Plan Review Details - Permit 17101114
Plan Review Stops For Permit 17101114
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-07 Cont ID  
Sent By jpearson Date 2017-11-07 Time 09:56 Rev Time 0.00
Received By jpearson Date 2017-11-07 Time 09:56 Sent To I
Notes
2017-11-07 09:56:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE DETAILS OF WIRING TO BE INSTALLED, SEE FIRE
 COMMENTS. FBC 107.2.1
 2. PROVIDE SPEC SHEETS FOR ALL EQUIPMENT TO BE
 INSTALLED. NEC 110.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-10-27 Cont ID  
Sent By pleduc Date 2017-10-27 Time   Rev Time 0.00
Received By pleduc Date 2017-10-27 Time 12:43 Sent To E
Notes
2017-10-27 13:20:32THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 INFORMATION: THERE IS INDICATION OF A CERTIFIED FIRE
 ALARM CONTRACTOR THAT IS DOING THE WORK. THOUGH A TBD
 PERMIT CAN BE PASSED AND HELD FOR A QUALIFING
 CONTRACTOR THERE ARE OTHER CONCERNS WITH THIS PLAN SET
 THAT NEED TO BE ADDRESSED.
  
  
 1) THESE ARE NOT SHOP DRAWINGS.
  
 PER NFPA 13
  
 3.3.238 SHOP DRAWINGS. DOCUMENTS THAT PROVIDE
 INFORMATION
 PERTAINING TO THE SYSTEM, SUCH AS PROPERTY LOCATION,
 SCALED
 FLOOR PLANS, EQUIPMENT WIRING DETAILS, TYPICAL
 EQUIPMENT INSTALLATION
 DETAILS, RISER DETAILS, CONDUIT/CONDUCTOR SIZE AND
 ROUTING INFORMATION, AND OTHER INFORMATION NECESSARY
 FOR THE
 INSTALLER TO COMPLETE THE FIRE ALARM INSTALLATION.
  
 10.18 DOCUMENTATION.
 10.18.1 APPROVAL AND ACCEPTANCE.
 10.18.1.1 THE AUTHORITY HAVING JURISDICTION SHALL BE
 NOTIFIED
 PRIOR TO INSTALLATION OR ALTERATION OF EQUIPMENT OR
 WIRING.
 10.18.1.2* AT THE AUTHORITY HAVING JURISDICTION?S
 REQUEST, COMPLETE
 INFORMATION REGARDING THE SYSTEM OR SYSTEM ALTERATIONS,
 INCLUDING SPECIFICATIONS, TYPE OF SYSTEM OR SERVICE,
 SHOP DRAWINGS,
 INPUT/OUTPUT MATRIX, BATTERY CALCULATIONS, AND
 NOTIFICATION
 APPLIANCE CIRCUIT VOLTAGE DROP CALCULATIONS, SHALL BE
 SUBMITTED
 FOR APPROVAL.
  
 GENERAL. SHOP DRAWINGS FOR FIRE ALARM SYSTEMS SHOULD
 PROVIDE
 BASIC INFORMATION AND SHOULD PROVIDE THE BASIS FOR THE
 RECORD DRAWINGS REQUIRED ELSEWHERE IN THIS CODE.
 CONTENT. SHOP DRAWINGS SHOULD INCLUDE, TO AN EXTENT
 COMMENSURATE
 WITH THE EXTENT OF THE WORK BEING PERFORMED, FLOOR PLAN
 DRAWINGS, RISER DIAGRAMS, CONTROL PANEL WIRING
 DIAGRAMS, POINT-TOPOINT
 WIRING DIAGRAMS, CONDUIT, CONDUCTOR ROUTING, TYPICAL
 WIRING
 DIAGRAMS, AND OTHER INFORMATION AS DESCRIBED HEREIN.
 ALL SHOP DRAWINGS SHOULD BE DRAWN ON SHEETS OF UNIFORM
 SIZE AND SHOULD INCLUDE THE FOLLOWING INFORMATION:
 (1) NAME OF PROTECTED PREMISES, OWNER, AND OCCUPANT
 (WHERE
 APPLICABLE)
 (2) NAME OF INSTALLER OR CONTRACTOR
 (3) LOCATION OF PROTECTED PREMISES
 (4) DEVICE LEGEND IN ACCORDANCE WITH NFPA 170, STANDARD
 FOR
 FIRE SAFETY AND EMERGENCY SYMBOLS
 (5) DATE OF ISSUE AND ANY REVISIONS
  
  
  
 2) THERE IS INSUFFICIENT DETAILS OF THE SYSTEM AND IT'S
 COMPONENTS INDICATED.
  
 PLEASE PROVIDE SYSTEM DETAILS
  
  
  
 3) THERE IS NO INDICATIONS OF A RISER DIAGRAM WITH ALL
 DEVICES, CIRCUITS, POWER CONNECTIONS AND INTERFACES.
  
 FIRE ALARM SYSTEM RISER DIAGRAMS SHOULD INCLUDE THE
 FOLLOWING
 INFORMATION:
 (1) GENERAL ARRANGEMENT OF THE SYSTEM IN BUILDING
 CROSS-SECTION
 (2) NUMBER OF RISERS
 (3) TYPE AND NUMBER OF CIRCUITS IN EACH RISER
 (4) TYPE AND NUMBER OF FIRE ALARM SYSTEM COMPONENTS/
 DEVICES ON EACH CIRCUIT, ON EACH FLOOR OR LEVEL
 (5) TYPE AND QUANTITY OF CONDUCTORS AND CONDUIT (IF
 USED) FOR
 EACH CIRCUIT
  
 PLEASE PROVIDE.
  
  
 4) THERE ARE NO VOLTAGE DROP CALCULATIONS.
  
 PLEASE PROVIDE
  
  
 5) THERE ARE NO BATTERY CALCULATIONS.
  
 PLEASE PROVIDE.
  
  
 6) THERE ARE DEVICE/EQUIPMENT SPECIFICATION SHHEETS.
  
 PLEASE PROVIDE.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-07 Cont ID  
Sent By jpearson Date 2017-11-07 Time 09:57 Rev Time 0.00
Received By jpearson Date 2017-10-26 Time 10:04 Sent To  
Notes
2017-10-27 10:04:43ROUTED TO FIRE INBOX