Plan Review Details - Permit 17101049
Plan Review Stops For Permit 17101049
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-09 Cont ID  
Sent By cthroop Date 2017-11-09 Time 11:21 Rev Time 0.00
Received By cthroop Date 2017-11-09 Time 11:14 Sent To E
Notes
2017-11-09 11:26:14BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SEE NOTE 1, PAGE 3. DESIGN SHALL BE BY A FLORIDA
 LICENSED PROFESSIONAL ENGINEER.
 2. EOR TO SIGN AND SEAL DESIGN.
 3. SEE NOTE 1, PAGE 3. CODE REFERENCE SHALL BE THE 2014
 FBC.
 4. PROVIDE DESIGN WIND LOADS FOR CHANNEL LETTERS.
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-09 Cont ID  
Sent By jleahy Date 2017-11-09 Time 13:16 Rev Time 0.00
Received By jpearson Date 2017-11-09 Time 13:16 Sent To I
Notes
2017-11-09 13:16:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
 2. PROVIDE NOTE THAT NO ELECTRICAL WILL BE INSTALLED TO
 THIS SIGN. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-09 Cont ID  
Sent By jpearson Date 2017-11-09 Time 13:16 Rev Time 0.00
Received By jpearson Date 2017-10-25 Time 08:10 Sent To  
Notes
2017-10-27 08:10:31REVISION ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2017-11-07 Cont ID  
Sent By ajones Date 2017-11-07 Time 11:40 Rev Time 0.00
Received By ajones Date 2017-10-31 Time 11:26 Sent To B
Notes
***NONE***