Plan Review Details - Permit 17110463
Plan Review Stops For Permit 17110463
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By aclange Date 2018-02-01 Time 10:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-17 Cont ID  
Sent By aclange Date 2017-11-17 Time 16:30 Rev Time 0.00
Received By aclange Date 2017-11-17 Time 10:15 Sent To  
Notes
2017-11-17 16:30:24 
 ****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 561-805-6718 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION
  
 1. PLEASE PROVIDE THE USE OF ROOMS 116 AND 117. THE ONE
 DIMENSION IS LESS THAN 7 FEET.
  
 FBC 1208.1 MINIMUM ROOM WIDTHS.
  
 HABITABLE SPACES, OTHER THAN A KITCHEN, SHALL BE NOT
 LESS THAN 7 FEET (2134 MM) IN ANY PLAN DIMENSION.
 KITCHENS SHALL HAVE A CLEAR PASSAGEWAY OF NOT LESS THAN
 3 FEET (914 MM) BETWEEN COUNTER FRONTS AND APPLIANCES
 OR COUNTER FRONTS AND WALLS.
  
 2. IN SUITE 110 THE NEW TENANT SEPARATION WALL HAS LEFT
 THE TWO EXITS WITHIN 13 FT. OF EACH OTHER. THE DIAGONAL
 OF THE SPACE IS APPROXIMATELY 100 FEET. SEE EXCEPTION
 2.
 FBC 1015.2 EXIT OR EXIT ACCESS DOORWAY ARRANGEMENT.
  
 REQUIRED EXITS SHALL BE LOCATED IN A MANNER THAT MAKES
 THEIR AVAILABILITY OBVIOUS. EXITS SHALL BE UNOBSTRUCTED
 AT ALL TIMES. EXIT AND EXIT ACCESS DOORWAYS SHALL BE
 ARRANGED IN ACCORDANCE WITH SECTIONS FBC 1015.2.1 AND
 1015.2.2.
  
 FBC 1015.2.1 TWO EXITS OR EXIT ACCESS DOORWAYS.
 WHERE TWO EXITS OR EXIT ACCESS DOORWAYS ARE REQUIRED
 FROM ANY PORTION OF THE EXIT ACCESS, THE EXIT DOORS OR
 EXIT ACCESS DOORWAYS SHALL BE PLACED A DISTANCE APART
 EQUAL TO NOT LESS THAN ONE-HALF OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN
 EXIT DOORS OR EXIT ACCESS DOORWAYS. INTERLOCKING OR
 SCISSOR STAIRS SHALL BE COUNTED AS ONE EXIT STAIRWAY.
  
 EXCEPTIONS: 2. WHERE A BUILDING IS EQUIPPED THROUGHOUT
 WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION FBC 903.3.1.1 OR 903.3.1.2, THE SEPARATION
 DISTANCE OF THE EXIT DOORS OR EXIT ACCESS DOORWAYS
 SHALL NOT BE LESS THAN ONE-THIRD OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA SERVED.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-02-12 Cont ID  
Sent By jpearson Date 2018-02-12 Time 10:54 Rev Time 0.00
Received By jpearson Date 2018-02-12 Time 08:36 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-11 Cont ID  
Sent By jpearson Date 2017-12-11 Time 11:43 Rev Time 0.00
Received By jpearson Date 2017-12-11 Time 10:58 Sent To  
Notes
2017-12-11 11:42:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 2. PROVIDE WIRE SIZES FROM METER CAN AND DISCONNECT TO
 NEW PANEL H. FBC 107.2.1; NEC 215.2, 215.5
 3. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE.
 NEC 110.10
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-01-25 Cont ID  
Sent By pleduc Date 2018-01-25 Time   Rev Time 0.00
Received By pleduc Date 2018-01-25 Time 13:41 Sent To  
Notes
2018-01-25 16:17:19THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1 FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-11-15 Cont ID  
Sent By pleduc Date 2017-11-15 Time   Rev Time 0.00
Received By pleduc Date 2017-11-14 Time 13:56 Sent To  
Notes
2017-11-15 10:23:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 2 - TWO EXITS ARE INDICATED FROM UNIT # 175,
 HOWEVER, IT DOES NOT APPEAR THAT THEY MEET THE
 SEPARATION REQUIREMENTS OF NFPA 101, CHAPTER 39,
 EXISTING BUSINESS OCCUPANCIES OR CHAPTER 7, MEANS OF
 EGRESS.
  
 THIS IS AN EXISTING BUSINESS OCCUPANCY; HOEVER, DUE TO
 THE SEPARATION WALL THIS IS NOT AN EXISTING SPACE AND
 REMOTENESS OF THE TWO EXISTS IS REQUIRED.
  
 39.2.5 ARRANGEMENT OF MEANS OF EGRESS.
 39.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH SECTION 7.5.
  
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS REQUIRED FROM A BUILDING OR PORTION
 THEREOF, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES
 SHALL BE REMOTELY LOCATED FROM EACH OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR
 OTHER EMERGENCY CONDITION.
  
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A
 DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF THE
 LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT
 LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT
 ACCESSES, OR EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED
 IN 7.5.1.3.3 THROUGH 7.5.1.3.5.
 7.5.1.3.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7, THE MINIMUM SEPARATION
 DISTANCE BETWEEN TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES, MEASURED IN ACCORDANCE WITH 7.5.1.3.2,
 SHALL BE NOT LESS THAN ONE-THIRD THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED.
  
 PLEASE PROVIDE THE DIMENSIONAL CRITERIA THAT MEETS THE
 CODE, JUSTIFY WITH CODE REFERNCES OR CORRECT.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-02-12 Time   Rev Time 0.00
Received By cpuell Date 2018-01-19 Time 17:06 Sent To  
Notes
2018-01-22 17:06:45C13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-20 Cont ID  
Sent By aclange Date 2017-12-20 Time 09:49 Rev Time 0.00
Received By aclange Date 2017-11-13 Time 15:51 Sent To  
Notes
2017-12-20 09:31:34TO AL DESK
  
  
2017-11-13 15:51:57C13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-12-20 Cont ID  
Sent By aclange Date 2017-12-20 Time 09:49 Rev Time 0.00
Received By aclange Date 2017-12-20 Time 09:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-02-08 Cont ID  
Sent By ccole Date 2018-02-08 Time 09:09 Rev Time 0.00
Received By ccole Date 2018-02-08 Time 07:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-11 Cont ID  
Sent By ccole Date 2017-12-11 Time 17:51 Rev Time 0.00
Received By ccole Date 2017-12-11 Time 17:32 Sent To  
Notes
2017-12-11 17:54:341ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17110463
 12/11/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) PROVIDE AN EQUIPMENT SCHEDULE FOR THE VAV BOXES.
  
 3) PROVIDE KEY NOTES FOR THE SCOPE OF WORK RELATING TO
 FIRE DAMPER INSTALLATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-12-20 Cont ID  
Sent By gjohnson Date 2017-12-20 Time 08:55 Rev Time 0.00
Received By gjohnson Date 2017-12-20 Time 08:55 Sent To  
Notes
***NONE***