Plan Review Details - Permit 17110707
Plan Review Stops For Permit 17110707
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-27 Cont ID  
Sent By cthroop Date 2017-12-27 Time 10:58 Rev Time 0.00
Received By cthroop Date 2017-12-27 Time 08:20 Sent To  
Notes
2017-12-27 11:15:31BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 3. SEE PLAN PAGE A-1 - PLAN SHOWS NEW FRONT DOOR
 PROPOSED. PROVIDE PRODUCT APPROVAL FOR PROPOSED DOOR.
 4. SEE PLAN PAGE A-1 - EXT. WALL, EAST ELEVATION -
 VERTICAL REINFORCING REQUIRED AT ENDS OF NEW WALL PER
 FBC R606.12.2.2.3.
 4A. PROVIDE CONNECTION DETAIL FOR NEW CMU WALL TO
 EXISTING WALL.
 5. ONLY ONE SET OF PRODUCT APPROVALS PROVIDED FOR
 WINDOWS, SGD AND MULLIONS. SUBMITTAL DOCUMENTS SHALL BE
 IN DUPLICATE.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 R606.12.2.2.3 REINFORCEMENT REQUIREMENTS FOR MASONRY
 ELEMENTS.
 MASONRY ELEMENTS LISTED IN SECTION R606.12.2.2.2 SHALL
 BE REINFORCED IN EITHER THE HORIZONTAL OR VERTICAL
 DIRECTION IN ACCORDANCE WITH THE FOLLOWING:
  
 1. HORIZONTAL REINFORCEMENT. HORIZONTAL JOINT
 REINFORCEMENT SHALL CONSIST OF AT LEAST TWO
 LONGITUDINAL W1.7 WIRES SPACED NOT MORE THAN 16 INCHES
 (406 MM) FOR WALLS GREATER THAN 4 INCHES (102 MM) IN
 WIDTH AND AT LEAST ONE LONGITUDINAL W1.7 WIRE SPACED
 NOT MORE THAN 16 INCHES (406 MM) FOR WALLS NOT
 EXCEEDING 4 INCHES (102 MM) IN WIDTH; OR AT LEAST ONE
 NO. 4 BAR SPACED NOT MORE THAN 48 INCHES (1219 MM).
 WHERE TWO LONGITUDINAL WIRES OF JOINT REINFORCEMENT ARE
 USED, THE SPACE BETWEEN THESE WIRES SHALL BE THE WIDEST
 THAT THE MORTAR JOINT WILL ACCOMMODATE. HORIZONTAL
 REINFORCEMENT SHALL BE PROVIDED WITHIN 16 INCHES (406
 MM) OF THE TOP AND BOTTOM OF THESE MASONRY ELEMENTS.
  
 2. VERTICAL REINFORCEMENT. VERTICAL REINFORCEMENT SHALL
 CONSIST OF AT LEAST ONE NO. 4 BAR SPACED NOT MORE THAN
 48 INCHES (1219 MM). VERTICAL REINFORCEMENT SHALL BE
 LOCATED WITHIN 16 INCHES (406 MM) OF THE ENDS OF
 MASONRY WALLS.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-08 Cont ID  
Sent By jpearson Date 2017-12-08 Time 15:50 Rev Time 0.00
Received By jpearson Date 2017-12-08 Time 15:50 Sent To  
Notes
2017-12-08 15:50:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE FULL FLOOR PLAN SHOWING ALL SMOKE/CO ALARMS
 IN EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL
 EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE,
 SHOW AS NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1
 2. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 4. NOTE 11 STATES THAT BEDROOM CIRCUITS SHALL COMPLY
 WITH 210.12. THIS DOES NOT COVER THE SCOPE OF THIS
 ARTICLE, WHICH STATES: "ALL 120-VOLT, SINGLE PHASE, 15
 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION." PROVIDE
 CORRECTION. NEC 210.12; FBC RE3902.12
 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 7. PLAN SHOWS STANDARD RECESS LIGHTS IN LASTER CLOSET.
 PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION.
 NEC 410.16; FBC RE4003.12
 8. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE3901.7
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-27 Cont ID  
Sent By cthroop Date 2017-12-27 Time 11:15 Rev Time 0.00
Received By cthroop Date 2017-11-16 Time 11:43 Sent To I
Notes
2017-11-21 11:43:50R29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-27 Cont ID  
Sent By cthroop Date 2017-12-27 Time 10:57 Rev Time 0.00
Received By cthroop Date 2017-12-27 Time 08:20 Sent To  
Notes
2017-12-27 10:58:39BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-13 Cont ID  
Sent By hmoser Date 2017-12-13 Time 09:01 Rev Time 0.00
Received By hmoser Date 2017-12-13 Time 08:04 Sent To  
Notes
2017-12-13 09:01:09PLAN DENIED
 1) REFER TO SECTION M1602.4 BALANCED RETURN AIR.
 2014 RESIDENTIAL CODE.
 2) MISSING DUCT SIZE ON SUPPLY DUCT IN MASTER
 HALL WAY. SECTION 107 FBC 2014
 3) SEER ON ENERGY CALCULATIONS AND PLAN
 DO NOT MATCH.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-12-14 Cont ID  
Sent By tklarge Date 2017-12-14 Time 08:18 Rev Time 0.00
Received By tklarge Date 2017-12-01 Time 11:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-12-27 Cont ID  
Sent By cthroop Date 2017-12-27 Time 10:57 Rev Time 0.00
Received By cthroop Date 2017-12-27 Time 09:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-11-27 Cont ID  
Sent By PG Date 2017-11-27 Time   Rev Time  
Received By llouie Date 2017-11-27 Time   Sent To  
Notes
2017-11-27 16:20:35** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE VALUE OF THE CONSTRUCTION ($115,000.00) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($91,659.00) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
  
 NOTES:
  
 * IF THE EXISTING LANDSCAPING DOES NOT COMPLY WITH THE
 CURRENT LANDSCAPE STANDARDS OF THE ZLDRS, A SEPARATE
 LANDSCAPE PERMIT WILL BE REQUIRED PRIOR TO CERTIFICATE
 OF OCCUPANCY.
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  