Plan Review Details - Permit 17100938
Plan Review Stops For Permit 17100938
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-11-16 Time 13:53 Sent To  
Notes
2017-11-20 13:53:52RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-11-15 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-09 Time 09:24 Sent To  
Notes
2017-11-13 09:24:53RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-10-27 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-23 Time 10:32 Sent To  
Notes
2017-10-24 10:32:22MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-11-21 Cont ID  
Sent By ccole Date 2017-11-21 Time 13:13 Rev Time 0.00
Received By ccole Date 2017-11-21 Time 13:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-11-15 Cont ID  
Sent By ccole Date 2017-11-15 Time 09:28 Rev Time 0.00
Received By ccole Date 2017-11-15 Time 09:28 Sent To  
Notes
2017-11-15 09:34:392ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17100938
 11/15/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DUCT DROP INTO THE NEW UTILITY ROOM IS NOT
 SHOWN- SEE THE AC CALCULATIONS WHICH CALL OUT A 5" DUCT
 SUPPLYING 84 CFMS OF COOLING AND 39 CFMS OF HEATING.
  
 2) TWO SETS OF ENERGY AND AC CALCULATIONS MUST BE
 PROVIDED- ONLY ONE SET OF EACH WAS SUBMITTED- SECTTION
 107.2.1 WPB AMENDMENTS TO THE FBC
  
 2) 2ND REQUEST FOR SIGNATURE OF DESIGNER/CONTRACTOR ON
 PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-27 Cont ID  
Sent By ccole Date 2017-10-27 Time 12:44 Rev Time 0.00
Received By ccole Date 2017-10-27 Time 11:51 Sent To  
Notes
2017-10-27 13:00:531ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17100938
 10/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW UTILITY ROOM IS DEFINED AS AN ADDITION
 ACCORDING TO SECTION R202 FBC-14 ENERGY CONSERVATION.
 PLEASE PROVIDE AN ENERGY COMPLIANCE SUBMITTAL USING
 EITHER THE THERMAL ENVELOPE ALTERNATIVE OR PERFORMANCE
 COMPLIANCE METHOD- SEE R101.5.1.1.
  
 2) SUBMIT MANUFACTURER'S SPECIFCATIONS FOR THE GAS
 DRYER AND PROVIDE COMBUSTION AIR CALCULATIONS- SECTION
 G2407.1. FBC-14 RESIDENTIAL.
  
 3) SIGNATURE OF CONTRACTOR OR QUALIFIER ON PLANS
 REQUIRED- SECTION 107.2.1 FBC. WPB AMENDMENTS TO THE
 FBC: ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  