Plan Review Details - Permit 17101146
Plan Review Stops For Permit 17101146
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-11-06 Cont ID  
Sent By aclange Date 2017-11-06 Time 10:46 Rev Time 0.00
Received By aclange Date 2017-11-06 Time 08:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-12-04 Cont ID  
Sent By jpearson Date 2017-12-04 Time 11:38 Rev Time 0.00
Received By jpearson Date 2017-12-04 Time 10:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-02 Cont ID  
Sent By wjolin Date 2017-11-02 Time 12:39 Rev Time 0.00
Received By wjolin Date 2017-11-02 Time 12:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-01-04 Time   Rev Time 0.00
Received By lmarchan Date 2017-12-21 Time 10:43 Sent To  
Notes
2017-12-22 10:43:49RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-04 Cont ID  
Sent By aclange Date 2017-12-04 Time 11:40 Rev Time 0.00
Received By aclange Date 2017-10-27 Time 13:09 Sent To  
Notes
2017-10-30 13:09:23C19

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-01-04 Cont ID  
Sent By ccole Date 2018-01-04 Time 09:51 Rev Time 0.00
Received By ccole Date 2018-01-04 Time 08:16 Sent To I
Notes
2018-01-04 09:57:13MECHANICAL PROVISO
 1/4/18
  
 1) THE ALTERATIONS TO THE MECHANICAL SYSTEM ON THE 7TH
 FLOOR SHALL NOT IMPACT OR ALTER THE FUNCTION OF THE
 EXISTING SMOKE CONTROL SYSTEM FOR THE BUILDING.
  
 A HOLD WILL BE PLACED ON THE CO PENDING VERIFICATION BY
 EITHER TESTING OF THE SYSTEM, OR CERTIFICATION LETTER
 FROM THE BUILDING ENGINEER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-18 Cont ID  
Sent By ccole Date 2017-11-18 Time 10:10 Rev Time 0.00
Received By ccole Date 2017-11-18 Time 09:16 Sent To  
Notes
2017-11-18 10:14:141ST REVIEW FBC-2014 BUILDING, EXISTING BUILDING, ENERGY
 CONSERVATION CODES
 PERMIT #17101146
 11/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) INDICATE HOW O/A IS BEING PROVIDE TO THE VAV'S AND
 SHOW COMPLIANCE WITH SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION: AUTOMATIC SHUTOFF DAMPERS, EITHER
 MOTORIZED OR GRAVITY, SHALL BE PROVIDED TO SHUT DOWN
 THE O/A WHEN THE ROOMS OR SPACES ARE NOT IN USE.
  
 3) INDICATE HOW COMPLIANCE WILL BE MET WITH SECTION
 606.2.2 COMMON SUPPLY AND RETURN AIR SYSTEMS:
  
 WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY
 WITH A COMBINED DESIGN CAPACITY GREATER THAN 2,000 CFM
 (0.9 M3/S), EACH SUPPLY AIR SYSTEM SHALL BE PROVIDED
 WITH SMOKE DETECTORS IN ACCORDANCE WITH SECTION
 606.2.1.
  
 EXCEPTION: INDIVIDUAL SMOKE DETECTORS SHALL NOT BE
 REQUIRED FOR EACH FAN-POWERED TERMINAL UNIT, PROVIDED
 THAT SUCH UNITS DO NOT HAVE AN INDIVIDUAL DESIGN
 CAPACITY GREATER THAN 2,000 CFM (0.9 M3/S) AND WILL BE
 SHUT DOWN BY ACTIVATION OF ONE OF THE FOLLOWING:
  
 1.SMOKE DETECTORS REQUIRED BY SECTIONS 606.2.1 AND
 606.2.3.
  
 2.AN APPROVED AREA SMOKE DETECTOR SYSTEM LOCATED IN THE
 RETURN AIR PLENUM SERVING SUCH UNITS.
  
 3.AN AREA SMOKE DETECTOR SYSTEM AS PRESCRIBED IN THE
 EXCEPTION TO SECTION 606.2.1.
  
 IN ALL CASES, THE SMOKE DETECTORS SHALL COMPLY WITH
 SECTIONS 606.4 AND 606.4.1.[F]
  
 3) INDICATE COMPLIANCE WITH SECTION 606.4 CONTROLS
 OPERATION:
  
 UPON ACTIVATION, THE SMOKE DETECTORS SHALL SHUT DOWN
 ALL OPERATIONAL CAPABILITIES OF THE AIR DISTRIBUTION
 SYSTEM IN ACCORDANCE WITH THE LISTING AND LABELING OF
 APPLIANCES USED IN THE SYSTEM. AIR DISTRIBUTION SYSTEMS
 THAT ARE PART OF A SMOKE CONTROL SYSTEM SHALL SWITCH TO
 THE SMOKE CONTROL MODE UPON ACTIVATION OF A DETECTOR.
  
 4) INDICATE COMPLIANCE SECTION 606.4.1 SUPERVISION:
  
 THE DUCT SMOKE DETECTORS SHALL BE CONNECTED TO A FIRE
 ALARM SYSTEM WHERE A FIRE ALARM SYSTEM IS REQUIRED BY
 THE FLORIDA FIRE PREVENTION CODE. THE ACTUATION OF A
 DUCT SMOKE DETECTOR SHALL ACTIVATE A VISIBLE AND
 AUDIBLE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION. IN FACILITIES THAT ARE REQUIRED TO BE
 MONITORED BY A SUPERVISING STATION, DUCT SMOKE
 DETECTORS SHALL REPORT ONLY
  
 AS A SUPERVISORY SIGNAL, NOT AS A FIRE ALARM.
  
 EXCEPTIONS:
  
 1.THE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION IS NOT REQUIRED WHERE THE DUCT SMOKE DETECTOR
 ACTIVATES THE BUILDING'S ALARM-INDICATING APPLIANCES.
  
 2.IN OCCUPANCIES NOT REQUIRED TO BE EQUIPPED WITH A
 FIRE ALARM SYSTEM, ACTUATION OF A SMOKE DETECTOR SHALL
 ACTIVATE A VISIBLE AND AUDIBLE SIGNAL IN AN APPROVED
 LOCATION. DUCT SMOKE DETECTOR TROUBLE CONDITIONS SHALL
 ACTIVATE A VISIBLE OR AUDIBLE SIGNAL IN AN APPROVED
 LOCATION AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR
 TROUBLE.
  
 PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR FIRE
 ALARM ALTERATIONS.
  
 5) CLARIFY IF THERE IS AN EXISTING SMOKE CONTROL SYSTEM
 IN THE BUILDING AND IF THE NEW FIRE DAMPERS IN THE
 ELEVATOR LOBBY AND CORRIDOR ARE CONNECTED TO IT AS PART
 OF THE CONTROLS OPERATION. PLEASE NOTE FIRE/SMOKE
 DAMPERS MAY BE REQUIRED IN THE FIRE-RATED WALLS
 ENCLOSING THE ELEVATOR LOBBY.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-11-29 Cont ID  
Sent By gjohnson Date 2017-11-29 Time 14:42 Rev Time 0.00
Received By gjohnson Date 2017-11-29 Time 13:52 Sent To  
Notes
***NONE***