WATER | | FOUNTAIN IS NOT REQUIRED BUT FOR THE BUSINESS OR | | MERCANTILE OCCUPANCY'S WITH A OCCUPANT LOAD OVER 15 A | | WATER FOUNTAIN IS REQUIRED. PER FBC PL TABLE 403.1 | | | | 5. PLEASE PROVIDE FIXTURE COUNT FOR THE OCCUPANTS OF | | THE PARK NEXT TO RESTAURANT AND THE STANDARD THAT IT | | WAS DESIGNED UNDER. PER WPB AMEND TO FBC 107.2.1 | | | | 6. SHT LS .1.2 SYSTEM NO-C-AJ-1014 PART OF THE TEXT IS | | CUT OFF PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | 7. PROVIDE DETAIL WITH A SYSTEM DESIGNED FOR PLASTIC | | PIPE LARGE THAN 2". PER WPB AMEND TO FBC 107.2.1 | | | | 8. SHT. A2-2-2 DETAIL PLEASE SHOW CLEAR FLOOR SPACE FOR | | WATER CLOSETS. PER FBC ACC 604.3.1 | | | | 9. SHT. A2-2-2 LABEL ALL CLEAR FLOR SPACES WITH | | DIMENSIONS. PER WPB AMEND TO FBC 107.2.1 | | | | 10.SHT. A2-2-2 THE GRAB BARS SHALL BE MEASURE FROM THE | | GRIPPING SURFACE TI FINISHED FLOOR. PER FBC ACC 609.4 | | | | 11. SHT. A2-2-2 PLEASE SHOW COMPLIANCE WITH FBC ACC | | 604.7 DISPENSERS. | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT | | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE | | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 | | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH | | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. | | | | 12. SHT. A2-2-2 PLEASE SHOW COMPLIANCE WITH FBC ACC | | 604.4 SEATS. | | THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH | | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES | | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS | | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. | | | | 13. SHT. A2-2-2 PLEASE SHOW COMPLIANCE WITH FBC ACC | | 603.3 MIRRORS. | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES | | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE | | OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM | | ABOVE THE FINISH FLOOR OR GROUND. | | | | 14. SHT. A8-2-1 DETAIL #3 PLEASE SHOW PLEASE SHOW HOW | | THE-ROOF DRAIN WILL BE SECURED TO STRUCTURAL SLAB. PER | | WPB AMEND TO FBC 107.2.1 | | | | 15. SHT. P2.1.1 PROVIDE NOTE ON PLAN OR SHOW ON RISER | | COMPLIANCE WITH FBC PL 416.5 TEMPERED WATER FOR PUBLIC | | HAND-WASHING FACILITIES. | | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND | | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES | | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED | | WATER SHALL BE DELIVERED THEOUGH AN APPROVED | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | 1070 OR CSA B125.3. | | | | 16. HOW WILL THE FUTURE CAPPED SANITARY LINE BE | | LOCATED-UNDER THE SLAB. PER WPB AMEND TO FBC 107.2.1 | | | | 17. SHT. P3.2.1 PLEASE SHOW DFU LOAD ON SANITARY | | ISOMETRIC. PER FBC PL 710.1 AND TABLE 710.1(1) | | | | 18. SHT. P3.3.1 THE PIPE SIZE IS MISSING PLEASE CLARIFY | | PER WPB AMEND TO FBC 107.2.1 | | A) THE BRANCH FROM SECOND FLOOR TROUGH DRAIN | | B) THE BRANCH FROM THR RISER CONNECTING TROUGH DRAINS | | | | 19. P3.3.1 SQFT IS MISSING ON BRANCH CONNECTING THE | | ROOF TERRACE TRENCH DRAIN. PER WPB AMEND TO FBC 107.2.1 | | | | 20. PROVIDE SIZING CALCULATIONS FROM SCHEIR | | MANUFACTURING FOR THE GREASE INTERCEPTORS. PER WPB | | AMEND TO FBC 107.2.1 | | | | 21. SHT. P3.3.1 THE 4" BRANCH CONNECTING THR TRENCH | | DRAIN-AND A + B STACKS FROM THE ROOF TERRACE IS | | UNDERSIZED PER FBC PL TABLE 1106.3 | | | | 22. SHT. P3.3.1 SHOW SQFT ON OVERFLOW PIPING. PER WPB | | AMEND TO FBC 107.2.1 | | | | 23. SHT. P3.3.1 THE 6" HORIZONTAL OVERFLOW DRAIN PIPE | | IS UNDERSIZED PER FBC PL TABLE 1106.3 | | | | 24. SHT. P3.3.1 THE SECOND SECTION OF 8" HORIZONTAL | | DRAIN PIPE WITH 12796 SQFT IS UNDERSIZED PER FBC PL | | TABLE 1106.3 | | | | 25. SHT. P3.3.1 WHAT LEVEL IS THE TRENCH DRAIN THAT IS | | LABELED WITH 350 SQFT PLEASE CLARIFY. PER WPB AMEND TO | | FBC 107.2.1 | | | | 26. SHT. P4.1.1 A DOUBLE SANITARY TEE CAN NOT BE USED | | AS A SAMPLING PORT A PRE MANUFACTURED SAMPLING PORT OR | | A TWO WAY CLEANOUT CAN BE USED PER WPB UTILITIES DEPT. | | SEE STANDARD DETAIL GS 7 OR GS 7.1 | | | | 27. P4.1.1 MIAMI DADE CODES DO NOT APPLY TO THIS | | PROJECT PLEASE REMOVE ANY REFERENCES FROM PLAN. PER WPB | | AMEND TO FBC 107.2.1 | | | | 28. P4.2.1 DETAIL WITH SPACING OF PIPE HANGERS DOES NOT | | COMPLY WITH FBC PL TABLE 308.5 PLEASE CLARIFY | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
Rev No |
1 |
Status |
P |
Date |
2018-03-15 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-03-15 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-03-15 |
Time |
14:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2018-05-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-05-27 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-05-27 |
Time |
15:30 |
Sent To |
|
|
Notes |
2018-05-27 15:37:55 | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. DIGITAL SIGNATURES/SEALS ARE IN ACCORDANCE WITH FS | | 471, FS 481. NEW SHEETS SUBMITTED IN THE NEXT REVIEW | | CYCLE REQUIRE REVIEW. | | | | 2. ENERGY CALCS, AC CALCS - OK | | | | 3. CIVILS OK | | | | 4. ARCHITECTURAL SHEETS (KEITH SPINA, RA) OK | | | | 5. STRUCTURAL SHEETS (ANDREW P. SULLIVAN, PE) OK | | | | 6. MECHANICAL, PLUMBING, ELECTRICAL, FA, FS SHEETS | | (STEVEN FELLER, PE) OK | | | | 7. HARDSCAPE SHEETS (BRYAN DONAHUE, RLA) OK | | | | | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2018-03-06 |
|
|
Cont ID |
|
Sent By |
aclange |
Date |
2018-03-06 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2018-03-06 |
Time |
10:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2017-12-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-12-20 |
Time |
06:37 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-12-20 |
Time |
06:37 |
Sent To |
|
|
Notes |
2018-03-06 12:46:01 | MECH DIG/SIGS OK | | CCOLE-3/6/18 | 2017-12-20 06:49:40 | SAMANTHA HILL | | 561-805-6724 | | [email protected] | | | | PROVISO: DIGITAL SIGNATURE REVIEW: NEW SHEETS AND | | DOCUMENTS SUBMITTED NEXT REVIEW CYCLE NEED REVIEW | | | | DIGITAL SIGNATURE/SEALS VERIFIED: | | | | ENERGY CALC REPORT - STEVEN FELLERS, PE AND KEITH | | SPINA: OK | | ENERGY INPUT REPORT - STEVEN FELLERS, PE: OK | | SYSTEM CHECKSUMS - NEED TO BE SIGNED AND SEALED | | CIVILS - GREGORY F. BOLEN, PE: OK | | ARCHITECTURAL SHEETS - KEITH M. SPINA: OK | | STRUCTURAL SHEETS - ANDREW P. SULLIVAN, PE: OK | | MECHANICAL, ELECTRICAL, PLUMBING, FIRE ALARM, FIRE | | PROTECTION SHEETS - STEVEN FELLERS, PE: OK | | | | | | | | | | |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
2 |
Status |
P |
Date |
2018-03-06 |
|
|
Cont ID |
|
Sent By |
aclange |
Date |
2018-03-06 |
Time |
11:28 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2018-03-06 |
Time |
11:28 |
Sent To |
|
|
Notes |
2018-03-06 11:29:55 | SPECIAL INSPECTOR AGRREEMENT ON FILE WITH FOUNDATION | | PERMIT 17090199. COPIES PROVIDED TO RICHARD GATHRIGHT | | AND KEN CONRAD. |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
1 |
Status |
F |
Date |
2017-12-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-12-20 |
Time |
06:53 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2017-12-20 |
Time |
06:53 |
Sent To |
|
|
Notes |
2017-12-20 10:14:47 | 12/20/17 | | | | ART LANGE BUILDING PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | 401 CLEMATIS STREET | | WEST PALM BEACH, FL 33402 | | 561-805-6718 [email protected] | | | | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | | | CALLED HEDRICK CONSTRUCTION. REQUESTED AN EMAIL ADDRESS | | TO SEND OVER THE GUIDELINES AND POLICIES FOR PROJECTS | | CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT | | INSPECTORS. | | | | 1) A RESIDENT INSPECTOR WILL BE REQUIRED FOR THIS | | PROJECT PER WEST PALM BEACH ADMINISTRATIVE CODE | | SECTION: | | 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING | | OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE | | INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT | | REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION | | SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS | | SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A | | CERTIFICATE CALLED FOR BY ANY PROVISION OF THE | | TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS | | UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A | | RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING | | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION | | SERVICE IN THE FOLLOWING INSTANCES: | | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II | | CONSTRUCTION | | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS | | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE | | STRENGTH IN EXCESS OF 3000 POUNDS PER SQUARE | | INCH | | 4. FOR PILE DRIVING | | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE | | FOOT | | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT | | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR | | METHODS OF CONSTRUCTION | | SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES | | WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE | | BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED | | ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER | | CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH | | INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS | | INCLUDING THE DAILY INSPECTIONS TO THE BUILDING | | OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF | | THE RESIDENT INSPECTOR. | | CONTACT KEN CONRAD MANAGER OF THE RESIDENT INSPECTOR | | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION | | BEFORE THE PERMIT MAY BE ISSUED. | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2018-05-04 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2018-05-04 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2018-05-04 |
Time |
15:48 |
Sent To |
|
|
Notes |
2018-05-04 15:49:43 | PROVISO: LANDSCAPE PERMITS SHALL BE SUBMITTED BEFORE | | CONSTRUCTION STARTS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2018-04-06 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2018-04-06 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2018-04-06 |
Time |
10:27 |
Sent To |
|
|
Notes |
2018-04-06 12:10:40 | 1. NOT SATISFIED. SHEET A1-1-1 IS DIFFERENT THAN SHEET | | A1-1-2 , PLEASE ADJUST ALL DRAWINGS TO REFLECT THE SAME | | INFORMATION. SHEET A1-1-1 INDICATES THE STAIR ENDING | | NORTH OF THE PROJECTION OF THE PLANTER (DRAWING NOT | | DIMENSION THEREFORE CONFIRMATION NOT POSSIBLE BY | | STAFF), IT SEEMS AN ACCEPTABLE CONDITION, BUT DIMENSION | | DRAWING NEEDED TO CONFIRM. - 1/17/18- A MINIMUM 8' | | CLEAR SIDEWALK SHALL BE PROVIDED AROUND THE PROJECT. | | THE MAIN STAIR AT THE CORNER OF FLAGLER DRIVE AND | | BANYAN BLVD IS ENCROACHING TOO MUCH INTO THE CLEAR | | SIDEWALK PATH. ONE FOOT OF THE TREE GRATE CAN BE | | COUNTED TOWARDS THE CLEAR PATH IF NEEDED. | | 2. NOT SATISFIED - 1/18/19. ARTIFICAL GRASS IS NOT | | ALLOWED IN ANY LOCATION VISIBLE FROM THE PUBLIC RIGHT | | OF WAY. | | 3. NOT SATISFIED. IN ADDITION TO THE ELEMENTS MENTIONED | | IN PREVIOUS REVIEW, THE AMOUNT OF WINDOWS ALONG BANYAN | | BLVD HAS ALSO BEEN REDUCED. PLEASE SUBMTI INFORMATION | | TO CONFIRM COMPLIANCE WITH THE MINIMUM 50% TRANSPARENCY | | REQUIRED ALONG BANYAN BOULEVARD. -1/17/18 .ORIGINAL | | APPROVAL INCLUDED AN EYE BROW ELEMENT ALONG BANYAN | | BOULEVARD AND A METAL MESH ELEMENT AT THE CORNER OF | | NARCISSUS AVE AND BANYAN BLVD TO ENHANCE THE BLANK | | FACADE. THOSE ELEMENTS SHALL NOT BE REMOVED AS THEY | | WERE APPROVED AS PART OF THE ARCHITECTURAL DESIGN | | PRESENTED TO THE DAC. | | 4. SP1-01 STILL SHOWS DOOR, PLEASE ADJUST ALL DRAWING.- | | 1/17/18 -ORIGINAL APPROVAL DID NOT INCLUDE A MECHANICAL | | DOOR ALONG NARCISSUS AVENUE. IF THE DOOR SHALL REMAIN | | AT THAT LOCATION ITS APPEARANCE SHALL BE IMPROVED. | | ORIGINAL APPROVAL DEPICTS A WINDOW. | | 5. ACCORDING TO CURRENT SIGN REGULATION, ONLY SIGNAGE | | ALLOWED IS FOR TENANT ON FIRST FLOOR.-1/17/18 -SIGNAGE | | IS NOT INCLUDED UNDER THIS PERMIT. SECODN FLOOR TENANT | | IS NOT ALLOWED TO HAVE SIGN ON BUILDING FACADE. A | | PEDESTRIAN BLADE SIGN WILL BE PERMITTED. | | 6. SATISFIED - 1/17/18-ROOF TOP TERRACE DOES NOT | | INCLUDE ANY VEGETATION OR ANY ROOF SCREENING FOR | | MECHANICAL EQUIPMENT. HOTEL ROOMS WILL HAVE A DIRECT | | VIEW OF MECHANICAL EQUIPMENT. | | 7. APPLICANT'S RESPONSE ACKNOWLEDGED. STAFF WILL | | DISCUSS WITH ENG. DEPARTMENT FOR FINAL | | DETERMINATION.-1/17/18 -PLEASE PROVIDE A PEDESTRIAN | | CROSSING AT NARCISSUS AVE AND 2ND STREET TO CONNECT | | WITH THE PARK ON THE NORTH SIDE. | | 8. OK- 1/17/18- CAN THE PROPOSED SWITCH CABINET ALONG | | NARCISSUS BE RELOCATED AWAY FROM THE PEDESTRIAN PATH OF | | TRAVEL? | | 9. DETAIL OF SPECIFIC LIGHT FIXTURE ARE NEEDED. | | -1/19/18.PLEASE PROVIDE SPECS FOR LIGHT FIXTURES AND | | POLES ON ROW. FLAGLER POLES AND FIXTURES SHALL MATCH | | THE WATERFRONT DESIGN, AND OTHER STREETS SHALL FOLLOW | | THE DOWNTOWN STANDARD. IF ANY COBRA HEADS EXISTS, THEY | | SHOUDL BE REMOVED AND REPLACED BY DECORATIVE. | | 10.OK- 1/17/18- STAFF RECOMMENDS NARCISSUS AVE TO BE | | DESIGNED AS A CURBLESS ROAD TO FACILITATE THE | | RELATIONSHIP BETWEEN THE HOTEL AND THE PARK. | | 11. OK - 1/17/18. ADA RAMPS AT CORNRES SHALL BE | | DESIGNED TO REDUCED PEDESTRIAN DISTANCE AT CROSSING. | | STAFF SUGGEST DOING TWO RAMPS INSTEAD OF ONE. | | 12. OK- 1/17/18. PLEASE COORDINATE WITH THE CITY FOR | | THE REDESIGN OF THE FLAGLER DRIVE AND BANYAN BOULEVARD | | INTERSECTION. CHANGES MAY AFFECT PROJECT STARS. | | 13. CITY RECORDS DO NOT SHOW A SEPARATE LANDSCAPE | | PERMIT FOR ANY OF THE 3 PROJECTS ASSOCIATED WITH THE | | OLD CITY HALL SITE. PLEASE SUBMIT A SEPARATE LANDSCAPE | | PERMIT. 1/19/18. A SEPARATE LANDSCAPE PERMIT SHALL BE | | SUBMITTED FOR THE PROJECT. AN ENGINEERING PERMIT WILL | | BE REQUIRED FOR THE LANDSCAPE ON THE ROW. | | 14. OK - 1/17/18.FURTHER DISCUSSION IS NECESSARY FOR | | THE DESIGN OF THE PUBLIC PARK. | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2018-01-17 |
|
|
Cont ID |
|
Sent By |
AA |
Date |
2018-01-17 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2018-01-17 |
Time |
11:21 |
Sent To |
|
|
Notes |
2018-01-17 12:34:49 | 1. A MINIMUM 8' CLEAR SIDEWALK SHALL BE PROVIDED AROUND | | THE PROJECT. THE MAIN STAIR AT THE CORNER OF FLAGLER | | DRIVE AND BANYAN BLVD IS ENCROACHING TO MUCH INTO THE | | CLEAR SIDEWALK PATH. ONE FOOT OF THE TREE GRATE CAN BE | | COUNTED TOWARDS THE CLEAR PATH IF NEEDED. | | 2. ARTIFICAL GRASS IS NOT ALLOWED IN ANY LOCATION | | VISIBLE FROM THE PUBLIC RIGHT OF WAY. | | 3. ORIGINAL APPROVAL INCLUDED AN EYE BROW ELEMENT ALONG | | BANYAN BOULEVARD AND A METAL MESH ELEMENT AT THE CORNER | | OF NARCISSUS AVE AND BANYAN BLVD TO ENHANCE THE BLANK | | FACADE. THOSE ELEMENTS SHALL NOT BE REMOVED AS THEY | | WERE APPROVED AS PART OF THE ARCHITECTURAL DESIGN | | PRESENTED TO THE DAC. | | 4. ORIGINAL APPROVAL DID NOT INCLUDE A MECHANICAL DOOR | | ALONG NARCISSUS AVENUE. IF THE DOOR SHALL REMAIN AT | | THAT LOCATION ITS APPEARANCE SHALL BE IMPROVED. | | ORIGINAL APPROVAL DEPICTS A WINDOW. | | 5. SIGNAGE IS NOT INCLUDED UNDER THIS PERMIT. SECODN | | FLOOR TENANT IS NOT ALLOWED TO HAVE SIGN ON BUILDING | | FACADE. A PEDESTRIAN BLADE SIGN WILL BE PERMITTED. | | 6. ROOF TOP TERRACE DOES NOT INCLUDE ANY VEGETATION OR | | ANY ROOF SCREENING FOR MECHANICAL EQUIPMENT. HOTEL | | ROOMS WILL HAVE A DIRECT VIEW OF MECHANICAL EQUIPMENT. | | 7. PLEASE PROVIDE A PEDESTRIAN CROSSING AT NARCISSUS | | AVE AND 2ND STREET TO CONNECT WITH THE PARK ON THE | | NORTH SIDE. | | 8. CAN THE PROPOSED SWITCH CABINET ALONG NARCISSUS BE | | RELOCATED AWAY FROM THE PEDESTRIAN PATH OF TRAVEL? | | 9. PLEASE PROVIDE SPECS FOR LIGHT FIXTURES AND POLES ON | | ROW. FLAGLER POLES AND FIXTURES SHALL MATCH THE | | WATERFRONT DESIGN, AND OTHER STREETS SHALL FOLLOW THE | | DOWNTOWN STANDARD. IF ANY COBRA HEADS EXISTS, THEY | | SHOUDL BE REMOVED AND REPLACED BY DECORATIVE. | | 10. STAFF RECOMMENDS NARCISSUS AVE TO BE DESIGNED AS A | | CURBLESS ROAD TO FACILITATE THE RELATIONSHIP BETWEEN | | THE HOTEL AND THE PARK. | | 11. ADA RAMPS AT CORNRES SHALL BE DESIGNED TO REDUCED | | PEDESTRIAN DISTANCE AT CROSSING. STAFF SUGGEST DOING | | TWO RAMPS INSTEAD OF ONE. | | 12. PLEASE COORDINATE WITH THE CITY FOR THE REDESIGN OF | | THE FLAGLER DRIVE AND BANYAN BOULEVARD INTERSECTION. | | CHANGES MAY AFFECT PROJECT STARS. | | 13. A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED FOR | | THE PROJECT. AN ENGINEERING PERMIT WILL BE REQUIRED FOR | | THE LANDSCAPE ON THE ROW. | | 14. FURTHER DISCUSSION IS NECESSARY FOR THE DESIGN OF | | THE PUBLIC PARK. | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439. |
|
|