Plan Review Details - Permit 17110405
Plan Review Stops For Permit 17110405
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-01-11 Cont ID  
Sent By rmcdouga Date 2018-01-11 Time 17:57 Rev Time 0.00
Received By rmcdouga Date 2018-01-11 Time 15:16 Sent To  
Notes
2018-01-11 17:57:56APPROVED WITH EXCEPTIONS
  
 1) THE FIELD INSPECTOR SHALL VERIFY THAT THE
 REPLACEMENT BEDROOM WINDOW PROVIDES FOR AN EQUAL OR
 GREATER OPENING AREA THAN THE EXISTING WINDOW AND
 COMPLIES WITH FBC EXISTING BUILDING SECTION 704.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-12-15 Cont ID  
Sent By rmcdouga Date 2017-12-15 Time 18:47 Rev Time 0.00
Received By rmcdouga Date 2017-12-15 Time 18:47 Sent To I
Notes
2017-12-15 18:47:17PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING (PREVIOUS COMMENTS WERE NOT
 ADDRESSED) SUBMIT A NARRATIVE EXPLANING HOW EACH OF THE
 COMMENTS HAS BEEN ADDRESSED.
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R310.1 REQUIRES EVERY SLEEPING ROOM TO HAVE AT
 LEAST ONE OPERABLE EMERGENCY ESCAPE AND RESCUE OPENING.
 IN ORDER TO VERIFY THIS REQUIREMENT, PROVIDE A FLOOR
 PLAN WITH THE ROOMS LABELED. SPECIFY THE TYPE AND SIZE
 OF THE EXISTING WINDOWS ON THE PLANS. IF WINDOWS ARE
 CONNECTED TO EACH OTHER USING MULLIONS SPECIFY THE SIZE
 AND NUMBER OF THE WIDOWS IN THE OPENING. FBC 107.2.1
  
 2) A PRODUCT APPROVAL FOR STRUCTURAL MULLIONS WAS
 SUBMITTED. INDICATE THE CONFIGURATION OF THE WINDOWS
 WHERE THIS WILL BE INSTALLED. IN ORDER TO REVIEW THE
 MULLIONS FOR CODE COMPLIANCE THE MULLION SPAN AND
 TRIBUTARY WIDTH ARE REQUIRED.FBC - R301.2.1
  
 3) THE PRODUCT CERTIFICATION AND INSTALLATION
 INSTRUCTIONS THAT ARE ATTACHED TO THE HORIZONTAL
 SLIDING WINDOW FL16804 ARE NOT THE ONES FOR THE XO, OX
 CONFIGURATIONS THAT WERE CIRCLED BY YOU ON PAGE 2 OF
 THE PRODUCT APPROVAL. PLEASE CORRECT. FBC 107.2.1
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-14 Cont ID  
Sent By rmcdouga Date 2017-11-14 Time 08:45 Rev Time 0.00
Received By rmcdouga Date 2017-11-13 Time 19:01 Sent To I
Notes
2017-11-14 08:45:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R310.1 REQUIRES EVERY SLEEPING ROOM TO HAVE AT
 LEAST ONE OPERABLE EMERGENCY ESCAPE AND RESCUE OPENING.
 IN ORDER TO VERIFY THIS REQUIREMENT, PROVIDE A FLOOR
 PLAN WITH THE ROOMS LABELED. SPECIFY THE TYPE AND SIZE
 OF THE EXISTING WINDOWS ON THE PLANS. IF WINDOWS ARE
 CONNECTED TO EACH OTHER USING MULLIONS SPECIFY THE SIZE
 AND NUMBER OF THE WIDOWS IN THE OPENING. FBC 107.2.1
  
 2) A PRODUCT APPROVAL FOR STRUCTURAL MULLIONS WAS
 SUBMITTED. INDICATE THE CONFIGURATION OF THE WIDOWS
 WEAR THIS WILL BE INSTALLED. IN ORDER TO REVIEW THE
 MULLIONS FOR CODE COMPLIANCE THE MULLION SPAN AND
 TRIBUTARY WIDTH ARE REQUIRED.FBC - R301.2.1
  
 3) THE PRODUCT CERTIFICATION AND INSTALLATION
 INSTRUCTIONS THAT ARE ATTACHED TO THE HORIZONTAL
 SLIDING WINDOW FL16804 ARE NOT THE ONES FOR THE XO, OX
 CONFIGURATIONS THAT WERE CIRCLED BY YOU ON PAGE 2 OF
 THE PRODUCT APPROVAL. PLEASE CORRECT. FBC 107.2.1
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-11 Cont ID  
Sent By rmcdouga Date 2018-01-11 Time 17:58 Rev Time 0.00
Received By rmcdouga Date 2018-01-09 Time 13:46 Sent To I
Notes
2018-01-10 13:46:15RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-15 Cont ID  
Sent By rmcdouga Date 2017-12-15 Time 18:47 Rev Time 0.00
Received By rmcdouga Date 2017-12-12 Time 11:44 Sent To  
Notes
2017-12-13 11:45:13RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-14 Cont ID  
Sent By rmcdouga Date 2017-11-14 Time 08:45 Rev Time 0.00
Received By rmcdouga Date 2017-11-09 Time 09:32 Sent To  
Notes
2017-11-13 09:33:07BLDG MISC 1