Plan Review Details - Permit 17110548
Plan Review Stops For Permit 17110548
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By cthroop Date 2018-01-18 Time 11:20 Rev Time 0.00
Received By cthroop Date 2018-01-11 Time 15:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-13 Cont ID  
Sent By cthroop Date 2017-12-13 Time 15:05 Rev Time 0.00
Received By cthroop Date 2017-12-12 Time 13:56 Sent To  
Notes
2017-12-13 15:28:58BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. OWNER/AGENT TO SIGN ENERGY SUBMITTAL FOR MAIN HOUSE.
 2. REVISIT YOUR WINDOW AND DOOR SCHEDULES AND NOA
 SUBMITTAL PACKAGE. THERE ARE NOA'S MISSING FROM
 SCHEDULES AND NOA'S MISSING FORM SUBMITTAL. I.E. FIXED
 WINDOWS/OHD/ETC.
 3. PROVIDE PRODUCT APPROVALS FOR PROPOSED SURFACE MOUNT
 WIND ABATEMENT SYSTEM.
 4. PROVIDE ICC-ES REPORT FOR PROPOSED ICYNENE
 INSULATION. IDENTIFY PRODUCT TO BE INSTALLED BASED ON
 REQUIRED R - VALUE. PRODUCT MANUFACTURERS INSTALLATION
 INSTRUCTIONS TO BE ON-SITE AT TIME OF INSPECTION.
 5. REF. PLAN PAGE A101 - WIND EXPOSURE AND SURFACE
 ROUGHNESS CATEGORIES SHOULD BE ROUGHNESS B PER FBC
 R301.2.1.4.2 & EXPOSURE B PER R301.2.1.4.3.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 R301.2.1.4.2 SURFACE ROUGHNESS CATEGORIES.
 A GROUND SURFACE ROUGHNESS WITHIN EACH 45-DEGREE (0.79
 RAD) SECTOR SHALL BE DETERMINED FOR A DISTANCE UPWIND
 OF THE SITE AS DEFINED IN SECTION R301.2.1.4.3 FROM THE
 CATEGORIES DEFINED BELOW, FOR THE PURPOSE OF ASSIGNING
 AN EXPOSURE CATEGORY AS DEFINED IN SECTION
 R301.2.1.4.3.
  
 SURFACE ROUGHNESS B. URBAN AND SUBURBAN AREAS, WOODED
 AREAS OR OTHER TERRAIN WITH NUMEROUS CLOSELY SPACED
 OBSTRUCTIONS HAVING THE SIZE OF SINGLE-FAMILY DWELLINGS
 OR LARGER
  
 R301.2.1.4.3 EXPOSURE CATEGORIES.
 AN EXPOSURE CATEGORY SHALL BE DETERMINED IN ACCORDANCE
 WITH THE FOLLOWING:
  
 EXPOSURE B. FOR BUILDINGS WITH A MEAN ROOF HEIGHT OF
 LESS THAN OR EQUAL TO 30 FEET (9144 MM), EXPOSURE B
 SHALL APPLY WHERE THE GROUND SURFACE ROUGHNESS, AS
 DEFINED BY SURFACE ROUGHNESS B, PREVAILS IN THE UPWIND
 DIRECTION FOR A DISTANCE OF AT LEAST 1,500 FEET (457
 M). FOR BUILDINGS WITH A MEAN ROOF HEIGHT GREATER THAN
 30 FEET (9144 MM), EXPOSURE B SHALL APPLY WHERE SURFACE
 ROUGHNESS B PREVAILS IN THE UPWIND DIRECTION FOR A
 DISTANCE OF AT LEAST 2,600 FEET (792 M) OR 20 TIMES THE
 HEIGHT OF THE BUILDING, WHICHEVER IS GREATER.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-01-09 Cont ID  
Sent By jpearson Date 2018-01-09 Time 10:59 Rev Time 0.00
Received By jpearson Date 2018-01-09 Time 10:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-08 Cont ID  
Sent By jpearson Date 2017-12-08 Time 13:49 Rev Time 0.00
Received By jpearson Date 2017-12-08 Time 13:49 Sent To  
Notes
2017-12-08 13:49:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FEEDER "F-4" SHOWS 2/0 WIRE FEEDING A 200 AMP PANEL,
 PANEL A. THIS IS LABELED AS PANEL B IN THE PANEL
 SCHEDULE FOR PANEL DP AND SHOWS 3/0 WIRE FEEDING THE
 PANEL. CORRECT DISCREPANCY. BE ADVISED THAT 2/0 WIRE IS
 NOT RATED FOR A 200 AMP FEED. TABLE 310.15(B)(7) IS NOT
 PERMITTED TO BE USED UNLESS THE FEEDER IN QUESTION
 CARRIES 100% OF THE LOAD. PROVIDE CORRECTION. NEC
 310.15(B)(7) AND (B)(15); FBC RE TABLE E3603.1, 3704.1
 2. FEEDER FROM METER CAN TO ATS SHOULD NOT INCLUDE AN
 EQUIPMENT GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC
 250.6, 250.24
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 4. SHEET E-0, ARC FAULT BREAKER NOTE # 2 REFERENCES NEC
 406.11, WHICH IS NOT THE CURRENT CODE FOR TAMPER
 RESISTANT RECEPTACLES. THE STATEMENT ALSO LEAVES OUT
 THE REQUIREMENT FOR 15 AMP RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14
 5. PANEL SCHEDULE FOR PANEL DP SHOWS # 1 WIRE ON A 150
 AMP BREAKER FOR THE GUEST HOUSE. PROVIDE CORRECTION,
 SAME REASONING AS COMMENT # 1. NEC 310.15(B)(7) AND
 (B)(15); FBC RE TABLE E3603.1, 3704.1
 6. SECOND FLOOR PLAN SHOWS A PENDANT LIGHT IN HER
 CLOSET. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS". PROVIDE
 CORRECTION. NEC 410.16; FBC RE4003.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By skennedy Date 2018-01-18 Time 12:46 Rev Time 0.00
Received By skennedy Date 2018-01-18 Time 12:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-12-06 Cont ID  
Sent By tklarge Date 2017-12-06 Time 06:07 Rev Time 0.00
Received By tklarge Date 2017-12-06 Time 05:42 Sent To  
Notes
2017-12-06 05:42:511) THE TANKLESS WATER HEATERS SHALL BE LOCATED A
 MINIMUM OF 4 FEET BELOW OR TO THE SIDE OF A WINDOW OR
 DOOR THAT CAN BE OPENED PER THE MANUFACTURER'S
 INSTALLATION MANUAL.
 2) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 FOR ALL GAS EQUIPMENT/APPLIANCES. APPLIANCES SHALL BE
 LISTED AND LABELED. FBC-FUEL GAS SEC.301.3.
 3) SHT. P-3 - SHOW THE TYPE OF PIPE AND SIZE OF THE
 PIPE FOR THE TANKLESS WATER HEATERS. FBC -FUEL GAS CODE
 TABLE 402.4 (15).
 4) SHT. P-3 - SHOW THE TYPE OF PIPE AND SIZE FOR THE
 GAS LINE TO THE GENERATOR.
 5) SHOW THE SIZE AND TYPE OF PIPE ON THE OUTLET SIDE OF
 THE GAS METER.
 6) THE GAS INSTALLATION SHALL BE DONE UNDER A SEPARATE
 PERMIT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-24 Cont ID  
Sent By shill Date 2018-01-24 Time 16:30 Rev Time 0.00
Received By shill Date 2018-01-24 Time 15:25 Sent To  
Notes
2018-01-24 15:25:41IMPACT FEES ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-18 Cont ID  
Sent By cpuell Date 2018-01-18 Time 16:36 Rev Time 0.00
Received By cpuell Date 2017-12-22 Time 16:27 Sent To  
Notes
2017-12-22 16:27:20R39

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-13 Cont ID  
Sent By cthroop Date 2017-12-13 Time 15:04 Rev Time 0.00
Received By cthroop Date 2017-11-14 Time 09:39 Sent To I
Notes
2017-11-15 09:39:29R39

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-01-24 Cont ID  
Sent By shill Date 2018-01-24 Time 15:31 Rev Time 0.00
Received By shill Date 2018-01-24 Time 15:31 Sent To I
Notes
2018-01-24 15:31:56MU-2018-2460
 $0 DUE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-13 Cont ID  
Sent By cthroop Date 2017-12-13 Time 15:03 Rev Time 0.00
Received By cthroop Date 2017-12-12 Time 13:56 Sent To  
Notes
2017-12-13 15:04:43BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By skennedy Date 2018-01-18 Time 12:47 Rev Time 0.00
Received By skennedy Date 2018-01-18 Time 12:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-11 Cont ID  
Sent By hmoser Date 2017-12-11 Time 11:17 Rev Time 0.00
Received By hmoser Date 2017-12-11 Time 08:51 Sent To  
Notes
2017-12-11 11:17:27PLAN DENIED
 1) REFER TO SECTION M1602.2 PROHIBITED SOURCES.
 NOTE # 4 (RETURN AIR IN KITCHEN) 1014 RESIDENTIAL CODE
 2) REFER TO SECTION M1503.4 MAKEUP AIR. PROVIDE
 MANUFACTURES SPECKS ON RANGE HOOD WITH PLANS
 2014 RESIDENTIAL CODE
 3) REFER TO SECTION M1602.4 BALANCED RETURN AIR
 (MASTER BEDROOM) 2014 RESIDENTIAL CODE
 4) REFER TO SECTION R403.2.4 AIR HANDLER
 UNITS (FOR AIR HANDLERS 3 & 4)
 2014 FLORIDA ENERGY CODE
 5) THERE WERE NO AIR CONDITIONING PLAN
 SUBMITTED FOR GUEST HOUSE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By skennedy Date 2018-01-18 Time 12:46 Rev Time 0.00
Received By skennedy Date 2018-01-18 Time 12:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-12-06 Cont ID  
Sent By tklarge Date 2017-12-06 Time 05:56 Rev Time 0.00
Received By tklarge Date 2017-12-04 Time 09:33 Sent To  
Notes
2017-12-05 06:20:341) SHT. A 102 - SHOW THE WIDTH OF THE SHOWER ON THE 2ND
 FLOOR. THE SHOWER SHALL BE A MINIMUM OF 30 INCHES WIDE
 AND A MINIMUM OF 900 SQUARE INCHES.
 2) SHT. A 102 - THE WATER VALVES FOR THE STACKABLE
 WASHER SHALL BE ACCESSIBLE. FBC-PLUMBING SEC.606.3.
 3) SHT. A113 - INDICATE ON THE PLAN THE SLOPE OF THE 6
 INCH GUTTER. COMPLY WITH FBC-PLUMBING, TABLE 1106.6 FOR
 THE SQUARE FFOOTAGE BEING DRAINED.
 4) THE TANKLESS WATER HEATERS SHALL BE LOCATED A
 MINIMUM OF 4 FEET BELOW OR TO THE SIDE OF A WINDOW OR
 DOOR THAT CAN BE OPENED PERR THE MANUFACTURER'S
 INSTALLATION MANUAL.
 5) AN AIR ARRESTOR IS REQD. ON THE WATER SUPPLY TO THE
 ICE MAKER. FBC-PLUMBING SEC. 604.9.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By cthroop Date 2018-01-18 Time 11:20 Rev Time 0.00
Received By cthroop Date 2018-01-11 Time 15:45 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-12-13 Cont ID  
Sent By cthroop Date 2017-12-13 Time 15:02 Rev Time 0.00
Received By cthroop Date 2017-12-12 Time 17:17 Sent To  
Notes
2017-12-13 15:03:42BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING
 SYSTEMS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By PG Date 2018-01-18 Time   Rev Time 0.00
Received By pgreilic Date 2018-01-18 Time 15:44 Sent To  
Notes
2018-01-18 15:43:51PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2017-11-17 Time   Rev Time 0.00
Received By pgreilic Date 2017-11-17 Time 13:22 Sent To  
Notes
2017-11-17 13:23:17PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]