Plan Review Details - Permit 17110810
Plan Review Stops For Permit 17110810
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-11-27 Cont ID  
Sent By jpearson Date 2017-11-27 Time 07:07 Rev Time 0.00
Received By jpearson Date 2017-11-27 Time 07:07 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-28 Cont ID  
Sent By rmcdouga Date 2017-11-28 Time 15:08 Rev Time 0.00
Received By rmcdouga Date 2017-11-20 Time 14:07 Sent To  
Notes
2017-11-21 14:07:54REVISION ROUTED TO JPEARSON

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-11-28 Cont ID  
Sent By rmcdouga Date 2017-11-28 Time 15:08 Rev Time 0.00
Received By rmcdouga Date 2017-11-28 Time 11:20 Sent To I
Notes
2017-11-28 14:55:15FBC-R - M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-11-28 Cont ID  
Sent By gjohnson Date 2017-11-28 Time 07:23 Rev Time 0.00
Received By gjohnson Date 2017-11-28 Time 07:22 Sent To  
Notes
***NONE***