Plan Review Details - Permit 17110268
Plan Review Stops For Permit 17110268
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-12-14 Cont ID  
Sent By cthroop Date 2017-12-14 Time 10:31 Rev Time 0.00
Received By cthroop Date 2017-12-14 Time 10:31 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-20 Cont ID  
Sent By cthroop Date 2017-11-20 Time 13:33 Rev Time 0.00
Received By cthroop Date 2017-11-18 Time 07:53 Sent To  
Notes
2017-11-20 13:45:35BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. BASED ON THE SUBMITTED SURVEY, DATED MARCH 7, 2016,
 THE PROPOSED GENERATOR PAD ELEVATION IS ESTABLISHED AT
 8.00 FEET NGVD 1929, WHICH IS APPROX. 6.5 FEET NAVD88.
  
 2. AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY
 MANAGEMENT AGENCY (FEMA) ESTABLISHED A NEW FLOOD
 INSURANCE RATE MAP (FIRM) UTILIZING THE RECENTLY
 COMPLETED FLOOD HAZARD DETERMINATION (FHD) FOR THE CITY
 OF WEST PALM BEACH, FL.
  
 3. ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED
 ON NAVD88 DATUM. EFFECTIVE OCT. 5, 2017, THE CITY OF
 WEST PALM BEACH, BY ORDINANCE, BEGAN ENFORCEMENT OF A
 TWO FOOT FREEBOARD ABOVE THE (BFE).
  
 4. YOU MAY SUBMIT A NEW SURVEY SHOWING ALL EXISTING AND
 PROPOSED ELEVATIONS BASED ON NAVD88 DATUM PLUS TWO FEET
 OF FREEBOARD OR THE ENGINEER OF RECORD (EOR) MAY ADD A
 STATEMENT TO THE STRUCTURAL PLAN THAT THE DESIGN FLOOD
 ELEVATION (DFE) WILL BE 8.00 FEET NAVD88 BASED ON THE
 (BFE) OF 6.00 FEET FOR FLOOD ZONE AE PLUS TWO FEET OF
 FREEBOARD.
  
 5. PLEASE IDENTIFY THE SIZE AND PLACEMENT OF THE
 HORIZONTAL RE-ENFORCING AT THE BOTTOM OF THE FOOTING.
  
 6. PROVIDE GENERATOR MANUFACTURERS INSTALLATION
 INSTRUCTIONS FOR REVIEW. CANNOT DETERMINE IF PROPOSED
 SLAB ON GRADE IS SUFFICIENT FOR PROPOSED GENERATOR.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-20 Cont ID  
Sent By cthroop Date 2017-11-20 Time 14:18 Rev Time 0.00
Received By cthroop Date 2017-11-07 Time 10:09 Sent To I
Notes
2017-11-08 10:09:54ROUTED TO ZONING

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2017-12-14 Cont ID  
Sent By cthroop Date 2017-12-14 Time 10:31 Rev Time 0.00
Received By cthroop Date 2017-12-14 Time 10:31 Sent To  
Notes
2017-12-14 10:32:57GENERATOR PAD IS CONSIDERED AN ACCESS. TO THE RES-ADD
 PERMIT # 16070876.

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2017-11-16 Time   Rev Time 0.00
Received By ajones Date 2017-11-08 Time 15:58 Sent To B
Notes
2017-11-16 14:38:55 
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved