Plan Review Details - Permit 17110463
Plan Review Stops For Permit 17110463 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
aclange |
Date |
2018-02-01 |
Time |
10:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2017-11-17 |
|
|
Cont ID |
|
Sent By |
aclange |
Date |
2017-11-17 |
Time |
16:30 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2017-11-17 |
Time |
10:15 |
Sent To |
|
|
Notes |
2017-11-17 16:30:24 | | | ****PLAN REVIEW COMMENTS**** | | | | ART LANGE BUILDING PLANS EXAMINER | | 561-805-6718 [email protected] | | FBC FLORIDA BUILDING CODE 2014 5TH EDITION | | | | 1. PLEASE PROVIDE THE USE OF ROOMS 116 AND 117. THE ONE | | DIMENSION IS LESS THAN 7 FEET. | | | | FBC 1208.1 MINIMUM ROOM WIDTHS. | | | | HABITABLE SPACES, OTHER THAN A KITCHEN, SHALL BE NOT | | LESS THAN 7 FEET (2134 MM) IN ANY PLAN DIMENSION. | | KITCHENS SHALL HAVE A CLEAR PASSAGEWAY OF NOT LESS THAN | | 3 FEET (914 MM) BETWEEN COUNTER FRONTS AND APPLIANCES | | OR COUNTER FRONTS AND WALLS. | | | | 2. IN SUITE 110 THE NEW TENANT SEPARATION WALL HAS LEFT | | THE TWO EXITS WITHIN 13 FT. OF EACH OTHER. THE DIAGONAL | | OF THE SPACE IS APPROXIMATELY 100 FEET. SEE EXCEPTION | | 2. | | FBC 1015.2 EXIT OR EXIT ACCESS DOORWAY ARRANGEMENT. | | | | REQUIRED EXITS SHALL BE LOCATED IN A MANNER THAT MAKES | | THEIR AVAILABILITY OBVIOUS. EXITS SHALL BE UNOBSTRUCTED | | AT ALL TIMES. EXIT AND EXIT ACCESS DOORWAYS SHALL BE | | ARRANGED IN ACCORDANCE WITH SECTIONS FBC 1015.2.1 AND | | 1015.2.2. | | | | FBC 1015.2.1 TWO EXITS OR EXIT ACCESS DOORWAYS. | | WHERE TWO EXITS OR EXIT ACCESS DOORWAYS ARE REQUIRED | | FROM ANY PORTION OF THE EXIT ACCESS, THE EXIT DOORS OR | | EXIT ACCESS DOORWAYS SHALL BE PLACED A DISTANCE APART | | EQUAL TO NOT LESS THAN ONE-HALF OF THE LENGTH OF THE | | MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR | | AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN | | EXIT DOORS OR EXIT ACCESS DOORWAYS. INTERLOCKING OR | | SCISSOR STAIRS SHALL BE COUNTED AS ONE EXIT STAIRWAY. | | | | EXCEPTIONS: 2. WHERE A BUILDING IS EQUIPPED THROUGHOUT | | WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH | | SECTION FBC 903.3.1.1 OR 903.3.1.2, THE SEPARATION | | DISTANCE OF THE EXIT DOORS OR EXIT ACCESS DOORWAYS | | SHALL NOT BE LESS THAN ONE-THIRD OF THE LENGTH OF THE | | MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA SERVED. | | | | | | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: | | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. | | | | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED | | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS | | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE | | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE | | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR | | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN | | THE PERMIT PACKAGE. | | | | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-02-12 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-02-12 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-02-12 |
Time |
08:36 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2017-12-11 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-12-11 |
Time |
11:43 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-12-11 |
Time |
10:58 |
Sent To |
|
|
Notes |
2017-12-11 11:42:34 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS | | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF | | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE | | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET | | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, | | 107.2.1 | | 2. PROVIDE WIRE SIZES FROM METER CAN AND DISCONNECT TO | | NEW PANEL H. FBC 107.2.1; NEC 215.2, 215.5 | | 3. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT | | CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. | | NEC 110.10 | | 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-01-25 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-01-25 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-01-25 |
Time |
13:41 |
Sent To |
|
|
Notes |
2018-01-25 16:17:19 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1 FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE SHOP | | DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2017-11-15 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-11-15 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-11-14 |
Time |
13:56 |
Sent To |
|
|
Notes |
2017-11-15 10:23:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET A 2 - TWO EXITS ARE INDICATED FROM UNIT # 175, | | HOWEVER, IT DOES NOT APPEAR THAT THEY MEET THE | | SEPARATION REQUIREMENTS OF NFPA 101, CHAPTER 39, | | EXISTING BUSINESS OCCUPANCIES OR CHAPTER 7, MEANS OF | | EGRESS. | | | | THIS IS AN EXISTING BUSINESS OCCUPANCY; HOEVER, DUE TO | | THE SEPARATION WALL THIS IS NOT AN EXISTING SPACE AND | | REMOTENESS OF THE TWO EXISTS IS REQUIRED. | | | | 39.2.5 ARRANGEMENT OF MEANS OF EGRESS. | | 39.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN | | ACCORDANCE WITH SECTION 7.5. | | | | 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR | | EXIT DISCHARGE IS REQUIRED FROM A BUILDING OR PORTION | | THEREOF, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES | | SHALL BE REMOTELY LOCATED FROM EACH OTHER AND BE | | ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE | | HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR | | OTHER EMERGENCY CONDITION. | | | | 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT | | DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A | | DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF THE | | LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE | | BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT | | LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT | | ACCESSES, OR EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED | | IN 7.5.1.3.3 THROUGH 7.5.1.3.5. | | 7.5.1.3.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN | | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN | | ACCORDANCE WITH SECTION 9.7, THE MINIMUM SEPARATION | | DISTANCE BETWEEN TWO EXITS, EXIT ACCESSES, OR EXIT | | DISCHARGES, MEASURED IN ACCORDANCE WITH 7.5.1.3.2, | | SHALL BE NOT LESS THAN ONE-THIRD THE LENGTH OF THE | | MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR | | AREA TO BE SERVED. | | | | PLEASE PROVIDE THE DIMENSIONAL CRITERIA THAT MEETS THE | | CODE, JUSTIFY WITH CODE REFERNCES OR CORRECT. | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-02-12 |
Time |
|
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-01-19 |
Time |
17:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-12-20 |
|
|
Cont ID |
|
Sent By |
aclange |
Date |
2017-12-20 |
Time |
09:49 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2017-11-13 |
Time |
15:51 |
Sent To |
|
|
Notes |
2017-12-20 09:31:34 | TO AL DESK | | | | | 2017-11-13 15:51:57 | C13 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2017-12-20 |
|
|
Cont ID |
|
Sent By |
aclange |
Date |
2017-12-20 |
Time |
09:49 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2017-12-20 |
Time |
09:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2018-02-08 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-02-08 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-02-08 |
Time |
07:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2017-12-11 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-12-11 |
Time |
17:51 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-12-11 |
Time |
17:32 |
Sent To |
|
|
Notes |
2017-12-11 17:54:34 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | PERMIT #17110463 | | 12/11/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | PROVIDED CFMS OF OUTDOOR AIR. | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE FOR THE VAV BOXES. | | | | 3) PROVIDE KEY NOTES FOR THE SCOPE OF WORK RELATING TO | | FIRE DAMPER INSTALLATIONS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2017-12-20 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-12-20 |
Time |
08:55 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-12-20 |
Time |
08:55 |
Sent To |
|
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |