Plan Review Details - Permit 17110036
Plan Review Stops For Permit 17110036
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-04 Cont ID  
Sent By cthroop Date 2018-01-04 Time 13:41 Rev Time 0.00
Received By cthroop Date 2018-01-04 Time 13:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-11-18 Cont ID  
Sent By cthroop Date 2017-11-18 Time 12:57 Rev Time 0.00
Received By cthroop Date 2017-11-18 Time 12:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-12-29 Cont ID  
Sent By jleahy Date 2017-12-29 Time 14:38 Rev Time 0.00
Received By jleahy Date 2017-12-29 Time 14:38 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-16 Cont ID  
Sent By jleahy Date 2017-11-16 Time 08:12 Rev Time 0.00
Received By jleahy Date 2017-11-16 Time 08:12 Sent To B
Notes
2017-11-16 09:06:59FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A
 SIGN OR OUT-LINE LIGHTING SYSTEM, SHALL BE CONTROLLED
 BY AN EXTERNALLY OPERABLE SWITCH
 OR CIRCUIT BREAKER THAT WILL OPEN ALL UNGROUNDED
 CONDUCTORS WITHIN SIGHT OF THE SIGN
 NEC 600.6(A)(1)
  
 YOU HAVE A DISCONNECT ON THE ROOF BUT NOT AT THE SIGN.
  
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN
 OFF AT DAYLIGHT OR WHEN NOT REQUIRED. CONTROLS SHALL BE
 PHOTOSENSOR & TIME CLOCK OR
 ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES SHALL BE
 CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS.
 FBC-EC 405.2.4
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-04 Cont ID  
Sent By cthroop Date 2018-01-04 Time 13:41 Rev Time 0.00
Received By cthroop Date 2017-12-18 Time 13:34 Sent To I
Notes
2017-12-19 13:34:19RESUB ROUTED TO LLOUIE VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-18 Cont ID  
Sent By cthroop Date 2017-11-18 Time 12:57 Rev Time 0.00
Received By cthroop Date 2017-11-01 Time 11:18 Sent To I
Notes
2017-11-02 11:18:30ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2017-12-28 Cont ID  
Sent By LL Date 2017-12-28 Time   Rev Time 0.00
Received By llouie Date 2017-12-21 Time 10:37 Sent To  
Notes
2017-12-28 13:02:20SIGN CALCULATIONS:
 - MAX. SIGN AREA PERMITTED = 602.56 SQ. FT.
 - SIGN AREA PROPOSED = 379 SQ. FT.
  
 NOTES:
 - TOTAL OF 3 WALL SIGNS ON BUILDING (3 WALL SIGNS MAX.
 PER ZLDRS)
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-11-14 Cont ID  
Sent By LL Date 2017-11-14 Time   Rev Time 0.00
Received By llouie Date 2017-11-07 Time 10:03 Sent To E
Notes
2017-11-14 08:45:05** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) BUILDING ELEVATION AND PROPOSED WALL SIGNAGE DOES
 NOT MATCH THE APPROVED PLANS. A MINOR AMENDMENT TO THE
 AUSTRALIAN OFFICE PARK COMMERCIAL PLANNED DEVELOPMENT
 (CPD) IS REQUIRED THROUGH THE DEVELOPMENT SERVICES
 DEPARTMENT - PLANNING DIVISION PRIOR TO ZONING
 SIGN-OFF.
  
 NOTES:
  
 THE 2017 DEVELOPMENT APPLICATION FOR THE MINOR PLANNED
 DEVELOPMENT (PD) AMENDMENT IS AVAILABLE ON THE CITY'S
 WEBSITE AT: HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERV
 ICES/FORMS/PLANNING-ZONING-FORMS
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: CPD (AUSTRALIAN OFFICE PARK)
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved