Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-01-24 Cont ID  
Sent By rbrown Date 2018-01-24 Time 19:35 Rev Time 0.00
Received By rbrown Date 2018-01-24 Time 19:35 Sent To  
Notes
2018-01-24 19:35:35PERMIT NOT REQUIRED. SOLAR TREE IS OWNED
 BY FP&L AND WILL BE GENARATING POWER FOR
 THE UTILITY SO IT IS EXEMPT FROM BUILDING PERMIT
 PROCESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-28 Cont ID  
Sent By cthroop Date 2017-12-28 Time 11:24 Rev Time 0.00
Received By cthroop Date 2017-12-28 Time 10:41 Sent To E
Notes
2017-12-28 11:29:23BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE DESIGN WIND LOADS FOR EXPOSURE C, 170 VULT
 WIND SPEED.
 2. PROVIDE STRUCTURAL FOUNDATION DETAIL FOR EACH
 FOUNDATION TYPE PER DESIGN WIND LOADS.
 3. ENGINEER OF RECORD TO SIGN AND SEAL STRUCTURAL
 DETAILS.
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-01-24 Cont ID  
Sent By rbrown Date 2018-01-24 Time 19:37 Rev Time 0.00
Received By rbrown Date 2018-01-24 Time 19:37 Sent To  
Notes
2018-01-24 19:37:24PERMIT NOT REQUIRED. SOLAR TREE IS OWNED
 BY FP&L AND WILL BE GENARATING POWER FOR
 THE UTILITY SO IT IS EXEMPT FROM BUILDING PERMIT
 PROCESS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-28 Cont ID  
Sent By jleahy Date 2017-12-28 Time 12:39 Rev Time 0.00
Received By rbrown Date 2018-01-24 Time 19:36 Sent To  
Notes
2017-12-28 12:43:54FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW THE LOCATION OF THE TRANSFORMER AND
 DISCONNECTS AS TO WHERE THE TREES ARE.
  
 PRIMARY TO TRANSFORMER IF NOT WITHIN SIGHT REQUIRES A
 DISCONNECT 450.14
  
 60A BREAKER ON #10 PER WHICH SECTION?
2017-11-27 17:26:32SENT TO ZONING JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-28 Cont ID  
Sent By jleahy Date 2017-12-28 Time 13:05 Rev Time 0.00
Received By jleahy Date 2017-11-16 Time 13:51 Sent To  
Notes
2017-12-28 13:06:09I THINK IT FAILED ZONING???
2017-12-18 11:28:19TO MISC 2 BOX.
2017-11-20 13:51:48ROUTED TO JLEAHY

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By aaponte Date 2017-12-18 Time 11:24 Sent To  
Notes
2017-12-18 11:27:281. SOLAR TREES LOCATED SOUTH OF STATION ARE WITHIN THE
 CITY'S ROW. AN AGREEMENT WITH THE CITY IS NECESSARY
 BEFORE ANY PERMIT CAN BE ISSUED.
 2. SOLAR TREE LOCATED NORTH OF STATION APPEARS TO BE
 LOCATED WITHIN THE BRIGHTLINE PROPERTY. PLEASE PROVIDE
 A SURVEY TO CLEARLY IDENTIFY THE ROW LINE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.