Plan Review Details - Permit 17110427
Plan Review Stops For Permit 17110427
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-07 Cont ID  
Sent By cthroop Date 2018-06-07 Time 15:58 Rev Time 0.00
Received By cthroop Date 2018-06-07 Time 14:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-07 Cont ID  
Sent By rmcdouga Date 2017-12-07 Time 13:11 Rev Time 0.00
Received By rmcdouga Date 2017-12-06 Time 18:52 Sent To E
Notes
2017-12-07 09:01:02PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF A DRAINAGE PLAN WITH ELEVATIONS
 TO SHOW COMPLIANCE WITH FBC-R401.3. SURFACE DRAINAGE
 SHALL BE DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER
 APPROVED POINT OF COLLECTION THAT DOES NOT CREATE A
 HAZARD. LOTS SHALL BE GRADED TO DRAIN SURFACE WATER
 AWAY FROM FOUNDATION WALLS. THE GRADE SHALL FALL A
 MINIMUM OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET
 (3048 MM). EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR
 OTHER PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF
 FALL WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL
 BE CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE
 STRUCTURE. IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM)
 OF THE BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
 THIS INFORMATION IS REQUIRED ON THE SITE PLAN PER FBC
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES AND, AS APPLICABLE,
 FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN FLOOD
 ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE BOUNDARY LINE SURVEY.
 IN THE CASE OF DEMOLITION, THE SITE PLAN SHALL SHOW
 CONSTRUCTION TO BE DEMOLISHED AND THE LOCATION AND SIZE
 OF EXISTING STRUCTURES AND CONSTRUCTION THAT ARE TO
 REMAIN ON THE SITE OR PLOT. THE BUILDING OFFICIAL IS
 AUTHORIZED TO WAIVE OR MODIFY THE REQUIREMENT FOR A
 SITE PLAN WHEN THE APPLICATION FOR PERMIT IS FOR
 ALTERATION OR REPAIR OR WHEN OTHERWISE WARRANTED.
  
 2) SPECIFY THE SIZE OF THE ATTIC ACCESS ON THE PLANS.
 FBC-R807.1 ATTIC ACCESS, THE ROUGH-FRAMED OPENING SHALL
 NOT BE LESS THAN 22 INCHES BY 30 INCHES (559 MM BY 762
 MM) AND SHALL BE LOCATED IN A HALLWAY OR OTHER READILY
 ACCESSIBLE LOCATION.
  
 3) ON SHEET 4 - 4 OF THE PLANS, THE ROOF FRAMING PLAN
 SPECIFIES (2) SIMPSON HETAL 20 ANCHORS FOR THE GIRDER
 TRUSS WITH AN UPLIFT OF 3600 LBS. THIS IS NOT CORRECT.
 THE SIMPSON CATALOG HAS AN UPLIFT LOAD CAPACITY OF 2700
 LBS. FOR (2) HETA ANCHORS ON A TWO PLY TRUSS. PLEASE
 CORRECT.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-21 Cont ID  
Sent By ppetty Date 2018-05-21 Time 12:48 Rev Time 0.00
Received By ppetty Date 2018-05-21 Time 12:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-12-07 Cont ID  
Sent By jleahy Date 2017-12-07 Time 13:47 Rev Time 0.00
Received By jleahy Date 2017-12-07 Time 13:47 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-07 Cont ID  
Sent By cthroop Date 2018-06-07 Time 15:58 Rev Time 0.00
Received By cthroop Date 2018-05-10 Time 10:44 Sent To I
Notes
2018-05-14 10:43:57R18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-07 Cont ID  
Sent By jleahy Date 2017-12-07 Time 13:47 Rev Time 0.00
Received By jleahy Date 2017-11-09 Time 09:12 Sent To  
Notes
2017-11-13 09:12:56R17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-06-07 Cont ID  
Sent By cthroop Date 2018-06-07 Time 15:57 Rev Time 0.00
Received By cthroop Date 2018-06-07 Time 15:56 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-06 Cont ID  
Sent By rmcdouga Date 2017-12-06 Time 18:52 Rev Time 0.00
Received By rmcdouga Date 2017-12-06 Time 18:52 Sent To  
Notes
2017-12-06 18:53:29BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-05-24 Cont ID  
Sent By ccole Date 2018-05-24 Time 12:36 Rev Time 0.00
Received By ccole Date 2018-05-24 Time 12:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-04 Cont ID  
Sent By ccole Date 2017-12-04 Time 11:26 Rev Time 0.00
Received By ccole Date 2017-12-04 Time 11:26 Sent To  
Notes
2017-12-04 11:41:431ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110427
 12/4/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: THE AC PLAN INDICATES A TOTAL OF 1420
 CFMS OF CONDITIONED AIR TO BE SUPPLIED BY THE 3.0-TON
 SYSTEM. PROVIDE PRODUCT DATA FROM THE AC MANUFACTURER
 TO CONFIRM THE SYSTEM CAN SUPPLY THAT MUCH AIR.
  
 2) M-1: PROVIDE A PRODUCT DATA SHEET FOR THE 3" FLEX
 DUCT. TYPICALLY, THE SMALLEST FLEX DUCT AVAILABLE IS A
 4"
  
 3) THE OWNER/AGENT SHALL SIGN THE ENERGY COMPLIANCE
 FORM R405-2014.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-12-01 Cont ID  
Sent By tklarge Date 2017-12-01 Time 08:53 Rev Time 0.00
Received By tklarge Date 2017-12-01 Time 08:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-05-18 Cont ID  
Sent By llouie Date 2018-05-18 Time   Rev Time 0.00
Received By llouie Date 2018-05-18 Time   Sent To  
Notes
2018-05-18 15:47:46ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) SEPERATE PERMIT APPLICATIONS REQUIRED FOR
 LANDSCAPING AND DRIVEWAY PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY.

Review Stop Z ZONING
Rev No 1 Status F Date 2017-11-17 Cont ID  
Sent By LL Date 2017-11-17 Time   Rev Time  
Received By llouie Date 2017-11-17 Time   Sent To  
Notes
2017-11-17 10:03:35** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PLEASE DIMENSION THE PROPOSED DRIVEWAY. THE
 DRIVEWAY CANNOT EXCEED 20 FT. IN WIDTH. [ZLDR S.94-312]
  
 2.) SHOW SETBACK DIMENSION FROM THE DRIVEWAY TO THE
 SIDE PROPERTY LINE. THE DRIVEWAY SHALL BE SETBACK AT
 LEAST 3 FT. FROM THE SIDE PROPERTY LINE. [ZLDR
 S.94-482(D)]
  
 3.) WHAT IS THE WIDTH OF THE PROPOSED SIDEWALK ON THE
 PROPERTY? WHAT IS THE SETBACK DISTANCE FROM THE SIDE
 PROPERTY LINE? PLEASE PROVIDE DIMENSIONS IN THE SITE
 PLAN.
  
 4.) 1,000 SQ. FT. OF FRONT YARD AREA (WITHIN THE FIRST
 25 FT. OF THE PROPERTY LINE FROM 55TH STREET) SHALL BE
 LANDSCAPED LIVING PLANT MATERIAL. PLEASE DEMONSTRATE
 COMPLIANCE BY PROVIDING DIMENSIONS AND CALCULATIONS.
 [ZLDR S.94-482(A)]
  
 5.) SHOW SETBACK DISTANCE FROM THE LOCATION OF THE
 PROPOSED A/C UNIT TO THE PROPERTY LINES. PLEASE NOTE
 THAT THE A/C PAD SHALL NOT PROJECT MORE THAN 4 FT. INTO
 A REQUIRED SETBACK. [ZLDR S.94-305]
  
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * SEPARATE PERMIT REQUIRED FOR THE PROPOSED NEW
 DRIVEWAY.
  
 * A SEPARATE LANDSCAPE PERMIT IS REQUIRED. A
 CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED UNTIL A
 LANDSCAPE PERMIT HAS BEEN SUBMITTED TO THE CONSTRUCTION
 SERVICES DEPARTMENT.
  
 * ZONE: SF7
  