Plan Review Details - Permit 17110321
Plan Review Stops For Permit 17110321
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-11-16 Cont ID  
Sent By aclange Date 2017-11-16 Time 16:56 Rev Time 0.00
Received By aclange Date 2017-11-15 Time 15:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-11-29 Cont ID  
Sent By jpearson Date 2017-11-29 Time 08:33 Rev Time 0.00
Received By jpearson Date 2017-11-29 Time 07:57 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-14 Cont ID  
Sent By pleduc Date 2017-11-14 Time   Rev Time 0.00
Received By pleduc Date 2017-11-13 Time 15:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-01-12 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-05 Time 08:20 Sent To  
Notes
2018-01-09 08:20:57RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-29 Cont ID  
Sent By jpearson Date 2017-11-29 Time 08:34 Rev Time 0.00
Received By jpearson Date 2017-11-08 Time 13:34 Sent To  
Notes
2017-11-09 13:34:17B27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-11-16 Cont ID  
Sent By aclange Date 2017-11-16 Time 16:57 Rev Time 0.00
Received By aclange Date 2017-11-16 Time 16:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-01-12 Cont ID  
Sent By ccole Date 2018-01-12 Time 11:19 Rev Time 0.00
Received By ccole Date 2018-01-12 Time 11:19 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-17 Cont ID  
Sent By ccole Date 2017-11-17 Time 16:20 Rev Time 0.00
Received By ccole Date 2017-11-17 Time 16:20 Sent To  
Notes
2017-11-17 16:25:061ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODE
 PERMIT #17110321
 11/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) M2.1: PROVIDE THE FLEX DUCT SIZES
  
 3) M2.1: PLEASE CLARIFY IF THE VAV BOX BY ROOM 105 IS
 NEW OR EXISTING.
  
 4) INDICATE IF THERE ARE ANY COOKING APPLIANCES IN THE
 NEW CAFE AND PROVIDE EXHAUST VENTILATION WHERE
 REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-11-28 Cont ID  
Sent By gjohnson Date 2017-11-28 Time 15:28 Rev Time 0.00
Received By gjohnson Date 2017-11-28 Time 15:15 Sent To  
Notes
***NONE***