Plan Review Details - Permit 17110080
Plan Review Stops For Permit 17110080
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-08 Cont ID  
Sent By shill Date 2017-11-08 Time 13:53 Rev Time 0.00
Received By shill Date 2017-11-08 Time 13:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-02 Cont ID  
Sent By shill Date 2017-11-02 Time 17:55 Rev Time 0.00
Received By shill Date 2017-11-02 Time 17:55 Sent To I
Notes
2017-11-02 18:11:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107, PROVIDE A GRAPHIC OF THE PROPOSED FASTENING
 (OR REVISE FASTENING).
  
 ENGINEER HAS SPECIFIED:
 ". . . BASE SHEET BE SECURED 2 ROWS AT 6" O.C. AT THE
 LAP . . ." (ETC.)
  
 IT IS NOT CLEAR HOW THE CONTRACTOR WILL BE ABLE TO
 INSTALL TWO ROWS 6" O.C. IN A 4" LAP. THE LANGUAGE
 DIFFERS FROM THE SECOND PAGE WHICH SPECIFIES ONE ROW.
  
 2. ENGINEER ALSO SPECIFIES:
 "AT THE PERIMETER FOR 4' IN EACH DIRECTION . . . "
  
 3. SEE CALCULATIONS; PER RAS117 10.4.5, FOR FRACTIONS
 ROUND DOWN. (NOTE THAT MINIMUM SPACING IS 4").
  
  
  
 IT IS NOT CLEAR WHAT "EACH DIRECTION" MEANS RELATIVE TO
 THE PERIMETER.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-08 Cont ID  
Sent By shill Date 2017-11-08 Time 13:53 Rev Time 0.00
Received By shill Date 2017-11-08 Time 13:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-02 Cont ID  
Sent By shill Date 2017-11-02 Time 18:11 Rev Time 0.00
Received By shill Date 2017-11-02 Time 13:53 Sent To  
Notes
2017-11-02 13:53:45SHILL