Plan Review Details - Permit 17100938
Plan Review Stops For Permit 17100938 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-11-16 |
Time |
13:53 |
Sent To |
|
|
Notes |
2017-11-20 13:53:52 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2017-11-15 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-11-09 |
Time |
09:24 |
Sent To |
|
|
Notes |
2017-11-13 09:24:53 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2017-10-27 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-10-23 |
Time |
10:32 |
Sent To |
|
|
Notes |
2017-10-24 10:32:22 | MECH <5K |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2017-11-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-11-21 |
Time |
13:13 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-11-21 |
Time |
13:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2017-11-15 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-11-15 |
Time |
09:28 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-11-15 |
Time |
09:28 |
Sent To |
|
|
Notes |
2017-11-15 09:34:39 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17100938 | | 11/15/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE DUCT DROP INTO THE NEW UTILITY ROOM IS NOT | | SHOWN- SEE THE AC CALCULATIONS WHICH CALL OUT A 5" DUCT | | SUPPLYING 84 CFMS OF COOLING AND 39 CFMS OF HEATING. | | | | 2) TWO SETS OF ENERGY AND AC CALCULATIONS MUST BE | | PROVIDED- ONLY ONE SET OF EACH WAS SUBMITTED- SECTTION | | 107.2.1 WPB AMENDMENTS TO THE FBC | | | | 2) 2ND REQUEST FOR SIGNATURE OF DESIGNER/CONTRACTOR ON | | PLAN. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2017-10-27 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-10-27 |
Time |
12:44 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-10-27 |
Time |
11:51 |
Sent To |
|
|
Notes |
2017-10-27 13:00:53 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | PERMIT #17100938 | | 10/27/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE NEW UTILITY ROOM IS DEFINED AS AN ADDITION | | ACCORDING TO SECTION R202 FBC-14 ENERGY CONSERVATION. | | PLEASE PROVIDE AN ENERGY COMPLIANCE SUBMITTAL USING | | EITHER THE THERMAL ENVELOPE ALTERNATIVE OR PERFORMANCE | | COMPLIANCE METHOD- SEE R101.5.1.1. | | | | 2) SUBMIT MANUFACTURER'S SPECIFCATIONS FOR THE GAS | | DRYER AND PROVIDE COMBUSTION AIR CALCULATIONS- SECTION | | G2407.1. FBC-14 RESIDENTIAL. | | | | 3) SIGNATURE OF CONTRACTOR OR QUALIFIER ON PLANS | | REQUIRED- SECTION 107.2.1 FBC. WPB AMENDMENTS TO THE | | FBC: ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
|