Plan Review Details - Permit 17110114
Plan Review Stops For Permit 17110114 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2017-12-06 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-12-04 |
Time |
14:55 |
Sent To |
|
|
Notes |
2017-12-05 14:55:56 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2017-11-30 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-11-28 |
Time |
12:49 |
Sent To |
|
|
Notes |
2017-11-29 12:49:30 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2017-11-08 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-11-03 |
Time |
09:47 |
Sent To |
|
|
Notes |
2017-11-06 09:48:05 | ROUTED TO MECHANICAL INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2017-12-06 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-12-06 |
Time |
12:50 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-12-06 |
Time |
10:21 |
Sent To |
|
|
Notes |
2017-12-06 12:53:48 | MECHANICAL PROVISO: | | | | ENGINEERING FOR INSTALLATION OF THE RTU SHALL BE | | SUBMITTED FOR REVIEW PRIOR TO INSPECTION. | | | | CCOLE- 12/6/17 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2017-11-30 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-11-30 |
Time |
14:31 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-11-30 |
Time |
12:04 |
Sent To |
I |
|
Notes |
2017-11-30 14:31:41 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17100499 | | 11/30/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE DESIGNER OF RECORD LILLIAN GONZALEZ P.E. MUST | | PROVIDE HER RAISED OR INK SEAL AND SIGNATURE ON THE | | MECHANICAL PLAN- SECTION 61G15-23.002 FLORIDA | | ADMINISTRATIVE CODE. | | | | 2) AS PREVIOUSLY NOTED IN THE FIRST REVIEW, THE RETURN | | TRANSFER DUCTS FROM THE BEDROOM ARE UNDERSIZED PER | | SECTION | | | | 3) THE SUBMITTED INSTALLATION INSTRUCTIONS FOR THE | | CONDENSER TIE-DOWN CLIPS ARE INCOMPLETE WITHOUT THE | | FRONT COVER SHEET OF THE MIAMI-DADE NOA OR FLORIDA | | PRODUCT APPROVAL- RULE 9N-3. | | | | 4) THE OWNER/AGENT'S SIGNATURE AND DATE ARE REQUIRED ON | | PAGE 1 OF ENERGY FORM R405. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2017-11-08 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-11-08 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-11-08 |
Time |
13:20 |
Sent To |
|
|
Notes |
2017-11-08 13:25:49 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL , ENERGY | | CONSERVATION CODES | | PERMIT #17110114 | | 11/8/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE PALM BEACH COUNTY APPRAISERS REPORT INDICATES | | THE RESIDENCE HAS NEVER HAD AN AC SYSTEM, AND THERE IS | | NO RECORD OF A PERMIT FOR A SYSTEM IN THE CITY PERMIT | | FILES. PLEASE REFER TO SECTION R101.4.5 FBC-14 ENERGY | | CONSERVATION AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE | | REPORT FOR THE NEWLY CONDITIONED RESIDENCE. | | | | 2) THE RETURN AIR TRANSFER DUCTS FROM THE BEDROOMS ARE | | UNDERSIZED PER SECTION M1602.4 FBC-14 RESIDENTIAL. | | | | 3) PROVIDE ENGINEERING FOR TIE DOWN OF THE RTU-SECTION | | 301.15. | | | | 4) PROVIDE AN ELECTRICAL PLAN AND A SUB-PERMIT | | APPLICATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
|