Plan Review Details - Permit 17110117
Plan Review Stops For Permit 17110117
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-05-26 Cont ID  
Sent By shill Date 2018-05-26 Time 11:43 Rev Time 0.00
Received By shill Date 2018-05-25 Time 11:29 Sent To  
Notes
2018-05-26 11:51:26****PROVISO****
 ****ISSUED AT APPLICANT'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 RAMP APPEARS TO EITHER REQUIRE HANDRAILS OR FOR RISE TO
 BE REDUCED. ALSO, THE WEST SIDE OF THE RAMP HAS A SMALL
 CHANGE IN ELEVATION BETWEEN THE SEATING AREA AND RAMP;
 NOT CLEAR WHAT THE SIZE THIS IS.
  
 PLEASE CONTACT ME TO DISCUSS OPTIONS PRIOR TO
 INSTALLATION. A REVISION MAY BE REQUIRED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-05-16 Cont ID  
Sent By shill Date 2018-05-16 Time 11:55 Rev Time 0.00
Received By shill Date 2018-05-12 Time 08:44 Sent To  
Notes
2018-05-16 12:00:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW IS NOT ENTIRELY COMPLETE, BUT I'LL WORK
 WITH APPLICANT VIA EMAIL TO GET ALL OUTSTANDING ISSUES
 RESOLVED.
  
 WE DISAGREE THAT THIS IS STRUCTURALLY INFEASIBLE; A
 PLAN WILL BE SENT VIA EMAIL TO MIGUEL (ARCHITECT'S
 OFFICE).
  
 AS DISCUSSED, PLEASE PROVIDE A DETAILED COST BREAKDOWN
 COST TO PROVIDE AN ACCESSIBLE ENTRANCE AND PROJECT COST
 (DISPROPORTIONATE COST).
  
 ALSO DISCUSSED WAS THE ISSUE OF: WE BELIEVE IT IS
 POSSIBLE THAT THERE WERE STEPS AT THIS LOCATION, AND
 WAS CONVERTED WITHOUT A PERMIT TO A NON COMPLIANT RAMP
 (OVER 14% SLOPE). THEREFORE, THE UNSAFE ENTRANCE IS NOT
 GRANDFATHERED IN VIA EXISTING BUILDING CODE AS IT WAS
 NOT BUILT IN COMPLIANCE WITH CODE IN EFFECT WHEN
 BUILDING WAS BUILT.
  
 A PRELIMINARY DETAIL WILL BE REVIEWED VIA EMAIL.
  
 FOR CODE SECTIONS, SEE FIRST REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-12 Cont ID  
Sent By jwitmer Date 2018-04-12 Time 16:36 Rev Time 0.00
Received By jwitmer Date 2018-04-12 Time 11:24 Sent To  
Notes
2018-04-12 16:36:052014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17110117
 ADD: 123 DATURA ST.
 CONT: FINE LINE CONSTRUCTION
 TEL: 561-582-7880
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. APRIL 12/ 2018
 ACTION: DENIED
  
 1) PLEASE SUBMIT THE PERMIT APPLICATION AND PLANS NOTED
 UNDER THE PROPER STREET ADDRESS AND TENANT ADDRESS.
 WHEN VIEWING THE TENANT SITE UNDER THE PALM BEACH
 COUNTY PROPERTY APPRAISERS WEBSITE THE BUILDING ADDRESS
 IS 125 DATURA, THE TENANT SPACE OR SUITE WOULD BE 123
 DATURA. PLEASE ADDRESS CORRECTLY.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2014 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2) SHEET ALS1.1:
  
 2A) LIST THE OCCUPANCY AS AN A-2 OCCUPANCY AND A LEVEL
 2 ALTERATION. PLEASE NOTE THE LAST KNOWN USE (LICENSED/
 BUSINESS TAX) WAS BEE ORGANICS AS A MERCANTILE
 OCCUPANCY. PLEASE NOTE THIS IS A CHANGE OF OCCUPANCY
 AND MEET THE REQUIREMENTS OF SECTION 1001.3.1 PARTIAL
 CHANGE OF OCCUPANCY CLASSIFICATION OF THE 2014 EXISTING
 BUILDING CODE.
 1001.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY.
 PLEASE UPDATE THE PLANS TO ILLUSTRATE NOT A LEVEL II
 ALTERATION BUT A CHANGE OF OCCUPANCY UNDER CHAPTER 10
 OF THE EXISTING BUILDING CODE.
  
 2B) PLEASE PROVIDE A CODE ANALYSIS OF THE BUILDING AND
 TENANT SPACE. PROVIDE THE FOLLOWING INFORMATION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILD
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503)
 SQUARE FOOTAGE OF BUILDING
 IS THE BUILDING FIRE SPRINKLERED? IS IT REQUIRED?
 OCCUPANT LOAD PER AREA OR USE OF THE TENANT SPACE A
 THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 2C) THE PLANS ARE SILENT TO HOW TENANT AND OCCUPANCY
 SEPARATION IS HANDLED?
 2014 FBC-EXISTING BUILDING CODE SECTIONS; 1012.1.1
 COMPLIANCE WITH CHAPTER 9 .
 THE REQUIREMENTS OF CHAPTER 9 SHALL BE APPLICABLE
 THROUGHOUT THE BUILDING FOR THE NEW OCCUPANCY
 CLASSIFICATION BASED ON THE SEPARATION CONDITIONS SET
 FORTH IN SECTIONS 1012.1.1.1 AND 1012.1.1.2.
 1012.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT
 SEPARATION.
 1012.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH
 SEPARATION.
  
 2D) 2014 EXISTING BUILDING CODE 1012.4.2 MEANS OF
 EGRESS FOR CHANGE OF USE TO EQUAL OR LOWER HAZARD
 CATEGORY. WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS
 MADE TO AN EQUAL OR LESSER HAZARD CATEGORY (HIGHER
 NUMBER) AS SHOWN IN TABLE 1012.4, EXISTING ELEMENTS OF
 THE MEANS OF EGRESS SHALL COMPLY WITH THE REQUIREMENTS
 OF SECTION 905 FOR THE NEW OCCUPANCY CLASSIFICATION.
 NEWLY CONSTRUCTED OR CONFIGURED MEANS OF EGRESS SHALL
 COMPLY WITH THE REQUIREMENTS OF CHAPTER 10 OF THE
 FLORIDA BUILDING CODE, BUILDING.
 PLEASE NOTE THE TABLE AND CHAIR LAYOUT GIVEN HAS A
 HIGHER OCCUPANT LOAD COUNT IF FOR BENCH SEATING IT IS
 TAKEN AT 18 INCHES PER OCCUPANT AND TABLES 6.5 FEET
 LONG ALL TABLES TO BE REPRESENTED WITH 6 OCCUPANTS PER
 TABLE, THE (2) BANQUETS IN THE WINDOW BENCH SEATING AT
 18 INCHES AND SEATING ON THE OPPOSITE SIDE OF THE TABLE
 PLUS AN ADDITIONAL 6 PERSON TABLE BEHIND THE HOSTESS
 STATION. THE OTHER ISSUE IS THE KITCHEN IS TAKEN AT
 1019 SQ. FT. / 200= 4 IT WOULD EQUAL 5.095 OCCUPANTS
 WITH FRACTIONS YOU ALWAYS ROUND UP. THE COOLER IS
 STORAGE OCCUPANCY AND AN OCCUPANT LOAD OF 1 SHOULD BE
 ADDED OR AN OCCUPANT LOAD OF 68 AND WITH 84 OCCUPANTS
 WHEN SEASONAL SEATING IS CONSIDERED FOR THE REQUIRED
 PLUMBING FIXTURE COUNT. 2014 FBC-B 1004.2.
  
 2E) WITH AN OCCUPANT LOAD OF 50 OR MORE (2) MEANS OF
 EGRESS ARE REQUIRED. 2014 FBC-B TABLE 1015.1.
  
 2F) WITH AN OCCUPANT LOAD OF 50 OR MORE (2) MEANS OF
 EGRESS ARE REQUIRED THE 2ND MEANS OF EGRESS CANNOT BE
 THROUGH THE KITCHEN. 2014 FBC-B 1014.2 EGRESS THROUGH
 INTERVENING SPACES. (4) EGRESS SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED FOR
 SIMILAR PURPOSES.
  
 2G) 2014 FBC-ACCESSIBILITY CODE. 206.4.1 PUBLIC
 ENTRANCES. (DOORWAYS) IN ADDITION TO ENTRANCES REQUIRED
 BY 206.4.2 THROUGH 206.4.9, AT LEAST 60 PERCENT OF ALL
 PUBLIC ENTRANCES SHALL COMPLY WITH 404. 2 X 0.60= 1.2
 OR 2 MEANS OF ACCESSIBLE ENTRANCES / EXITS.
  
 2H) PLEASE PROVIDE THE RISE AND RUN OF THE EXISTING
 RAMP AT THE FRONT ENTRY, IT WOULD APPEAR IT IS STEEPER
 THAN ALLOWED BY THE CODE. PLEASE REVIEW FOR EXISTING
 BUILDINGS THE MAXIMUM RAMP SLOPE AND RISE FOR EXISTING
 BUILDINGS 2014 FBC-ACCESSIBILITY CODE TABLE 405.2.
  
 2I) THE PLANS INDICATE A DOOR AND STAIRWAY INTO THE
 KITCHEN, PLEASE SHOW COMPLIANCE WITH LANDING. 2014
 FBC-B 1009.8 STAIRWAY LANDINGS. THERE SHALL BE A FLOOR
 OR LANDING AT THE TOP AND BOTTOM OF EACH STAIRWAY. THE
 WIDTH OF LANDINGS SHALL NOT BE LESS THAN THE WIDTH OF
 STAIRWAYS THEY SERVE. EVERY LANDING SHALL HAVE A
 MINIMUM WIDTH MEASURED PERPENDICULAR TO THE DIRECTION
 OF TRAVEL EQUAL TO THE WIDTH OF THE STAIRWAY. WHERE THE
 STAIRWAY HAS A STRAIGHT RUN THE DEPTH NEED NOT EXCEED
 48 INCHES.
  
 2J) THE PLANS DO NOT SHOW ANY HANDRAILS ON EITHER SIDE
 OF THE STAIR. 2014 EXISTING BUILDING CODE 805.9.1
 MINIMUM REQUIREMENT. EVERY REQUIRED EXIT STAIRWAY THAT
 IS PART OF THE MEANS OF EGRESS FOR ANY WORK AREA AND
 THAT HAS THREE OR MORE RISERS AND IS NOT PROVIDED WITH
 AT LEAST ONE HANDRAIL, OR IN WHICH THE EXISTING
 HANDRAILS ARE JUDGED TO BE IN DANGER OF COLLAPSING,
 SHALL BE PROVIDED WITH HANDRAILS FOR THE FULL LENGTH OF
 THE RUN OF STEPS ON AT LEAST ONE SIDE.
  
 2K) SHEET ALS1.1 SHOWS STAIRS GOING TO THE KITCHEN BUT
 NO VERTICAL ACCESSIBILITY, PLEASE SHOW COMPLIANCE WITH:
 2014 FBC-ACCESSIBILITY CODE 201.1.1 VERTICAL
 ACCESSIBILITY. SECTIONS 553.501-553.513, F.S., AND THE
 ADA STANDARDS FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE
 OWNER OF ANY BUILDING, STRUCTURE OR FACILITY GOVERNED
 BY THOSE SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR: 3)
 OCCUPIABLE SPACES AND ROOMS THAT ARE NOT OPEN TO THE
 PUBLIC AND THAT HOUSE NO MORE THAN FIVE PERSONS. WITH
 THE STORAGE AREA THE OCCUPANT LOAD OF THE KITCHEN WOULD
 BE 6 PLUS THE SERVERS.
  
 2L) THE EXIT FROM THE KITCHEN ITSELF IS NOT AN
 ACCESSIBLE MEANS OF EGRESS. 2014 FBC-ACCESSIBILITY
 CODE. 206.4.1 PUBLIC ENTRANCES. (DOORWAYS) IN ADDITION
 TO ENTRANCES REQUIRED BY 206.4.2 THROUGH 206.4.9, AT
 LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY
 WITH 404. 2 X 0.60= 1.2 OR 2 MEANS OF ACCESSIBLE
 ENTRANCES / EXITS.
  
 2M) THE DOOR THAT LEADS INTO THE KITCHEN DOES NOT HAVE
 THE 18 INCHES CLEARANCE ON THE LATCH SIDE OF THE DOOR.
 ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE FOR SIDE CLEARANCE.
  
 2N) THE LIFE SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH
 THE 2014 FBC-ACCESSIBILITY CODE;
 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
 TOTAL SEATING 84 X 0.05 = 4.2, ROUND UP TO 5.
  
 2O) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2P) 206.2.5 RESTAURANTS AND CAFETERIAS. IN RESTAURANTS
 AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL BE PROVIDED
 TO ALL DINING AREAS, INCLUDING RAISED OR SUNKEN DINING
 AREAS, AND OUTDOOR DINING AREAS.
  
 2R) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 2R)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2R)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) PLEASE NOTE UNDER THE ADDRESS OF 123 DATURA NOR 125
 DATURA DOES THE CITY RECORDS SHOW A WALK IN COOLER/
 FREEZER PLEASE PROVIDE PERMIT FOR WORK? 107.2.1.3
  
 4A) THE M-2 SHEET SHOWS AN A/C STAND, IS THIS A GENERIC
 DETAIL OR IS THERE GOING TO BE A ACTUAL A/C STAND
 INSTALLED ON THE ROOF? IF SO SHOW COMPLIANCE WITH:
 2014 / 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS
  
 4B) THE ROOF TOP A/C STAND SUBMIT A PRODUCT APPROVAL
 REPORT. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS
 CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP
 COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT
 VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND
 TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY
 THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT.
  
 4C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4D) PLEASE ALSO PROVIDE THE WIND DESIGN CRITERIA. 2014
 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-14 Cont ID  
Sent By aclange Date 2017-11-14 Time 10:40 Rev Time 0.00
Received By aclange Date 2017-11-14 Time 07:47 Sent To  
Notes
2017-11-14 10:45:06ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6667 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION
  
 1. THE PLANS SUBMITTED DO NOT CLEARLY SHOW EXISTING
 AREAS AND AREAS OF NEW WORK.
  
 1A. THE LIFE SAFETY PLAN SHOWS NEW WALLS AROUND THE
 KITCHEN AREA BUT ARE NOT SHOWN ON A1.0, E1 OR P1.
  
 1B. NO WALL DETAIL OR DOOR SCHEDULE PROVIDED.
  
 1C. PLANS DO NOT HAVE DIMENSIONS SHOWN.
  
 INSUFFICIENT INFORMATION SUBMITTED FOR PLAN REVIEW.
 SUBMIT PLANS SHOWING THE LOCATIONS AND TYPE OF WORK TO
 BE COMPLETED.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2. EXIT ACCESS SHOWN IS GOING THROUGH KITCHEN AREA.
  
 FBC 1014.2, FBC 107.2.3 EGRESS THROUGH INTERVENING
 SPACES. EGRESS THROUGH INTERVENING SPACES SHALL COMPLY
 WITH THIS SECTION. 4. EGRESS SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED FOR
 SIMILAR PURPOSES.
  
 3. DOORS ON ACCESSIBLE ROUTES. FRONT DOOR SHALL COMPLY
 WITH THE FOLLOWING SECTION FOR RECESSED DOORS.
  
 FBC ACCESSIBILITY 404.2.4.3 RECESSED DOORS AND GATES.
  
 MANEUVERING CLEARANCES FOR FORWARD APPROACH SHALL BE
 PROVIDED WHEN ANY OBSTRUCTION WITHIN 18 INCHES (455 MM)
 OF THE LATCH SIDE OF A DOORWAY PROJECTS MORE THAN 8
 INCHES (205 MM) BEYOND THE FACE OF THE DOOR, MEASURED
 PERPENDICULAR TO THE FACE OF THE DOOR OR GATE.
 REAR DOOR SHALL COMPLY WITH FBC ACCESSIBILITY 404.2.4
 MANEUVERING CLEARANCES.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH FBC ACCESSIBILITY 404.2.4. MANEUVERING
 CLEARANCES SHALL EXTEND THE FULL WIDTH OF THE DOORWAY
 AND THE REQUIRED LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 FBC ACCESSIBILITY 404.2.4.1 SWINGING DOORS AND GATES.
 SWINGING DOORS AND GATES SHALL HAVE MANEUVERING
 CLEARANCES COMPLYING WITH TABLE 404.2.4.1. SEE DETAIL
 (C).
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-05-22 Cont ID  
Sent By ppetty Date 2018-05-22 Time 13:51 Rev Time 0.00
Received By ppetty Date 2018-05-22 Time 13:43 Sent To  
Notes
2018-05-22 13:51:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED
 7. CORRECTED
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED
  
 NEW COMMENT:
  
 13. IT APPEARS THAT THERE IS A TABLE IN FRONT OF
 ELECTRICAL PANELS. CLEARANCE IN FRONT OF PANELS IS
 REQUIRED PER NEC, PROVIDE CORRECTION. NEC 110.26
 14. CORRECTED
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER ,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-05-15 Cont ID  
Sent By jpearson Date 2018-05-15 Time 09:27 Rev Time 0.00
Received By jpearson Date 2018-05-15 Time 08:25 Sent To  
Notes
2018-05-22 13:47:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED
 7. CORRECTED
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED
  
 NEW COMMENT:
  
 13. IT APPEARS THAT THERE IS A TABLE IN FRONT OF
 ELECTRICAL PANELS. CLEARANCE IN FRONT OF PANELS IS
 REQUIRED PER NEC, PROVIDE CORRECTION. NEC 110.26
 14. CORRECTED
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER ,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  
  
2018-05-15 09:27:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED. FBC CE 405.2.2, 405.2.2.2
 (NOT PROVIDED. A GENERAL NOTE IS NOT ACCEPTABLE,
 PROVIDE DETAILS OF LIGHTING CONTROL ON PLAN.)
 7. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1 (NOT
 PROVIDED.)
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. PROVIDE AUTOMATIC CONTROL FOR SIGN AND SHOW WINDOW
 LIGHTING. LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY EITHER A COMBINATION
 OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL
 TIME SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME
 SWITCH OR PHOTOSENSOR. ALL TIME SWITCHES SHALL BE
 CAPABLE OF RETAINING PROGRAMMING AND THE TIME SETTING
 DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
 FBC CE 405.2.4 (NOT PROVIDED. A GENERAL NOTE IS NOT
 ACCEPTABLE, PROVIDE DETAILS OF LIGHTING CONTROL ON
 PLAN.)
  
 NEW COMMENT:
  
 13. IT APPEARS THAT THERE IS A TABLE IN FRONT OF
 ELECTRICAL PANELS. CLEARANCE IN FRONT OF PANELS IS
 REQUIRED PER NEC, PROVIDE CORRECTION. NEC 110.26
 14. ONLY ONE SET OF PLANS WAS PROVIDED FOR REVIEW, AND
 THE PLAN IS NOT SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL. PROVIDE CORRECTION. WPB FBC 107.1, 107.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-05-15 Cont ID  
Sent By ppetty Date 2018-04-06 Time 08:52 Rev Time 0.00
Received By jpearson Date 2018-04-06 Time 08:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-21 Cont ID  
Sent By jpearson Date 2017-11-21 Time 08:23 Rev Time 0.00
Received By jpearson Date 2017-11-21 Time 08:23 Sent To  
Notes
2017-11-21 08:23:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30
 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 4. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5
 5. OCCUPANCY SENSORS FOR BATHROOMS SHOULD BE INSIDE
 BATHROOMS. PROVIDE CORRECTION. FBC 107.2.1; FBC CE
 405.2
 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED. FBC CE 405.2.2, 405.2.2.2
 7. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1
 8. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE.
 NEC 110.10
 9. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 10. PROVIDE AIC RATING OF PANELS. NEC 110.3, 110.9
 11. ALL RECEPTACLE OUTLETS IN KITCHEN AND BAR AREAS ARE
 REQUIRED TO BE GFCI PROTECTED. PROVIDE CORRECTION. NEC
 210.8
 12. PROVIDE AUTOMATIC CONTROL FOR SIGN AND SHOW WINDOW
 LIGHTING. LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY EITHER A COMBINATION
 OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL
 TIME SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME
 SWITCH OR PHOTOSENSOR. ALL TIME SWITCHES SHALL BE
 CAPABLE OF RETAINING PROGRAMMING AND THE TIME SETTING
 DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
 FBC CE 405.2.4
  
 A FULL REVIEW WAS NOT POSSIBLE AT THIS TIME DUE TO A
 LACK OF INFORMATION ON THE PLANS. FURTHER REVIEW
 COMMENTS MAY BE NECESSARY.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-05-24 Cont ID  
Sent By pleduc Date 2018-05-24 Time   Rev Time 0.00
Received By pleduc Date 2018-05-23 Time 11:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-05-04 Cont ID  
Sent By pleduc Date 2018-05-04 Time   Rev Time 0.00
Received By pleduc Date 2018-05-04 Time 10:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-09 Cont ID  
Sent By pleduc Date 2018-04-09 Time   Rev Time 0.00
Received By pleduc Date 2018-04-09 Time 12:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-11-08 Cont ID  
Sent By pleduc Date 2017-11-08 Time   Rev Time 0.00
Received By pleduc Date 2017-11-07 Time 16:11 Sent To  
Notes
2017-11-08 12:15:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS NO EXISTING OR PROPOSED OCCUPANCY
 CLASSIFICATION PER THE FLORIDA FIRE PREVENTION CODE.
  
 PLEASE PROVIDE THE PROPOSED OCCUPANCY CLASSIFICATION
 INCLUDING OCCUPANY CODE.
  
  
  
 2) THE IS NO NOTE INDICATING COMPLAINCE WITH ANY LIFE
 SAFETY CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
  
  
 3) THERE IN NO INDICATION OF ANY EXISTING OR PROPOSED
 BUILDING INFORMATION. I.E. TYPE OF CONSTRUCTION, FIRE
 SPRINKLER, FIRE ALARM, INTEIOR FINISHES, ETC.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 4) THERE ARE NO DIMENSIONS INDICATED.
  
 PLEASE PROVIDE ALL DIMENSIONS OF EACH
 AREA/ROOM/SPACE/CORRIDOR, ETC.
  
  
  
 5) THE IS NO DOOR SCHEDULE.
  
 PLEASE PROVIDE DOOR DETAILS, INCLUDING, TYPE, SIZE,
 LOCKS, LATCHES, HARDWARE, ETC.
  
  
  
 6) A KITCHEN IS INDICATED. THERE IS NO INFORMATION
 REGARDING COMPLIANCE WITH NFPA 96, STANDARD FOR
 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL
 COOKING OPERATIONS, 2011 EDITION, EITHER EXISITNG OR
 PROPOSED.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANT EXISITNG
 OR PROPOSED SHOP DRAWINGS UNDER SEPARATE PERMIT.
  
  
  
 7) A PIZZA OVEN IS INDICATED. THERE ARE NO
 SPECIFICATION SHEETS OF PROPTECTION PER NFPA 96.
  
 PLEASE PROVIDE MANUFACTURES DETAIL SHEETS INCLUDING
 INSTALLATION INSTURCTIONS.
  
  
  
 8) THERE IS ONLY ONE EXIT FROM THE MAIN AREA AND TWO
 ARE REQUIRED. THE EXIT FROM THE MAIN AREA CAN NOT PASS
 THRU THE KITCHEN AREA.
  
 PLEASE CORRECT OR PROVIDE FFPC REFERENCE FOR THE
 EXCEPTION.
  
  
  
 9) THE DOOR TO THE FRONT RESTROOM APPEARS TO OPEN UP
 INTO THE EXIT CORRIDOR/PATHWAY.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 PLEASE CORRECT OR JUSTIFY PER THE CODE.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2018-04-04 Cont ID  
Sent By tklarge Date 2018-04-04 Time 11:28 Rev Time 0.00
Received By tklarge Date 2018-04-04 Time 11:28 Sent To  
Notes
2018-04-04 11:30:14THERE IS NO GAS SYSTEM FOR THIS PROJECT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-11-22 Cont ID  
Sent By gjohnson Date 2017-11-22 Time 16:07 Rev Time 0.00
Received By gjohnson Date 2017-11-22 Time 16:06 Sent To  
Notes
2017-11-22 16:09:371ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-05-26 Cont ID  
Sent By shill Date 2018-05-26 Time 11:44 Rev Time 0.00
Received By shill Date 2018-05-18 Time 14:19 Sent To  
Notes
2018-05-21 14:19:59B13

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-16 Cont ID  
Sent By shill Date 2018-05-16 Time 12:00 Rev Time 0.00
Received By shill Date 2018-05-01 Time 11:38 Sent To  
Notes
2018-05-02 11:38:43B14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-12 Cont ID  
Sent By jwitmer Date 2018-04-12 Time 16:40 Rev Time 0.00
Received By jwitmer Date 2018-03-26 Time 08:49 Sent To  
Notes
2018-03-28 08:49:18B08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-28 Cont ID  
Sent By gjohnson Date 2017-11-28 Time 07:30 Rev Time 0.00
Received By gjohnson Date 2017-11-03 Time 11:32 Sent To  
Notes
2017-11-06 11:32:55B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-05-16 Cont ID  
Sent By shill Date 2018-05-16 Time 12:00 Rev Time 0.00
Received By shill Date 2018-05-14 Time 10:14 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-04-12 Cont ID  
Sent By jwitmer Date 2018-04-12 Time 16:36 Rev Time 0.00
Received By jwitmer Date 2018-04-12 Time 11:22 Sent To  
Notes
2018-04-12 16:40:10BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-05-22 Cont ID  
Sent By ccole Date 2018-05-22 Time 15:50 Rev Time 0.00
Received By ccole Date 2018-05-22 Time 15:50 Sent To  
Notes
2018-05-22 15:51:04MECHANICAL PROVISO:
  
 SEPARATE PERMIT REQUIRED FOR THE PIZZA OVEN AND EXHAUST
 SYSTEM.
  
 CCOLE- 5/22/18

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-05-14 Cont ID  
Sent By ccole Date 2018-05-14 Time 12:57 Rev Time 0.00
Received By ccole Date 2018-05-14 Time 12:56 Sent To  
Notes
2018-05-14 13:06:062ND REVIEW FBC-2014 MECHANICAL, WEST PALM BEACH
 AMENDMENTS TO THE FBC-14
 PERMIT #17110117
 5/14/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ONE SET OF THE MECHANICAL PLANS IS MISSING THE
 ENGINEER'S SEAL AND SIGNATURE- SECTION 61G15-23.002
 FAC.
  
 2) THE SUBMITTED ENERGY COMPLANCE FORM C402-2017 IS
 USED FOR ALTERATIONS. CHANGES OF OCCUPANCIES SHALL BE
 IN COMPLIANCE WITH THE CODE AS REQUIRED BY SECTION
 C101.4.4. PLEASE NOTE THAT THIS PROJECT IS UNDER THE
 2014 CODE, NOT THE 2017.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-09 Cont ID  
Sent By ccole Date 2018-04-09 Time 08:03 Rev Time 0.00
Received By ccole Date 2018-04-09 Time 07:58 Sent To  
Notes
2018-04-09 08:12:112ND REVIEW FBC-2014 MECHANICAL, WEST PALM BEACH
 AMENDMENTS TO THE FBC-14
 PERMIT #17110117
 4/9/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PLEASE LABEL THE OFFICE ON THE MECHANICAL
 PLAN- SECTION 107.2.1 WPB AMENDMENTS.
  
 2) M-1: INDICATE HOW THE BACK OF THE HOUSE AREA IS
 BEING VENTILATED- TABLE 403.3.
  
 3) PROVIDE AN AIR BALANCE CALCULATION- SECTION 508.1.2.
  
 4) THE CITY OF WPB PERMITTING RECORDS DO NOT SHOW ANY
 PERMITS FOR THE RTU'S, THE MINI-SPLIT SYSTEM, AND THE
 WALK-IN COOLER, THEREFORE THESE SYSTEMS SHALL BE
 REVIEWED AND PERMITTED AS NEW. PLEASE PROVIDE:
  
 A) EQUIPMENT SCHEDULES ON THE PLAN FOR THE SYSTEMS.
 B) AC COOLING AND HEATING CALCULATIONS.
 C) CONDENSATE DISPOSAL PLANS.
  
 PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR THE
 WALK-IN COOLER, AND THE PIZZA OVEN AND EXHAUST SYSTEM.
  
 5) M-1 & M-2: SHOW THE LOCATION OF THE AC STAND AND
 WHAT UNIT IT IS SUPPORTING- SECION 107.2.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-15 Cont ID  
Sent By ccole Date 2017-11-15 Time 14:53 Rev Time 0.00
Received By ccole Date 2017-11-15 Time 14:50 Sent To  
Notes
2017-11-15 15:01:551ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110117
 11/15/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MECHANICAL PLANS SHOWING ALL ALTERATIONS TO
 THE EXISTING SYSTEMS. PLEASE NOTE THAT ALL EXISTING
 UNPERMITTED MECHANICAL WORK MUST BE EVALUATED AS NEW
 WORK, AND SEPARATE PERMITS ARE REQUIRED FOR THE PIZZA
 OVEN EXHAUST SYSTEM, AND THE WALK-IN COOLER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-05-22 Cont ID  
Sent By tklarge Date 2018-05-22 Time 06:37 Rev Time 0.00
Received By tklarge Date 2018-05-22 Time 02:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-05-12 Cont ID  
Sent By tklarge Date 2018-05-12 Time 05:25 Rev Time 0.00
Received By tklarge Date 2018-05-07 Time 14:16 Sent To  
Notes
2018-05-12 05:25:231) THERE ARE TWO SETS OF PLANS THAT ARE MISSING THE
 "CVR" SHEET AND ALSO THE ELECTRICAL PLANS. SUBMIT TWO
 COMPLETE SETS OF PLANS FOR REVIEW. WPB AMEND TO FBC
 SEC. 107.1.
 2) ONE SET OF PLANS CONTAINS MEP SHEETS THAT ARE NOT
 SIGNED AND SEALED BY THE DESIGN PROFESSIONAL. COMPLY
 WITH FL. ADMIN. CODE RULE 61G15-23.001.
 3) SHT. A1.0 - DETAIL #3 - ENLARGED PLAN - THE
 ELEVATION ARROWS LISTING THE ELEVATION DETAIL DO NOT
 CORRELATE WITH THE ELEVATIONS ON THE PLANS AND ALSO
 REFER TO SHT. A4 WHICH THERE IS NO SUCH SHEET. REVISE.
 WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHT. A1.0 - THE OUTLET OF THE TOILET PAPER DISPENSER
 IN THE HANDICAPPED TOILET ROOMS SHALL BE LOCATED A
 MINIMUM OF 15 INCHES AND A MAXIMUM OF 48 INCHES ABOVE
 THE FINISH FLOOR. 2017 FBC-ACCESS. SEC.604.7. SHOW THIS
 ON SHT. A1.0.
 5) SHOW THE REQUIRED TURNING SPACE IN RESTROOM #105 IN
 ACCORDANCE WITH THE 2017 FBC-ACCESS. SEC.304.1,
 304.3.1, 304.3.2.
 6) SHT. A1.0 - RESTROOM #105 - SHOW THE WIDTH DIMENSION
 BETWEEN THE CORNER EDGE OF THE LAVATORY AND THE END OF
 THE URINAL PARTITION.COMPLY WITH 2017 FBC-ACCESS.
 SEC.305.3.
 7) SUBMIT 2 COMPLETE COPIES OF THE MANUFACTURER'S
 INSTALLATION MANUAL FOR THE DISHWASHER. WPB AMEND. TO
 FBC SEC. 107.2.1. 2ND REQUEST.
 8) SHT. P-2 - INDICATE ON THE EXPANSION TANK SIZING
 CHART ON SHT. P-2 THE SIZE OF THE EXPANSION TANK TO BE
 INSTALLED ON THE WATER SUPPLY SYSTEM.
 9) SUBMIT TWO COPIES OF THE INSTALLATION MANUAL FOR THE
 WATER FILTRATION SYSTEM. WPB AMEND. TO FBC SEC.
 107.2.1. 2ND REQUEST.
 10) SHT. A1.0 - DETAIL #4 - THE LOCATION OF THE SIDE
 GRAB BAR SHALL COMPLY WITH 2017 FBC-ACCESS.
 SEC.604.5.1. THE GRAB BAR SHALL EXTEND A MINIMUM OF 54
 INCHES FROM THE REAR WALL. REFER TO 2017 FBC-ACCESS.
 FIGURE 604.5.1.3RD REQUEST.
 11) SHT. P-2 - THE DISCHARGE LIINE FROM THE WORK TABLE
 IN BOH #103 SHALL BE INDIRECTLY WASTED TO THE GREASY
 WASTE SYSTEM PER THE 2017 FBC-PLUMBING SEC.802.2.
 12) SUBMIT AN EXPANDED PIPNG DETAIL / DIAGRAM FOR THE
 HOT WATER RECIRCULATION SYSTEM. THE HOT WATER OR
 TEMPERED WATER RETURN LINE SHALL BE INSTALLED IN
 ACCORDANCE WITH THE 2017 FBC-PLUMBING SEC.607.2.2. A
 NOTE HAS BEEN PLACED ON THE PLAN TO THIS EFFECT BUT IS
 INADEQUATE. I HAVE INCLUDED A DIAGRAM AND TEXT FROM THE
 PLUMBING CODE COMMENTARY IN THE PLAN REVIEW FOLDER FOR
 A REFERENCE.2ND REQUEST.
 13) NOTE: ALL PLUMBING PIPES SHALL BE EXPOSED AND
 TESTED FOR INSPECTION OR A VIDEO OF SANITARY PIPING
 SHALL BE APPROVED BY TIM LARGE FOR THE ROUGH
 INSPECTIONS PER FBC PL 312. ROUGH INSPECTION WILL NOT
 PASS IF THE VIDEO SSHOWS ANY PORTION OF THE UNDERGROUND
 PIPING EXHIBITING NON-COMPLIANCE WITH THE PLUMBING CODE
 AND IN THAT INSTANCE THE UNDERSLAB PIPING SHALL BE
 EXPOSED FOR AND CORRECTED AND INSPECTED FOR COMPLIANCE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-04-04 Cont ID  
Sent By tklarge Date 2018-04-04 Time 11:28 Rev Time 0.00
Received By tklarge Date 2018-04-02 Time 10:00 Sent To  
Notes
2018-04-03 15:23:162ND REVIEW
  
 PLUMBING COMMENTS:
  
 1. THE PREVIOUS OCCUPANCY OF THIS TENANT SPACE WAS
 MERCANTILE WHICH MAKES THIS A CHANGE OF OCCUPANCY. IN
 ADDITION, THIS IS ALSO CONSIDERED A LEVEL 3 ALTERATION
 BECAUSE THE ENTIRE AREA HAS BEEN ALTERED. THEREFORE THE
 REQUIREMENTS OF CHAPTER 10 OF THE 2017 FBC-EXISTING
 BUILDING CODE APPLIES TO THIS STRUCTURE, AND CHAPTERS
 7, 8 AND 9 WILL ALSO APPLY. PLEASE REVISE
 CLASSIFICATION OF WORK ON SHT. ALS 1.1 TO READ THAT
 THIS IS A CHANGE OF OCCUPANCY.PLACE THE PREVIOUS
 OCCUPANCY ON THE PLAN. WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.1.1. 2ND REQUEST.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 FOR THE
 GRAB BAR LOCATED ON THE SIDE WALL OF THE WATER CLOSET.
 SEE FIGURE 604.5.1.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND
 EXTENDING 54 INCHES
 MINIMUM FROM THE REAR WALL. 2ND REQUEST.
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.2 FOR THE
 GRAB BAR LOCATED ON THE REAR WALL OF THE WATER CLOSET.
 SEE FIGURE 604.5.2.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE. 2ND REQUEST.
  
 4. AT LEAST ONE OF THE URINALS SHALL COMPLY WITH FBC
 ACC 605.2 HEIGHT AND DEPTH.
 URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG TYPE
 WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 OR GROUND. URINALS SHALL BE 13 1/2 INCHES DEEP MINIMUM
 MEASURED FROM THE OUTER FACE OF THE URINAL RIM TO THE
 BACK OF THE FIXTURE.
 605.3 CLEAR FLOOR SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR FORWARD APPROACH SHALL BE PROVIDED. 2ND
 REQUEST.
  
 5. SHOW THE PLUMBING FIXTURE CLEARANCES FOR THE URINALS
 IN ACCORDANCE WITH 2017 FBC-PLUMBING SEC.405.3.1.
  
 6. SHT. A1.0 - SHOW THE LENGTH AND WIDTH DIMENSIONS OF
 THE CLEAR FLOOR SPACES IN THE HANDICAPPED TOILET ROOMS.
 CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSET SHALL
 COMPLY WITH 2017 FBC-ACCESS. SEC.604.3.1. CLEAR FLOOR
 SPACE FOR THE LAVATORIES SHALL COMPLY WITH SECS. 305,
 606.2. ALSO, SHOW THE DIMENSIONS OF THE CLEAR FLOOR
 SPACE LOCATED BEYOND THE ARC OF THE DOOR SWING. COMPLY
 WITH 2017 FBC - ACCESS. SEC. 305.3.
  
 7. PLEASE SHOW COMPLIANCE WITH FBC PL 405.3.5 URINAL
 PARTITIONS.
 EACH URINAL UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL
 OCCUPY A SEPARATE AREA WITH WALLS OR PARTITIONS TO
 PROVIDE PRIVACY. THE WALLS OR PARTITIONS SHALL BEGIN AT
 A HEIGHT NOT GREATER THAN 12 INCHES FROM AND EXTEND NOT
 LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR SURFACE.
 THE WALLS OR PARTITIONS SHALL EXTEND FROM THE WALL
 SURFACE AT EACH SIDE OF THE URINAL NOT LESS THAN 18
 INCHES OR TO A POINT NOT LESS THAN 6 INCHES BEYOND THE
 OUTERMOST FRONT LIP OF THE URINAL MEASURED FROM THE
 FINISHED BACKWALL SURFACE, WHICHEVER IS GREATER. 2ND
 REQUEST.
  
 8. SHT. A1.0 SHOWS ROOM #105 WITH TWO URINALS AND A
 LAVATORY AS "PRIVATE". THIS ROOM DOES NOT MEET THE
 DEFINITION OF "PRIVATE" IN SEC. 202 OF THE 2017 FBC -
 PLUMBING. THIS RESTROOM IS LOCATED IN A COMMON AREA AND
 SHALL BE OPEN AND ACCESSIBLE TO THE OCCUPANTS OF THIS
 SPACE AND SHALL FULLY COMPLY WITH 2017 FBC-ACCESS. SEC.
 213.2 AND 2017 FBC-PLUMBING SEC.405.3.1.
  
 9. THE LAVATORY IN ROOM #105 ( "PRIIVATE RESTROOM")
 SHALL COMPLY WITH THE 2017 FBC-ACCESS. SECS.213.3.4,
 305, & 606.
  
 10. THE HAND DRYER IN ROOM #105 SHALL COMPLY WITH 2017
 FBC -ACCESS. SECS. 308 & 309.
  
 11. SHT. A1.0 - NOTE #6 REFERS TO THE 2010
 ACCESSIBILITY CODE. THE 2017 FBC-ACCESS. IS THE CODE IN
 EFFECT FOR THIS PROJECT. PLEASE REVISE THE NOTE.
  
 12. THE FLOOR SINKS, FLOOR DRAIN AND SINKS IN THE
 SERVICE AREA # 102 AND THE WORKTABLE SINK IN BOH #103
 SHALL DISCHARGE THROUGH THE GREASE INTERCEPTOR PER THE
 2017 FBC-PLUMBING SEC. 1003.3.1. THE ICE WELLS SHALL
 DISCHARGE TO THE SANITARY SYSTEM PER 2017 FBC-PLUMBING
 SEC.1003.2.
  
 13. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 HEATER.2017 FBC-PLUMBING SEC.501.
  
 14. SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION INSTRUCTIONS FOR THE GREASE
 INTERCEPTOR. 2017 FBC-PLUMBING SEC.1003.2.
  
 15. INDICATE THE SIZE OF THE EXPANSION TANK ON THE
 WATER HEATER. THE EXPANSION TANK SHALL BE SIZED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS PERR
 2017 FBC-PLUMBING SEC.607.3. SUBMIT TWO COPIES OF
 MANUFACTURER'S INSTRUCTIONS. SHOW THE CAPACITY OF THE
 WATER HEATER IN GALLONS ON THE PLANS.
  
 16. SINKS USED FOR THE WASHING, RINSING,OR SANITIZING
 OF UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN
 THE PREPARATION, SERVING OR EATING OF FOOD SHALL
 DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK TO
 THE DRAINAGE SYSTEM PER 2017 FBC-PLUMBING SEC.802.2. (3
 COMPARTMENT SINK).
  
 17. THE DRAIN FOR THE INDIRECT WASTE FOR THE WARE
 WASHER AND PIZZA OVEN SHALL BE EQUIPPED WITH A TRAP.
 2017 FBC - PLUMBING SEC.301 & 802.2.
  
 18. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 FILTRATION SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1, 2017
 FBC-PLUMBING SEC. 611.1.
  
 19. SUBMIT A PIPING DETAIL OF THE HOT WATER
 RECIRCULATION SYSTEM. THE HOT WATER OR TEMPERED WATER
 RETURN LINE SHALL BE INSTALLED IN ACCORDANCE WITH 2017
 FBC-PLUMBING SEC.607.2.2. SHOW ON THE DETAIL WHERE/HOW
 THE 140 DEGREE HOT WATER IS CONNECTED TO THE WATER
 HEATER . IT IS UNCLEAR ON THE WATER RISER.
  
 20. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 DISHWASHER. THE DISHWASHER SHALL COMPLY WITH 2017
 FBC-PLUMBING SEC.409.
  
 21. HOT WATER PIPING SHALL BE INSULATED IN ACCORDANCE
 WITH 2017 FBC-ENERGY TABLE C403.2.10, NOT TABLE
 C403.2.8 AS NOTED ON SHT.P-3.
  
 22. ALL PLUMBING PIPES SHALL BE EXPOSED AND TESTED FOR
 INSPECTION OR A VIDEO OF SANITARY PIPING SHALL BE
 APPROVED BY TIM LARGE FOR THE ROUGH INSPECTIONS. PER
 FBC PL 312
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-22 Cont ID  
Sent By gjohnson Date 2017-11-22 Time 16:09 Rev Time 0.00
Received By gjohnson Date 2017-11-21 Time 17:28 Sent To  
Notes
2017-11-22 16:58:561ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE PREVIOUS OCCUPANCY OF THIS TENANT SPACE WAS
 MERCANTILE WHICH MAKES THIS A CHANGE OF OCCUPANCY
 PLEASE REVISE CLASSIFICATION OF WORK AND ALL WORK SHALL
 COMPLY WITH FBC EXISTING BUILDING CH 10
  
 2. THE PLAN SHOWS AN EXISTING KITCHEN UPON REVIEW OF
 PERMIT RECORDS THERE IS NO PERMITS FOR A KITCHEN AND
 TIM LARGE INFORMED ME THAT THEIR IS A CODE VIOLATION
 WRITTEN UP FOR WORK WITHOUT PERMITS FOR THE KITCHEN,
 BAR AREA, PIZZA OVEN AND BATHROOMS ALL PLUMBING WORK
 WILL BE CONSIDERED AS NEW WORK AND SHALL COMPLY WITH
 FBC PL, ACC 2014 5TH EDITION
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE
 WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND
 EXTENDING 54 INCHES
 MINIMUM FROM THE REAR WALL.
  
 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR
 WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 5. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT.
  
 6. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
  
 7. AT LEAST ONE OF THE URINALS SHALL COMPLY WITH FBC
 ACC 605.2 HEIGHT AND DEPTH.
 URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG TYPE
 WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 OR GROUND. URINALS SHALL BE 131/2 INCHES DEEP MINIMUM
 MEASURED FROM THE OUTER FACE OF THE URINAL RIM TO THE
 BACK OF THE FIXTURE.
 605.3 CLEAR FLOOR SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR FORWARD APPROACH SHALL BE PROVIDED.
 AND FBC PL 405.3.1
  
 8. PLEASE SHOW COMPLIANCE WITH FBC PL 405.3.5 URINAL
 PARTITIONS.
 EACH URINAL UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL
 OCCUPY A SEPARATE AREA WITH WALLS OR PARTITIONS TO
 PROVIDE PRIVACY. THE WALLS OR PARTITIONS SHALL BEGIN AT
 A HEIGHT NOT GREATER THAN 12 INCHES FROM AND EXTEND NOT
 LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR SURFACE.
 THE WALLS OR PARTITIONS SHALL EXTEND FROM THE WALL
 SURFACE AT EACH SIDE OF THE URINAL NOT LESS THAN 18
 INCHES OR TO A POINT NOT LESS THAN 6 INCHES BEYOND THE
 OUTERMOST FRONT LIP OF THE URINAL MEASURED FROM THE
 FINISHED BACKWALL SURFACE, WHICHEVER IS GREATER.
  
 9. A GREASE INTERCEPTOR IS REQUIRED FOR ALL KITCHEN
 FIXTURES MINUS ICE MACHINES. PER FBC PL 1003.3.1
  
 10. PLEASE PROVIDE AN ISOMETRIC DRAWING FOR HOT AND
 COLD WATER, SANITARY AND GREASY WASTE. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 11. PROVIDE GREASE INTERCEPTOR SIZING CALCULATIONS. PER
 WPB AMEND TO FBC 107.2.1
  
 12. ALL PLUMBING PIPES SHALL BE EXPOSED AND TESTED FOR
 INSPECTION OR A VIDEO OF SANITARY PIPING SHALL BE
 APPROVED BY TIM LARGE AND MYSELF FOR THE ROUGH
 INSPECTIONS. PER FBC PL 312
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  