Plan Review Details - Permit 17101215
Plan Review Stops For Permit 17101215
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-02 Cont ID  
Sent By jwitmer Date 2018-03-02 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2018-03-02 Time 07:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-08 Cont ID  
Sent By jwitmer Date 2018-01-08 Time 07:13 Rev Time 0.00
Received By jwitmer Date 2018-01-05 Time 14:23 Sent To  
Notes
2018-01-08 07:00:342014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17101215
 ADD: 1020 11TH. ST.
 CONT: T. B. D. / TO BE DETERMINED
 TEL: 561-822-1437
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JAN. 08/ 2018
 ACTION: BUILDING PROVISO
  
 1) BUILDING PROVISO: SHEET A2.2 SHOWS A NEW EXHAUST
 HOOD. HOOD AND SUPPRESSION ARE REVIEWED UNDER SEPARATE
 PERMITS.
 2801.1 SCOPE.
 MECHANICAL APPLIANCES, EQUIPMENT AND SYSTEMS SHALL BE
 CONSTRUCTED, INSTALLED AND MAINTAINED IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, MECHANICAL AND THE
 FLORIDA BUILDING CODE, FUEL GAS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-06 Cont ID  
Sent By jwitmer Date 2017-11-06 Time 13:33 Rev Time 0.00
Received By jwitmer Date 2017-11-03 Time 14:27 Sent To  
Notes
2017-11-06 13:33:142014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17101215
 ADD: 1020 11TH. ST.
 CONT: T. B. D. / TO BE DETERMINED
 TEL: 561-822-1437
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 06/ 2017
 ACTION: DENIED
  
 1) THE COVERSHEET A0.0 LIST THE BUILDING CONSTRUCTION
 TYPE AND INDICATES THE AMERICAN LEGION MEETS THERE, AND
 THE BUILDING IS OWNED BY THE CITY OF WEST PALM BEACH
 (TITLE II). WHAT THE DESIGNER OF RECORD HAS NOT
 DECLARED IS THE OCCUPANCY, THIS MAY BE A MIXED USE
 BUILDING DEPENDING ON THE FUNCTION OF THE BUILDING, A
 BANQUET HALL WITH TABLE AND CHAIRS, USED FOR MEETINGS
 WITH CHAIRS ONLY AND OR AS A DANCE HALL OR EVENT HALL
 WITH A MIXTURE OF ALL THREE. PLEASE PROVIDE AN
 OCCUPANCY TYPE.
  
 2014 FBC-B SECTION 302.1. STRUCTURES OR PORTIONS OF
 STRUCTURES SHALL BE CLASSIFIED WITH RESPECT TO
 OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED IN THIS
 SECTION. A ROOM OR SPACE THAT IS INTENDED TO BE
 OCCUPIED AT DIFFERENT TIMES FOR DIFFERENT PURPOSES
 SHALL COMPLY WITH ALL OF THE REQUIREMENTS THAT ARE
 APPLICABLE TO EACH OF THE PURPOSES FOR WHICH THE ROOM
 OR SPACE WILL BE OCCUPIED. STRUCTURES WITH MULTIPLE
 OCCUPANCIES OR USES SHALL COMPLY WITH SECTION 508.
  
 2) SHEET A2.0 PROVIDES A TABLE LISTING THE SQUARE FOOT
 AREA OF THE ROOMS BUT DOES NOT PROVIDE THE OCCUPANT
 LOAD FOR THE ROOMS AND OVERALL TOTAL OCCUPANT LOAD.
 OCCUPANT LOADS TO BE USED IN :
  
 TABLE 1004.1.2 OF THE 2014 FBC-B. A ROOM OR SPACE THAT
 IS INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR
 DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE
 REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE
 PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED
 THE MOST RESTRICTIVE WOULD APPLY.
  
 2014 FBC-B 201, FLOOR AREA, NET. THE ACTUAL OCCUPIED
 AREA NOT INCLUDING UNOCCUPIED ACCESSORY AREAS SUCH AS
 CORRIDORS, STAIRWAYS, TOILET ROOMS, MECHANICAL ROOMS
 AND CLOSETS.
  
 FLOOR AREA, GROSS. THE FLOOR AREA WITHIN THE INSIDE
 PERIMETER OF THE EXTERIOR WALLS OF THE BUILDING UNDER
 CONSIDERATION, EXCLUSIVE OF VENT SHAFTS AND COURTS,
 WITHOUT DEDUCTION FOR CORRIDORS, STAIRWAYS, CLOSETS,
 THE THICKNESS OF INTERIOR WALLS, COLUMNS OR OTHER
 FEATURES. THE FLOOR AREA OF A BUILDING, OR PORTION
 THEREOF, NOT PROVIDED WITH SURROUNDING EXTERIOR WALLS
 SHALL BE THE USABLE AREA UNDER THE HORIZONTAL
 PROJECTION OF THE ROOF OR FLOOR ABOVE. THE GROSS FLOOR
 AREA SHALL NOT INCLUDE SHAFTS WITH NO OPENINGS OR
 INTERIOR COURTS.
  
 3) SHEET A2.0 SHOWS PROPOSED WORK IN BOTH THE MENS &
 WOMENS RESTROOMS. THE COVERSHEET INDICATES A LEVEL 2
 ALTERATION. 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING. ALSO UNDER THE
 LEVEL II ALTERATIONS OF THE 2014 EXISTING BUILDING CODE
 SECTION 806.1 A BUILDING, FACILITY, OR ELEMENT THAT HAS
 IS ALTERED SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY. PLEASE NOTE THE
 NEW LAYOUT OF BOTH THE MENS AND WOMENS RESTROOMS DOES
 NOT COMPLY WITH THE ACCESSIBILITY CODE 604.3.1 SIZE,
 604.3.2 OVERLAP NOR 604.8.1.6.
  
 4) SHEET A2.1 DETAILS IN BOTH THE MENS AND WOMENS
 RESTROOMS THE MIRRORS ARE SHOWN ABOVE THE MAXIMUM
 HEIGHT OF 40 INCHES TO THE BOTTOM EDGE OF THE
 REFLECTIVE MIRROR SURFACE. ACCESS. CODE 603.3.
  
 5) WHEN THE OCCUPANCY CLASSIFICATION IS GIVEN AND THE
 OCCUPANT LOAD IS KNOWN PLEASE REVIEW SECTION 810.1 OF
 THE EXISTING BUILDING CODE TO SEE IF THE FIXTURE COUNT
 HAS BEEN MET.
  
 6) SHEET A2.0 ALSO SHOWS WORK AT THE BAR AREA. SHEET
 A2.2 DETAIL # 10 SHOWS THE BAR TOP AT A HEIGHT OF 3?-6?
 OR 42 INCHES TALL. PLEASE SHOW A PORTION OF THE BAR
 MEETING THE ACCESSIBILITY CODE 226.1 WHERE DINING
 SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR
 DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. 902.1 .DINING SURFACES AND WORK SURFACES
 SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1
 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT LIMITED
 TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 6)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 7) SHEET A2.2 SHOWS A NEW EXHAUST HOOD. HOOD AND
 SUPPRESSION ARE REVIEWED UNDER SEPARATE PERMITS.
 2801.1 SCOPE.
 MECHANICAL APPLIANCES, EQUIPMENT AND SYSTEMS SHALL BE
 CONSTRUCTED, INSTALLED AND MAINTAINED IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, MECHANICAL AND THE
 FLORIDA BUILDING CODE, FUEL GAS.
  
 8) SHEET S1.0 THE DESIGN PRESSURES FOR THE COMPONENTS
 AND CLADDING ARE LOW AND THE SAME FOR 10SQ. FT. 20 SQ.
 FT. AND 30 SQ. FT. 2014 FBC-B TABLE 1609.6.2. & TABLE
 R301.2(2). UNTIL THE PRESSURES ARE CORRECTED THE
 PRODUCT APPROVALS CANNOT BE EVALUATED.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-01-03 Cont ID  
Sent By jpearson Date 2018-01-03 Time 12:55 Rev Time 0.00
Received By jpearson Date 2018-01-03 Time 10:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-16 Cont ID  
Sent By jpearson Date 2017-11-16 Time 14:54 Rev Time 0.00
Received By jpearson Date 2017-11-16 Time 14:54 Sent To  
Notes
2017-11-16 14:54:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1
 2. EXISTING RISER AND PROPOSED RISER ARE BOTH MISSING
 INFORMATION. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS
 OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 4. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. KITCHEN AND BAR AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC CE 405.2.2,
 405.2.2.2
 7. INSIDE THE PANEL B PANEL SCHEDULE IS A LOAD
 CALCULATION LABELED "PANEL A". IS THIS A TYPO? CLARIFY
 AND/OR CORRECT. FBC 107.2.1
 8. THERE IS A NOTE THAT STATES ALL KITCHEN AND BAR AREA
 RECEPTACLES SHALL BE GFCI PROTECTED, EXCEPT THOSE FOR
 EQUIPMENT. ALL RECEPTACLE OUTLETS ARE REQUIRED TO HAVE
 GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8
 9. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE
 ELECTRICAL RECEPTACLE OUTLETS LOCATED UNDER THE HOOD
 PER NFPA 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-12-22 Cont ID  
Sent By pleduc Date 2017-12-22 Time   Rev Time 0.00
Received By pleduc Date 2017-12-22 Time 11:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-01 Cont ID  
Sent By pleduc Date 2017-11-01 Time   Rev Time 0.00
Received By pleduc Date 2017-11-01 Time 15:24 Sent To  
Notes
2017-11-01 15:53:10THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE HOOD AND SUPPRESSION SYSTEMS SHALL BE SUBMITTED,
 INSTALLED, INSPECTED AND TESTED UNDER SEPARATE SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-03-02 Time   Rev Time 0.00
Received By gjohnson Date 2018-03-01 Time 12:29 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-01-10 Cont ID  
Sent By gjohnson Date 2018-01-10 Time 13:15 Rev Time 0.00
Received By gjohnson Date 2018-01-10 Time 12:10 Sent To  
Notes
2018-01-10 12:11:322ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 2. PLEASE SHOW THE SYSTEM PRESSURE ON THE RISER. PER
 WPB AMEND TO FBC 107.2.1 THE TABLE ON THE GAS
 CONSUMPTION 402.4(3) IS FOR PRESSURE LESS THAN 2PSI
 WITH A PRESSURE DROP OF 3.0WC THE PRESSURE SHOWN ON THE
 PRINT IS 2PSI WITH A PRESSURE DROP OF 1PSI CLARIFY AND
 COMPLY WITH THE COMMENT SHOW PRESSURE ON THE RISER AND
 SHOW THE CORRECT TABLE
  
 3. PLEASE INDICATE TYPE OF PIPE ON THE RISER. PER WPB
 AMEND TO FBC 107.2.1 THE TABLE ON THE GAS CONSUMPTION
 402.4(3) IS FOR PRESSURE LESS THAN 2PSI WITH A PRESSURE
 DROP OF 3.0WC THE PRESSURE SHOWN ON THE PRINT IS 2PSI
 WITH A PRESSURE DROP OF 1PSI CLARIFY AND COMPLY WITH
 THE COMMENT SHOW TYPE OF PIPE ON THE RISER AND SHOW THE
 CORRECT TABLE
  
 4. PLEASE PROVIDE ACCURATE SIZING TABLE THE SHOWN ON
 PLAN IS INCORRECT TABLE 402.4(3) IS SHOWN AS 2PSI ON
 THE PLAN IT IS LESS THAN 2PSI IN THE FBC FG TABLE
 402.4(3) THE TABLE ON THE GAS CONSUMPTION 402.4(3) IS
 FOR PRESSURE LESS THAN 2PSI WITH A PRESSURE DROP OF
 3.0WC THE PRESSURE SHOWN ON THE PRINT IS 2PSI WITH A
 PRESSURE DROP OF 1PSI CLARIFY
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 PLACE
 NOTE ON PLAN TO PROVIDE ON JOBSITE FOR INSPECTIONS.
  
 11. PLEASE SHOW DRIP LEGS ON RISER DIAGRAM. PER WPB
 AMEND TO FBC 107.2.1 THE DETAIL DOES NOT SATISFY
 COMMENT PLEASE SHOW ON RISER.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-11-21 Cont ID  
Sent By gjohnson Date 2017-11-21 Time 12:12 Rev Time 0.00
Received By gjohnson Date 2017-11-21 Time 12:12 Sent To  
Notes
2017-11-21 12:29:341ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. PLEASE SHOW THE SYSTEM PRESSURE ON THE RISER. PER
 WPB AMEND TO FBC 107.2.1
  
 3. PLEASE INDICATE TYPE OF PIPE ON THE RISER. PER WPB
 AMEND TO FBC 107.2.1
  
 4. PLEASE PROVIDE ACCURATE SIZING TABLE THE SHOWN ON
 PLAN IS INCORRECT TABLE 402.4(3) IS SHOWN AS 2PSI ON
 THE PLAN IT IS LESS THAN 2PSI IN THE FBC FG TABLE
 402.4(3)
  
 5. PLEASE PROVIDE LENGTH FROM METER TO FURTHEST
 APPLIANCE NOT SHOWN ON RISER. FBC FG 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. THE MAX DISTANCE IS SHOWN AS 40' IS THAT FROM METER
 TO THE METER TO FIRST REG OF FROM REG TO FURTHEST
 APPLIANCE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 11. PLEASE SHOW DRIP LEGS ON RISER DIAGRAM. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2018-03-02 Cont ID  
Sent By gjohnson Date 2018-03-02 Time   Rev Time 0.00
Received By gjohnson Date 2018-02-21 Time 10:03 Sent To  
Notes
2018-02-22 10:03:32RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-10 Cont ID  
Sent By gjohnson Date 2018-01-10 Time 13:43 Rev Time 0.00
Received By gjohnson Date 2017-12-19 Time 14:44 Sent To  
Notes
2017-12-21 14:44:53B22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-21 Cont ID  
Sent By gjohnson Date 2017-11-21 Time 12:29 Rev Time 0.00
Received By gjohnson Date 2017-10-30 Time 15:17 Sent To  
Notes
2017-10-31 15:17:43B02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-11-06 Cont ID  
Sent By jwitmer Date 2017-11-06 Time 13:33 Rev Time 0.00
Received By jwitmer Date 2017-11-03 Time 14:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-12-28 Cont ID  
Sent By ccole Date 2017-12-28 Time 11:30 Rev Time 0.00
Received By ccole Date 2017-12-28 Time 11:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-11-13 Cont ID  
Sent By ccole Date 2017-11-13 Time 14:19 Rev Time 0.00
Received By ccole Date 2017-11-13 Time 14:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-03-02 Time   Rev Time 0.00
Received By gjohnson Date 2018-03-01 Time 12:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-01-10 Cont ID  
Sent By gjohnson Date 2018-01-10 Time 11:31 Rev Time 0.00
Received By gjohnson Date 2018-01-10 Time 11:31 Sent To  
Notes
2018-01-10 12:10:432ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 2ND REQUEST 1. PLEASE SHOW CLEAR FLOOR SPACE FOR THE
 TOILET, URINAL AND LAVATORY. PER FBC ACC 604.3.1, 605.3
 AND 606.2 SHT. A2.1 DOES NOT SHOW THE CLEAR FLOOR SPACE
 FOR THE TOILET AND URINAL.
  
 2ND REQUEST 2. PLEASE SHOW COMPLIANCE WITH FBC ACC
 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALLL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
 A) DETAILS #3, #4, #7 SHOWS A DIMENSION OF 6-3/4" FROM
 THE TOP OF THE LAVATORY TO THE BOTTOM OF THE MIRROR
 WHICH MAKES THE TOTAL DIMENSION FROM FINISHED FLOOR TO
 THE BOTTOM OF THE MIRROR 40-3/4" THE CODE REQUIRES 40"
 EXACTLY 3/4" IS TO MUCH TO ALLOW FOR A TOLERANCE PLEASE
 CORRECT THE DIMENSION SO THAT IT MEETS THE CODE
 REQUIREMENT.
 B) DETAIL #5 SOMEONE CHANGED THE IN PEN THE MIN 40" TO
 MAX ON THE DOUBLE LAVATORY BUT THEY DID NOT CHANGE
 IT-ON THE SINGLE LAVATORY IN-THE ACCESSIBLE STALL
  
 2ND REQUEST 3. PLEASE SHOW COMPLIANCE WITH FBC ACC
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE. PLEASE SHOW THE GRAB BARS MEASURED TO THE TOP
 OF THE GRIPPING SURFACE.
  
 2ND REQUEST 4. PLEASE SHOW COMPLIANCE WITH FBC ACC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. SHOW DIMENSION ON PLAN
  
 2ND REQUEST 5. PLEASE SHOW COMPLIANCE WITH FBC ACC
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.
  
 2ND REQUEST 6. SHT. A2.1 DETAIL #8 SHOWS LAVATORY RIM
 AT 36" OF FINISH FLOOR IT SHALL BE 34". PER FBC ACC
 606.3
  
 2ND REQUEST 10. THE WATER FILTER SHOWN ON SHT. K 2.0
 DETAIL P.1 IS NOT SHOWN ON WATER PIPE RISER PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1 EVEN IF IT IS
 EXISTING PLEASE SHOW ON WATER AND SANITARY RISER
 DIAGRAM AND MARK AS EXISTING.
  
 2ND REQUEST 11. A BACKFLOW IS REQUIRED ON SUPPLY TO ICE
 MACHINE WATER FILTER AND BEVERAGE DISPENSERS AND COFFEE
 MACHINES. PER FBC PL 608.3, 608.16.1 AND 608.16.10
 BACKFLOWS ARE NOT SHOWN ON THE WATER RISER AND ON THE
 PLUMBING FIXTURE SCHEDULE IT REFERS TO NOTE 23 I COULD
 NOT LOCATE NOTE 23 ON PLAN SHEET.
  
 2ND REQUEST 12. ONLY FIXTURES THAT PRODUCE GREASE WASTE
 SHALL DISCHARGE THROUGH A GREASE INTERCEPTOR LIKE
 KITCHEN AND FOOD PREP AREA AND MOP SIN, THE FIXTURES IN
 BAR AREA SHALL NOT DISCHARGE THROUGH THE GREASE
 INTERCEPTOR. PER FBC PL 1003.2 THE BARS FIXTURE ARE
 STILL SHOWN ON GREASE WASTE RISER.
  
 2ND REQUEST 13. LAVATORY'S SHALL COMPLY WITH FBC PL
 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. NOT SHOWN ON PLAN PLEASE PROVIDE
 NOTE
  
 2ND REQUEST 14. P;LEASE SHOW ICE MACHINE ON WATER
 RISER. PER WPB AMEND TO FBC 107.2.1 NOT SHOW ON RISER
 EVEN IF IT IS EXISTING PLEASE SHOW ON WATER AND
 SANITARY RISER DIAGRAM AND MARK AS EXISTING.
  
 2ND REQUEST 15. THE FIXTURE COUNT SHAL COMPLY WITH FBC
 PL 403.1.3 POTTY PARITY.
 IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO
 THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS
 PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER
 CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE
 TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH
 SECTION 553.86, FLORIDA STATUTES.
 IN ORDER TO COMPLY WITH THIS CODE SEC THERE SHALL BE
 THE SAME NUMBER OF TOILETS IN THE WOMENS BATHROOM AS
 THE COMBINED NUMBERS OF TOILETS AND URINALS IN THE
 MENS.
  
  
 2ND REQUEST 16. A TEST PORT IS REQUIRED ON THE
 DISCHARGE OF GREASE INTERCEPTOR. PER WPB UTILITIES. THE
 DETAIL DOES NOT COMPLY A DOUBLE SANITARY TEE WITH A CAP
 ON THE BOTTOM SHALL NOT BE USED. A MIN 4" TWOWAY CLEAN
 OUT OR PREMANUFACTERED TEST PORT SHALL BE USED PER WPB
 UTILITIES.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-21 Cont ID  
Sent By gjohnson Date 2017-11-21 Time 10:57 Rev Time 0.00
Received By gjohnson Date 2017-11-17 Time 10:49 Sent To  
Notes
2017-11-21 12:11:461ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW CLEAR FLOOR SPACE FOR THE TOILET, URINAL
 AND LAVATORY. PER FBC ACC 604.3.1, 605.3 AND 606.2
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALLL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 609.4 POSITION
 OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE.
  
 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 5. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE
 WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.
  
 6. SHT. A2.1 DETAIL 8 AND 5 SHOWS LAVATORY RIM AT 35"
 OF FINISH FLOOR IT SHALL BE 34". PER FBC ACC 606.3
  
 7. PLEASE LIST APPLICABLE CODES. PER WPB AMEND TO FBC
 107.2.1
  
 8. PLEASE PROVIDE A BREAK DOWN OF OCCUPANT LOAD. PER
 WPB AMEND TO FBC 107.2.1
  
 9. HOT WATER SYSTEM SHALL COMPLY WITH FBC PL 607.2 HOT
 OR TEMPERED WATER SUPPLY TO FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 . RECIRCULATING SYSTEM PIPING AND HEAT-TRACED PIPING
 SHALL BE CONSIDERED TO BE SOURCES OF HOT OR TEMPERED
 WATER.
  
 10. THE WATER FILTER SHOWN ON SHT. K 2.0 DETAIL P.1 IS
 NOT SHOWN ON WATER PIPE RISER PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 11. A BACKFLOW IS REQUIRED ON SUPPLY TO ICE MACHINE
 WATER FILTER AND BEVERAGE DISPENSERS AND COFFEE
 MACHINES. PER FBC PL 608.3, 608.16.1 AND 608.16.10
  
 12. ONLY FIXTURES THAT PRODUCE GREASEY WASTE SHALL
 DISCHARGE THROUGH A GREASE INTERCEPTOR LIKE KITCHEN AND
 FOOD PREP AREA AND MOP SIN, THE FIXTURES IN BAR AREA
 SHALL NOT DISCHARGE THROUGH THE GREASE INTERCEPTOR. PER
 FBC PL 1003.2
  
 13. LAVATORY'S SHALL COMPLY WITH FBC PL 416.5 TEMPERED
 WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 14. P;LEASE SHOW ICE MACHINE ON WATER RISER. PER WPB
 AMEND TO FBC 107.2.1
  
 15. THE FIXTURE COUNT SHAL COMPLY WITH FBC PL 403.1.3
 POTTY PARITY.
 IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO
 THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS
 PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER
 CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE
 TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH
 SECTION 553.86, FLORIDA STATUTES.
  
 EXCEPTION: THIS SECTION DOES NOT APPLY TO
 ESTABLISHMENTS LICENSED UNDER CHAPTER 509, FLORIDA
 STATUTES, IF THE ESTABLISHMENT DOES NOT PROVIDE MEETING
 OR BANQUET ROOMS WHICH ACCOMMODATE MORE THAN 150
 PEOPLE, AND THE ESTABLISHMENT HAS AT LEAST THE SAME
 NUMBER OF WATER CLOSETS FOR WOMEN AS THE COMBINED TOTAL
 OF WATER CLOSETS AND URINALS FOR MEN.
  
  
 16. A TEST PORT IS REQUIRED ON THE DISCHARGE OF GREASE
 INTERCEPTOR. PER WPB UTILITIES
  
 17. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREAS
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 18. WATER SYSTEM SHALL COMPLY WITH FBC PL 604.9 WATER
 HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2018-11-06 Cont ID  
Sent By gjohnson Date 2018-11-06 Time 09:32 Rev Time 0.00
Received By gjohnson Date 2018-11-06 Time 09:32 Sent To  
Notes
***NONE***