2017-10-27 13:20:32 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| INFORMATION: THERE IS INDICATION OF A CERTIFIED FIRE |
| ALARM CONTRACTOR THAT IS DOING THE WORK. THOUGH A TBD |
| PERMIT CAN BE PASSED AND HELD FOR A QUALIFING |
| CONTRACTOR THERE ARE OTHER CONCERNS WITH THIS PLAN SET |
| THAT NEED TO BE ADDRESSED. |
| |
| |
| 1) THESE ARE NOT SHOP DRAWINGS. |
| |
| PER NFPA 13 |
| |
| 3.3.238 SHOP DRAWINGS. DOCUMENTS THAT PROVIDE |
| INFORMATION |
| PERTAINING TO THE SYSTEM, SUCH AS PROPERTY LOCATION, |
| SCALED |
| FLOOR PLANS, EQUIPMENT WIRING DETAILS, TYPICAL |
| EQUIPMENT INSTALLATION |
| DETAILS, RISER DETAILS, CONDUIT/CONDUCTOR SIZE AND |
| ROUTING INFORMATION, AND OTHER INFORMATION NECESSARY |
| FOR THE |
| INSTALLER TO COMPLETE THE FIRE ALARM INSTALLATION. |
| |
| 10.18 DOCUMENTATION. |
| 10.18.1 APPROVAL AND ACCEPTANCE. |
| 10.18.1.1 THE AUTHORITY HAVING JURISDICTION SHALL BE |
| NOTIFIED |
| PRIOR TO INSTALLATION OR ALTERATION OF EQUIPMENT OR |
| WIRING. |
| 10.18.1.2* AT THE AUTHORITY HAVING JURISDICTION?S |
| REQUEST, COMPLETE |
| INFORMATION REGARDING THE SYSTEM OR SYSTEM ALTERATIONS, |
| INCLUDING SPECIFICATIONS, TYPE OF SYSTEM OR SERVICE, |
| SHOP DRAWINGS, |
| INPUT/OUTPUT MATRIX, BATTERY CALCULATIONS, AND |
| NOTIFICATION |
| APPLIANCE CIRCUIT VOLTAGE DROP CALCULATIONS, SHALL BE |
| SUBMITTED |
| FOR APPROVAL. |
| |
| GENERAL. SHOP DRAWINGS FOR FIRE ALARM SYSTEMS SHOULD |
| PROVIDE |
| BASIC INFORMATION AND SHOULD PROVIDE THE BASIS FOR THE |
| RECORD DRAWINGS REQUIRED ELSEWHERE IN THIS CODE. |
| CONTENT. SHOP DRAWINGS SHOULD INCLUDE, TO AN EXTENT |
| COMMENSURATE |
| WITH THE EXTENT OF THE WORK BEING PERFORMED, FLOOR PLAN |
| DRAWINGS, RISER DIAGRAMS, CONTROL PANEL WIRING |
| DIAGRAMS, POINT-TOPOINT |
| WIRING DIAGRAMS, CONDUIT, CONDUCTOR ROUTING, TYPICAL |
| WIRING |
| DIAGRAMS, AND OTHER INFORMATION AS DESCRIBED HEREIN. |
| ALL SHOP DRAWINGS SHOULD BE DRAWN ON SHEETS OF UNIFORM |
| SIZE AND SHOULD INCLUDE THE FOLLOWING INFORMATION: |
| (1) NAME OF PROTECTED PREMISES, OWNER, AND OCCUPANT |
| (WHERE |
| APPLICABLE) |
| (2) NAME OF INSTALLER OR CONTRACTOR |
| (3) LOCATION OF PROTECTED PREMISES |
| (4) DEVICE LEGEND IN ACCORDANCE WITH NFPA 170, STANDARD |
| FOR |
| FIRE SAFETY AND EMERGENCY SYMBOLS |
| (5) DATE OF ISSUE AND ANY REVISIONS |
| |
| |
| |
| 2) THERE IS INSUFFICIENT DETAILS OF THE SYSTEM AND IT'S |
| COMPONENTS INDICATED. |
| |
| PLEASE PROVIDE SYSTEM DETAILS |
| |
| |
| |
| 3) THERE IS NO INDICATIONS OF A RISER DIAGRAM WITH ALL |
| DEVICES, CIRCUITS, POWER CONNECTIONS AND INTERFACES. |
| |
| FIRE ALARM SYSTEM RISER DIAGRAMS SHOULD INCLUDE THE |
| FOLLOWING |
| INFORMATION: |
| (1) GENERAL ARRANGEMENT OF THE SYSTEM IN BUILDING |
| CROSS-SECTION |
| (2) NUMBER OF RISERS |
| (3) TYPE AND NUMBER OF CIRCUITS IN EACH RISER |
| (4) TYPE AND NUMBER OF FIRE ALARM SYSTEM COMPONENTS/ |
| DEVICES ON EACH CIRCUIT, ON EACH FLOOR OR LEVEL |
| (5) TYPE AND QUANTITY OF CONDUCTORS AND CONDUIT (IF |
| USED) FOR |
| EACH CIRCUIT |
| |
| PLEASE PROVIDE. |
| |
| |
| 4) THERE ARE NO VOLTAGE DROP CALCULATIONS. |
| |
| PLEASE PROVIDE |
| |
| |
| 5) THERE ARE NO BATTERY CALCULATIONS. |
| |
| PLEASE PROVIDE. |
| |
| |
| 6) THERE ARE DEVICE/EQUIPMENT SPECIFICATION SHHEETS. |
| |
| PLEASE PROVIDE. |
| |
| |
| 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| |
| |